You are on page 1of 1

Section Three

Low Voltage Cables

FOUR CORE CU PVC NEUTRAL SCREEN CABLES


Circular construction
Copper conductor
PVC insulation
Copper neutral screen
PVC sheath
Current ratings (A) and voltage drops (mV/A.m)

Product Sheet No. 080-04 B


Conductor
Size
(mm2)

(A)

(mV/A.m)

(A)

(mV/A.m)

(A)

(mV/A.m)

(A)

(mV/A.m)

2.5

25

15.6

26

15.6

28

15.6

28

15.6

33

9.71

35

9.71

36

9.71

36

9.71

42

6.49

46

6.49

46

6.49

46

6.49

10

58

3.86

62

3.86

61

3.86

61

3.86

16

78

2.43

82

2.43

106

2.43

80

2.43

Issue: September 2012


0.6/1 kV. Made to AS/NZS 4961
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C
Soil Temperature
15C
Soil Thermal Resistivity
1.2 K.m/W
Depth of Burial
0.5 m

Section 3, Page 34