You are on page 1of 1

Section Three

Low Voltage Cables

TWO CORE & EARTH CU REMOLEX CABLES


Circular construction
Copper conductor
PVC insulation
PVC sheath
Current ratings (A) and voltage drops (mV/A.m)

Product Sheet No. 021-02 B


Conductor Size

(mm2)

(A)

(mV/A.m)

(A)

(mV/A.m)

1.5

21

33.0

22

33.0

2.5

30

18.0

31

18.0

39

11.2

42

11.2

50

7.50

52

7.50

10

68

4.46

73

4.46

Issue: January 2012


450/750 V. Made to AS/NZS 5000.2
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C

Section 3, Page 52