You are on page 1of 32

CONDENSATION RECOVERY

QURANIC GIRL INTERMEDIATE SCHOOL CASE STUDY, JUBAIL KINGDOM OF


SAUDI ARABIA

PREPARED BY:
MUDASSAR IDRIS RAUT LEED GREEN ASSOCIATE
Mechanical Engineer
Email Id:mudassaridris.raut@gmail.com

1.1 ABSTRACT
The biggest reliable source of potable water in Saudi Arabia is from Desalination Water
treatment. Since Ground source water resources are very minimal due to geographical location,
country largest demand depends on Desalination water from Sea. However the production cost to
convert saline water to Potable water is considerable [1.09 US$ per cubic meter]. Since water is
very crucial for daily activities & converting Saline Water into potable consume ample amount of
energy & money, it obviously increases an alarm to reduce water consumption at site & look for
other replaceable derivatives which can replace Potable water intake from Municipal Bodies. The
Saudi Minister of Water & Electricity estimated that 25% of Saudi Oil & Gas Production in fiscal yr.
2009 was used domestically to generate electricity & produce water, with present demand rates
suggesting that this figure will reach 50% by yr. 2030 as per research by [BELFER CENER for science
& International Affair].
To focus on this cause Mechanical Engineering Division of Abdul Al Rahman AL Naim
Consultant- Dammam has developed a conceptual design for Water Reclaim use at Quranic School
Project- a Royal Commissioning Project in Jubail, Kingdom Of Saudi Arabia.

1.2 BACKGROUND STUDY ON CONDENSATION


Proposed HVAC system designed is of Chilled Water System where in there are 5 Nos Air
Handling Unit used in Girl Intermediate School & 2 Nos Air Cooled Chillers. Since this schools are
located in Jubail where there is enough amount of humidity present in air, the water present can
be used after condensation. As per ASHRAE [American Society Heating Refrigeration & Air
Conditioning Engineers] standards school requires larger amount of outside air to main inside
school environment healthy. Now this outside brings large load on Air Handlers Cooling Coils in
turn increasing the amount of moist air passing through these Coils. As this air passes through
these coil, temperature of air drops as a result the air can no longer holds the amount of moisture
as it was holding when it was relatively hot. This process can easily be understood in Psychometric
analysis of Air handling units. As a result the moisture present in moist air drops off & this entire
process is called Condensation. Note that not all the moisture present in moist air drops as there
is still resultant moisture present in air leaving the cooling coil. The exact theoretical amount of
moisture required depends on Indoor Desired room condition: - In this case we are maintaining
50% relative humidity as commanded by ASHRAE standards for school project & it also complying
with our client Royal Commission Design basis Reports [DBR]. This process is explained in below
fig. 1.1

PAGE 1

Fig: 1.1

1.3 WHAT IS CONDENSATE WATER?


Condensate is a byproduct generated during Air Conditioning process which is
usually wasted & drained to sewer. Condensate is generated in the same manner as distilled
water, which has a slightly acidic pH value around 5.8, as compared to a neutral pH value of 7.0,
and contains no minerals. However, unlike distilled water, condensate is subject to environmental
contamination during the process of collection and transport. Microorganisms (e.g., bacteria and
viruses) suspended in air drawn from inside and/or outside the building (i.e., return air and/or
outside air) through the Air Handling Unit (AHU) can collect on the cooling coils with the moisture
when condensate is formed (see Fig 1.1 for a schematic of an AHU). In addition, being slightly acidic,
condensate tends to react with materials with which it comes in contact. Such reactions can raise
the pH value of condensate. Any molecules or particulates the condensate picks up during
formation or along its flow path can be referred to as a contaminant and must be considered when
making treatment decisions.

PAGE 2

1.4 ACCUSTOMED CONDENSATE PRACTICES


Largely the condensate collected is discarded through various drain points & dumped into
normal sewers. This not only waste this high valuable clean Distilled water but also adds loads in
Sewer Treatment Plant on Local municipal bodies thus increasing additional Energy & Cost factors
to the Government. This not only burden the Government organization but also results in
additional GHG [Greenhouse Gas] emission into environment.

Fig: 1.2

PAGE 3

1.5 CONDENSATE WATER APPLICATION


Can be used in 3 main Domain.
1. COOLING TOWERS.
2. TOILET FLUSHING.
3. LANDSCAPE IRRIGATION & HARDSCAPE CLEANING.
The most effective use of condensate water collected from commercial or industrial
buildings is for makeup water in cooling towers. This is because the pure and cool condensate water
dilutes the sediment buildup in cooling towers (the sediment is left behind during the evaporative
cooling process), increases the efficiency of the cooling towers by virtue of its relatively cool
temperature, provides the most water in hot and humid conditions when makeup water for the
cooling towers is most needed, and requires no additional storage or treatment.
Other common uses of condensate include toilet flushing, irrigation, ornamental water features,
and process water, such as that used in manufacturing. Designing for these uses requires a water
budget to determine how much water is produced (supplied) versus how much is required
(demanded) for the intended purpose. Storage is required if the water produced cannot be
immediately used for its intended purpose. This is the case with most applications except for
cooling towers and perhaps some process water and irrigation applications, depending on exact
needs. Treatment in the form of filtration and disinfection is used to raise the quality of the water
for its intended application. Applications in which reclaimed water could conceivably come in
contact with human skin or be ingested require the highest-quality water. In all cases, a welldesigned and well-maintained HVAC system is critical to the production of condensate that is free
of microbial buildup or other contaminants
Except for Cooling Tower usage, local codes or AHJ Authority Having Jurisdiction & International
Code like IPC, IBC should be followed if condensate water is to be used for application involving
direct human contact or some time ingestion. Also a detail water report must be conducted on
monthly basis to study the acidic nature or micro Organism growth of condensate collected for
other uses. Because this acidic nature may harm the Toilet ceramic if repeatedly used or it may
harm landscape, Lawn Sprinklers, Drip irrigation pipes, Pumps, Fountains etc. For best result a
strict maintenance of AHU equipment is required on weekly/monthly basis from Maintenance &
Operation Contractor.
BECAUSE THERE ARE NO COOLING TOWERS IN QURANIC PROJECT, OPTION-2 & OPTION3 ARE LEFT TO BE IMPLEMENTED. HOWEVER PROPOSED CONCEPT IN THIS REPORT IS
OPTION-2 i.e TOILET FLUSHING

PAGE 4

1.6 HOW MUCH CONDENSATE WATER CAN QURANIC


INTERMEDIATE SCHOOL GIVE?
There are 5 Nos AHU in Quranic Girl Intermediate School & condensate generated in
Gallons by these AHUS are given in below Table 1.1.
There are various technique to capture condensate Flow Volume & Engineers & researchers have
developed certain Thumb rules even based on Tonnage & Sq Ft Area to be Air Conditioned.
However we have captured theoretical data from HAP [Hourly Analysis Program] Software based
on thermodynamic relation below.

QC= Qa X DENSITY X (W1-W2) X 0.45 X 0.2641 X 60----Where,

QC Gallons/Hr. of Condensate.
Qa = Air Flow rate of mixed air [Return + Outdoor] in CFM
Density - Stds Density of Air = 0.075 lb/ft3 at atmospheric Pressure.
W1 - Specific humidity of Mix Air Entering Cooling Coil.
W2 Specific humidity of Cool Air Leaving Cooling Coil.
& 0.45, 0.2641 & 60 are conversion factors to be used to get values in Gallon/Hr.

PAGE 5

AHU-01

AHU-02

AHU-03

AHU-04

AHU-05

JAN

2,769

3,028

3,137

3,151

2,073

FEB

4,789

6,900

6,051

6,227

4,224

MAR

4,194

5,674

5,942

5,939

3,839

APR

4,103

5,743

6,010

5,969

3,756

MAY

5,072

7,837

7,977

7,761

4,745

JUN

6,047

9,502

9,926

9,597

5,794

JUL

1,373

2,158

2,256

2,182

1,317

AUG

6,007

9,468

9,922

9,612

5,787

SEP

3,445

5,266

5,523

5,470

3,273

OCT

6,425

9,388

9,823

9,134

5,990

NOV

5,890

8,042

8,390

8,457

5,422

DEC

2,515

3,034

3,147

3,275

2,212

52,629

76,039

78,104

76,772

48,431

TOTAL
GALLONS/YR BY
AHU
TOTAL
GALLONS/YR BY
ENTIRE SCHOOL

331,977 GALLONS/YR

Table: 1.1

PAGE 6

Fig: 1.3

1.7 CONDENSATE CALCULATION PROCEDURE


Temperature Simulation file of Jubail is recorded from HAP file. The hottest day in particular
month is recorded for which the condensation is calculated. The Maximum & minimum Dry Bulb
temperature is recorded from HAP file for which W1 & W2 is recorded. Also in spite of recording
24 hrs. data for entire day only 13 hrs.[From 5 AM to 5 PM] data is recorded for that particular
hottest day in a particular month. 13 hrs. data is then added to get daily data & finally this Hottest
day data is multiplied with 70% diversity factor assuming all the condensate generated for
remaining days will always generate less amount of condensate. Also it is assume that each month
have 30 days immaterial of JFMAMJJASOND series. This all assumption are just for ease in
calculation as hourly condensate generated for all 365 days will take ample amount of time &
perhaps the exact & correlated values will have minimal variations.
W1 & W2 is recorded for every 13 hr. from HAP Psychometric Analysis procedures which shows
every 13 hrs. in every single month. Based on these value & Air flow rate of particular AHU the final
Qc value is recorded for every Single hours in those 13 hrs. study. Then all 13 hrs. resulted are
summoned up to get final day value of condensate on that particular day.

PAGE 7

Sample Calculation for January month for AHU-3 is as shown Below in Table-1.2

JAN

TIME

W1 @ TM

W2 @ T0

500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700

0.00864
0.01105
0.01105
0.01107
0.01104
0.01104
0.01102
0.01103
0.01101
0.011
0.00864
0.00807
0.00806

0.00769
0.00879
0.00874
0.00877
0.00869
0.00869
0.00864
0.00863
0.0086
0.0086
0.00764
0.00763
0.00765

LPM GPM GPH


0.52
1.24
1.27
1.27
1.29
1.29
1.31
1.32
1.33
1.32
0.55
0.24
0.23

0.14
0.33
0.34
0.33
0.34
0.34
0.35
0.35
0.35
0.35
0.15
0.06
0.06

8.29
19.73
20.16
20.08
20.51
20.51
20.77
20.95
21.04
20.95
8.73
3.84
3.58

GPD

MONTHLY

209.14

3137.17

Table: 1.2

LPM- Liters Per Minute


GPM Gallon Per Minute
GPH- Gallon Per Hour
GPD- Gallon Per Day
To Get Monthly data, peak load Condensation value is multiplied with Occupied Days of that
particular month [In above case January is noted (See Section 1.8).
In a similar way rest of the month data were recorded to get the results of yearly package. This data
capturing is done form all 5 Nos AHU to get the condensate generated for Entire Quranic
Intermediate School. Now as depicted from above calculation & Table-1.1 we have achieved 331,977
Gallons of Condensate.
Note that this condensate value is only theoretical figure & actual value in practice may be
low or more than this. So in order to get full proof value we have assume 50% diversity factor on
this overall value as we cannot ensure that 441,000 Gallons of condensate generated is actually
feasible at site. This final assumption is due below discussed reasons.
1. Nature is highly unpredicted as we cannot ascertain the values of Specific humidity W1 &
W2 we have entered from HAP analysis is exactly possible at site.

PAGE 8

2. The above data is when the building is occupied on full load & all Chillers are running on
peak Load. But this usually happens for only small amount of time & most of the time the
building is HVAC system is not running on full load.
3. AHU cooling coils must be perfectly clean & well maintained through the year as we cannot
guarantee the Exact Condensate generated with Poor maintained Cooling Coil.
HVAC CONDENSATION COMPARISION BETWEEN THEOROTICAL &
50% DIVERSITY FOR QURANIC GIRL INTERMEDIATE SCHOOL

70,000

40,866

40,795

40,759

60,000

36,200

40,000

GALLONS

33,393

50,000

28,191
25,588

25,582
22,977

30,000
14,158

20,000
10,000

20,433

20,398

20,380

16,696
14,095

12,794

9,286

12,791

7,079

14,182
18,100

11,488
7,091

4,643

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

MONTHS

Fig: 1.4

Moreover under worst case scenario even if we fail to get enough condensate, the proposed design
system by ACE Consultant is flexible enough to take in account Potable water as a back water to
flush the toilets. So the proposed design ensures that Human Comfort will not be disturbed by
implanting Condensate Water system for water flushing. So for Royal Commission its a Win-Win
situation where in they can not only save Water used at site but also end up in paying Less Water
& Tax to Govt municipal Bodies.
Fig-1.4 shows a comparison between theoretical & diversified Condensate values.50% diversity is
just a factor of safety to cushion our design & real-time values at site may exceed this diversity
factor.

PAGE 9

DEC

1.8 SCHOOL HOLIDAYS


SEP 9 TO SEP 17---------EID AL ADHA HOLIDAYS
DEC-16 TO JAN- 7----------WINTER BREAK
MARCH 24 TO APRIL 8-----SPRING BREAK
JUNE 20 TO JULY 29 ---------SUMMER BREAK
Above holiday structure is taken from KAUST[King Abdulla University of Science & TechnologyThuwal]. Although holiday structure of University is followed, this holiday structure is subjected
to change as per Royal Commission School guidelines.

For all these holidays, school is considered to be completely shut down where in there is no
HVAC Equipment running & also there is no Occupant load in School to use Toilet Flushing. Also
it is assume that a month will have only 22 days of occupancy excluding all weekend.
Note that for this reason among 3 Basic uses of condensate water , we have opted to use condensate
water for Toilet Flushing because even if school is shut down we need water to maintain Landscape
but on contrary we dont need water to flush toilets as there is no Occupant Load in toilets during
vacation period.
A detailed graphical representation will help in explaining the Holiday Structure & Occupancy
Load. It is quite important to note at this stage, for Water budget estimating for flushing, we will
use this same occupancy load to balance demand water for Toilet flushing with produced
condensate water.

PAGE 10

Fig: 1.5

1.9 WATER BUDGET

One of the prime motive to develop water budget is to estimate the Water demand used for
flushing of Water Closet. We are using highly efficient Toilets in this school with flush rate ranging
from 0.8-1.28 Gallons/Flush.
Quranic Girl Intermediate School is divided into 5 Zones for both HVAC & plumbing
Calculations. The detail Sub-Division of these zone is shown below in figure-1.51

PAGE 11

Fig: 1.51

Total number of Water Closet in all Zones & their respective demand Flow volume is as shown in
Table-1.31 & Total Flushing Demand for Entire School/monthly is shown in Table-1.32

PAGE 12

NO'S OF
WATER
CLOSET
5

0.8

246

738

590

0.8

246

738

590

0.8

225

675

540

0.8

20

60

48

ZONE

GALLONS/
FLUSH

NO OF OCCUPANT

Flush/
Person/Day

Flush/Day/
Zone

Gallons/Day/
Zone

0.8

20

60

48

Table: 1.31

Gallons/

Gallons/

Gallons/

Gallons/

Gallons/

MONTH

NO OF
OCCUPIED
DAYS

Month
ZONE-A

Month
ZONE-B

Month
ZONE-C

Month
ZONE-D

Month
ZONE-E

JAN

15

720

8,850

8,850

8,100

720

FEB

22

1,056

12,980

12,980

11,880

1,056

MAR

15

720

8,850

8,850

8,100

720

APR

14

672

8,260

8,260

7,560

672

MAY

22

1,056

12,980

12,980

11,880

1,056

JUN

22

1,056

12,980

12,980

11,880

1,056

JUL

240

2,950

2,950

2,700

240

AUG

22

1,056

12,980

12,980

11,880

1,056

SEP

11

528

6,490

6,490

5,940

528

OCT

22

1,056

12,980

12,980

11,880

1,056

NOV

22

1,056

12,980

12,980

11,880

1,056

DEC

12

576

7,080

7,080

6,480

576

9,792

120,360

120,360

110,160

9,792

TOTAL GALLONS/YR/
ZONE
TOTAL GALLONS/YR
FOR ENTIRE SCHOOL

370,464

Table: 1.32

PAGE 13

1.91 DETAIL WATER BUDGET CALCULATION OF ZONEA FOR JANUARY MONTH


Assuming 3 flushes/day/student or staff in Girl Intermediate School
Toilet Flush & Gallons used in ZONE-A:
No of occupant = 20
Flush/person/day = 3
Flush/Day/Zone = 20 x 3 = 60
Gallons/Day = 60 x 0.8 = 48
No of Occupied days in January Month = 15 Days
Total Demand Gallons/month = 15 x 48 = 720 Gallons-----------A
Available Gallons of Condensate Generated in January month for this Zone
2769 Gallons-----------------B
Assuming 50% diversity factor as discussed above in section 1.7
Total Supply Condensate = 2769 x 0.5 = 1385---------------C
[Please read Point 1,2,3 in section 1.7 to know more about this Diversity Factor]

From Equ-A & Equ-C its clear that Condensate generated is enough to take all the flushes
assumed & still 1385-720= 665 Gallons will be left unused for any uncertain demand.

This explains that condensate generated in January Month for Zone-A in GIRL
INTERMEDIATE SCHOOL IS SUFFICIENT TO FLUSH THESE TOILETS

1.92 DETAIL WATER BUDGET CALCULATION OF ZONEB FOR JANUARY MONTH


Assuming 3 flushes/day/student or staff in Girl Intermediate School
Toilet Flush & Gallons used in ZONE-B:
No of occupant = 246
PAGE 14

Flush/person/day = 3
Flush/Day/Zone = 246 x 3 = 738
Gallons/Day = 738 x 0.8 = 591
No of Occupied days in January Month = 15 Days
Total Demand Gallons/month = 15 x 591 = 8856 Gallons-----------A
Available Gallons of Condensate Generated in January month for this Zone
3028 Gallons-----------------B
Assuming 50% diversity factor as discussed above in section 1.7
Total Supply Condensate = 3028 x 0.5 = 1514---------------C
[Please read Point 1,2,3 in section 1.7 to know more about this Diversity Factor]

From Equ-A & Equ-C its clear that Condensate generated is not enough to take all the
flushes assumed & still 8856-1328= 7528 Gallons will be additional demand.

This explains that condensate generated in January Month for Zone-B in GIRL
INTERMEDIATE SCHOOL IS NOT SUFFICIENT TO FLUSH THESE TOILETS

1.93 DETAIL WATER BUDGET CALCULATION OF ZONEC FOR JANUARY MONTH


Assuming 3 flushes/day/student or staff in Girl Intermediate School
Toilet Flush & Gallons used in ZONE-C:
No of occupant = 246
Flush/person/day = 3
Flush/Day/Zone = 246 x 3 = 738
Gallons/Day = 738 x 0.8 = 591
No of Occupied days in January Month = 15 Days
Total Demand Gallons/month = 15 x 591 = 8856 Gallons-----------A

PAGE 15

Available Gallons of Condensate Generated in January month for this Zone


3137 Gallons-----------------B
Assuming 50% diversity factor as discussed above in section 1.7
Total Supply Condensate = 3137 x 0.5 = 1569---------------C
[Please read Point 1,2,3 in section 1.7 to know more about this Diversity Factor]

From Equ-A & Equ-C its clear that Condensate generated is not enough to take all the
flushes assumed & still 8856-1569= 7287 Gallons will be additional demand.

This explains that condensate generated in January Month for Zone-C in GIRL
INTERMEDIATE SCHOOL IS NOT SUFFICIENT TO FLUSH THESE TOILETS

1.94 DETAIL WATER BUDGET CALCULATION OF ZONED FOR JANUARY MONTH


Assuming 3 flushes/day/student or staff in Girl Intermediate School
Toilet Flush & Gallons used in ZONE-D:
No of occupant = 225
Flush/person/day = 3
Flush/Day/Zone = 225 x 3 = 675
Gallons/Day = 675 x 0.8 = 540
No of Occupied days in January Month = 15 Days
Total Demand Gallons/month = 15 x 540 = 8100 Gallons-----------A
Available Gallons of Condensate Generated in January month for this Zone
3151 Gallons-----------------B
Assuming 50% diversity factor as discussed above in section 1.7
Total Supply Condensate = 3151 x 0.5 = 1575.5---------------C
[Please read Point 1,2,3 in section 1.7 to know more about this Diversity Factor]

PAGE 16

From Equ-A & Equ-C its clear that Condensate generated is not enough to take all the
flushes assumed & still 8100-1575.5= 6524.5 Gallons will be additional demand.

This explains that condensate generated in January Month for Zone-D in GIRL
INTERMEDIATE SCHOOL IS NOT SUFFICIENT TO FLUSH THESE TOILETS

1.95 DETAIL WATER BUDGET CALCULATION OF ZONEE FOR JANUARY MONTH


Assuming 3 flushes/day/student or staff in Girl Intermediate School
Toilet Flush & Gallons used in ZONE-E:
No of occupant = 20
Flush/person/day = 3
Flush/Day/Zone = 20 x 3 = 60
Gallons/Day = 60 x 0.8 = 48
No of Occupied days in January Month = 15 Days
Total Demand Gallons/month = 15 x 48 = 720 Gallons-----------A
Available Gallons of Condensate Generated in January month for this Zone
2073 Gallons-----------------B
Assuming 50% diversity factor as discussed above in section 1.7
Total Supply Condensate = 2073 x 0.5 = 1037---------------C
[Please read Point 1,2,3 in section 1.7 to know more about this Diversity Factor]

From Equ-A & Equ-C its clear that Condensate generated is enough to take all the flushes
assumed & still 1037-720= 317 Gallons will be left unused for any uncertain demand.

PAGE 17

This explains that condensate generated in January Month for Zone-E in GIRL
INTERMEDIATE SCHOOL IS SUFFICIENT TO FLUSH THESE TOILETS

CONCLUSION: CONDENSATE GENERATED IN ZONE-A & ZONE-B IS SUFFICIENT TO


COVER ALL THE FLUSHING DEMANDS DUE TO LOW OCCUPANT LOAD BUT
CONDENSATE GENERATED IN ZONE-B,C,D IS NOT SUFFICIENT TO MEET THE FLUSHING
DEMAND DUE TO HIGH OCCUPANT LOAD

The Demand curve vs Condensate to support flushing Demand for all the zone is shown
below in Fig:1.6

ZONE-A
3,000

2409

2,500

GALLONS

2268

2,000

2253

2209

1902

1796
1573

1539

1,500

1292
1038

1,056

1,056

1,056

1,056

1,056

1,056

1,000
720

720

672

500

576

528

515

943

240

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

MONTH

PAGE 18

DEC

ZONE-B
14,000
12,980

12,980

12,980

12,980

12,980

12,980

12,000

10,000

GALLONS

8,850

8,850
8,260

8,000

7,080
6,490

6,000
4,751
4,000
3,450
2,837
2,000

4,734

4,694
4,021

3,919
2,950

2,871

1,514

2,633
1,517

1,079

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

MONTH

ZONE-C

Fig: 1.6

14,000

12,980

12,980

12,980

12,980

12,980

12,980

12,000

10,000

8,850

8,850

GALLONS

8,260
8,000

7,080
6,490

6,000

4,963

4,961

4,911
4,195

3,989
4,000

2,000

3,026

2,971

3,005

2,950

1,569

2,761
1,573

1,128

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

DEC

MONTH

PAGE 19

DEC

ZONE-D
14,000

12,000

11,880

11,880

11,880

11,880

11,880

11,880

GALLONS

10,000

8,000

8,100

8,100

7,560

6,000
4,806

4,798
4,000

4,567

3,881
3,114

2,000

6,480

5,940

2,970

2,985

2,735

2,700

1,575

4,228

1,637

1,091

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

DEC

MONTH

Fig: 1.6

PAGE 20

ZONE-E
3,500

3,000

2,897

2,995

2,893

2,711
2,500

GALLONS

2,373
2,112

2,000

1,920

1,878
1,636

1,500

1,000

1,037

1,056

720

1,056
720

1,056

672

1,056

1,056

1,056

658

576

528

500

1,106

240
0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

MONTH

Fig: 1.6

From above graphical representation its clear that for Zone-A & Zone-E; condensate is available in
excess amount & same can be pumped to Zone B, C, and D as required as condensate in these
Zone is not sufficient due to heavy Occupant Load. This can be well understood with Fig 1.7 which
shows condensate deficit in Zone-B-C-D.
As Zone-B is close to Zone-A, excess condensate from Zone-A can be used in Zone-B. In a similar
way excess condensate from Zone-E can be used in Zone-D. This is explained in Table: 1.4 & Fig
1.7.
This will ensure that the excess of Condensate in Zone-A, E is not wasted & in-turn used in other
zone to meet the motive of water conservation

PAGE 21

DEC

EXCESS
ORIGINAL
COMPENSATED
CONDENSATE CONDENSATE CONDENSATE
IN ZONE-A
IN ZONE-B
OF ZONE-B
[X]
[Y]
[Z=X+Y]
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC

665
1,338
1,377
1,380
1,480
1,968
447
1,947
1,195
2,156
1,889
682

1,514
3,450
2,837
2,871
3,919
4,751
1,079
4,734
2,633
4,694
4,021
1,517

EXCESS
CONDENSATE
IN ZONE-E
[M]

ORIGINAL
CONDENSATE
IN ZONE-D
[N]

COMPENSATED
CONDENSATE
OF ZONE-D
[O=M+N]

317
1,056
1,200
1,206
1,317
1,841
418
1,837
1,108
1,939
1,655
530

1,575
3,114
2,970
2,985
3,881
4,798
1,091
4,806
2,735
4,567
4,228
1,637

1,892
4,170
4,169
4,191
5,197
6,639
1,509
6,643
3,843
6,506
5,883
2,167

2,179
4,788
4,214
4,251
5,399
6,719
1,526
6,681
3,828
6,850
5,910
2,199
Table: 1.4

COMPENSATED CONDENSATE ZONE-D


14,000
12,000

11,880

11,880

11,880

11,880

6,639

6,643

11,880

11,880

GALLONS

10,000
8,000

8,100

8,100

7,560

6,000
5,197
4,170
3,114

4,000
2,000

4,169

4,191

2,970

2,985

5,940

4,806

4,798

3,881

6,506
4,567

3,843

6,480

4,228

2,735

2,700

1,892
1,575

5,883

2,167
1,637

1,509
1,091

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

DEC

MONTH

Fig: 1.7

PAGE 22

COMPENSATED CONDENSATE ZONE-B


14,000
12,980

12,980

12,980

12,980

6,719

6,681

12,980

12,980

12,000

GALLONS

10,000
8,850

8,850

8,000

8,260

6,000
4,788
4,000
2,000

3,450
2,179
1,514

5,399
4,214
2,837

4,251

4,751

6,490

4,734

3,919

5,910
4,694

3,828
2,950

2,871

7,080

6,850

4,021

2,633

2,199
1,517

1,526
1,079

0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

DEC

MONTH

Fig: 1.7

At this stage we can build the condensate use of Entire School with the total demand. This is
explained with Fig: 1.8 below.

DEMAND VS CONDENSATE IN ENTIRE GIRL INTERMEDIATE


SCHOOL
45,000

39,952

39,952

39,952

39,952

20,433

20,398

39,952

39,952

40,000
35,000

GALLONS

30,000

27,240

27,240

25,424

25,000

20,380

16,696

20,000

14,095

15,000
10,000

19,976

12,794

12,791

18,100

11,488

9,080

7,079

21,792

7,091

4,643

5,000
0
JAN

FEB

MAR

APR

MAY

JUN

JUL

AUG

SEP

OCT

NOV

DEC

MONTH

Fig: 1.8

PAGE 23

2.0 CONCLUSION AFTER WATER BUDGETTING.

After detailed Water Budget study, it can be concluded that if we can use
1. 100% Condensate water for Toilet Flushing we can save up to 331,977 Gallons/Yr. of Potable
water.
2. 50% Condensate water for Toilet Flushing we can save up to 165,989 Gallons/Yr. of Potable
water.
In addition its important to note that these thousands of Gallons is avoided both at input stage &
at Exit stage of School premises. This means

We dont need to pump this much of saved Gallons of water from Marafiq Municipal Govt
Organization which not only guarantee reduced Water charges to Quranic Project but also
reduces Water Desalination requirement at these many Gallons of water thus helping Saudi
Arabia energy demand crisis which is discussed in Section 1.1.
We can avoid draining these many Gallons of water into Local Sewer which could have again
increased Water Treatment Cost of these many Gallons.

Lease but not less, this condensate Reclaim may look like tiny save of water when compared with
Overall Mutrafiah Quranic School Demand but still this little saving of water can assure
Sustainability & Commitment to Environment.

2.1 COST ANALYSIS


A. SYSTEM WITHOUT CONDENSATE
Let us now analysis how much savings we get in terms of money. Clearly there is 370,464 Gallons
or 1403 Cu meter of annual water demand alone for flushing. If it happens to use only Potable water
alone for flushing, it would cost 8,414 SAR/Annual as per Marafiq Water Tariff in Table 1.5.

PAGE 24

WITHOUT CONDENSATE
MONTH

Demand
Gallons/
Month
Entire
School

Potable Water
Demand CU
METER/MONTH
ENTIRE SCHOOL

SAR
[300 ABOVE]
CU.M
6 SAR

JAN
27,240
103
619
FEB
39,952
151
907
MAR
27,240
103
619
APR
25,424
96
577
MAY
39,952
151
907
JUN
39,952
151
907
JUL
9,080
34
206
AUG
39,952
151
907
SEP
19,976
76
454
OCT
39,952
151
907
NOV
39,952
151
907
DEC
21,792
82
495
TOTAL
370,464
1,402
8,414
Note: Water tariff are standards water tariff taken
exclusively for Royal Commissioning Projects considering
water consumption are always above 300 Cu
Meter/Monthly

Table: 1.5

8414 SAR annual cost will be of no comparison if it needs to be compared with Condensate
Recovery System Initial Cost. Because in Saudi Arabia water is charged at very low compared
with a price its produced at Desalination Plants. This extra amount Govt is subsidizing from over
exempting on its citizen & delivering water at very low tariff. This is why we cannot get a Pay Back
period for our Condensate Recovery System with actual Marafiq Tariff as this system obviously
will exceed 8414 SAR overall Cost even for a Payback Period of 5 yrs.
So to get a clear picture let us bring additional Cost for Sea Water Desalination & Water Treatment
to be done to this 1403 Cu meter water, so that this water to be eligible for Potable Water.
Note that this additional cost Saudi Govt is paying for every Cu Meter to convert Sea Water into
Potable water & treat Sewer after being used.

PAGE 25

Table: 1.5

A Potable Water Cost: 8414 SAR--------------------------A


B. Cost of Desalination=4.08 SAR/Cu Meter [1.09 US$/CU Meter]
Total Cost = 4.08 x 1403 = 5724 SAR ------------------------B
C. Cost Of Water Treatment = 7.45 SAR/CU Meter [1.98 US$/CU Meter]
Total Cost = 7.45 x 1403 = 10,452 SAR-------------------------C
TOTAL COST = A +B + C = 8414+5724+10,452 = 24,590 SAR /Annual.

B. SYSTEM WITH CONDENSATE


Assuming 50% condensation, we noticed that we have 165,989 Gallons of
Condensate. Table 1.6. & additional we need 774 Cu Meter of potable water
for complete flushing. This comes with an expense of 4644 SAR/Annually.
A Potable Water Cost: 4644 SAR--------------------------A
B. Cost of Desalination=4.08 SAR/Cu Meter [1.09 US$/CU Meter]
Total Cost = 4.08 x 774 = 3158 SAR ------------------------B
C. Cost Of Water Treatment = 7.45 SAR/CU Meter [1.98 US$/CU Meter]
Total Cost = 7.45 x 774 = 5766 SAR-------------------------C
TOTAL COST = A+B + C = 4644+3158+5766 = 13,568 SAR /Annual.

PAGE 26

TOTAL COST SAVINGS: 24,590 13,568 = 11,022 SAR/ANNUALLY


TOTAL WATER SAVINGS: = 165,989 GALLONS/ANNUALLY

WITH CONDENSATE
MONTH

Demand
Gallons/
Month
Entire
School

Gallons OF 50%
Condensate/
Month
Entire School

POTABLE
WATER CU
METER/MONTH
ENTIRE SCHOOL

SAR
[300
ABOVE]
CU.M
6 SAR

JAN
27,240
7,079
76
458
FEB
39,952
14,095
98
587
MAR
27,240
12,794
55
328
APR
25,424
12,791
48
287
MAY
39,952
16,696
88
528
JUN
39,952
20,433
74
443
JUL
9,080
4,643
17
101
AUG
39,952
20,398
74
444
SEP
19,976
11,488
32
193
OCT
39,952
20,380
74
445
NOV
39,952
18,100
83
496
DEC
21,792
7,091
56
334
TOTAL
370,464
165,989
774
4,644
Note: Water tariff are standards water tariff taken exclusively for Royal
Commissioning Projects considering water consumption are always
above 300 Cu Meter/Monthly
Table: 1.6

CONDENSATE RECOVERY SYSTEM COST:


PAYBACK PERIOD:

PAGE 27

2.2 BASIC DESIGN


Concept of Initial Design is made simple with the use of 2 Nos Condensation Tank. Exact
tank sizing & Pipe Sizing is not done at this stage of design as the whole Condensate Reclaim
Engineering need prior approval from Royal Commissioning.
2 tank concept is used to overcome all the unpredicted condensation thus adding more
safety & reliability. Tank-1 is designed to hold 1 week condensate & Tank-2 is designed to depend
on Tank-1 to meet the Flushing demand. Also 2 or more Zones can be combined to use this Dual
Design concept. Tank-1 can hold 1 week condensate demand to feed the Flushing requirement in
School. Float switch installed in Tank-2 is preset between Upper & Lower layer; where in lower
layer is set for at least 1 day Flushing Demand of Zones involved in that design
Fig-1.9 explain the schematic layout of typical Condensate Collection System.
NOTE:
1. To capture the flow of condensate Water Metering may be required. This will be
mandate if any building is applying for LEED Certification; as per LEED V4 is concerned
Building Level Water Metering is both Pre-requisite & Credit. However in this proposed
designed we have not included any Water meters since Quranic Project didnt applied
for any LEED certification.
2. It will be an optional step to use water treatment depending on the pH value of the
condensate. If pH reduces drastically then a chlorine Dosing tank along with pH sensor
installed & interlocked with dosing tank may be used. It all depends on pH value of
condensate at the time of Commissioning Phase.

SEQUENCE OF OPERATION

Float switch in Tank-2 after reaching at lower level sends a control signal to Motorized
Valve-1 through Control Logic Panel-1[CP-1]. This will activate the valve to open & condensate
collected in Tank 1 reaches Tank-2. This flow is sensed by Flow-Switch installed & this in turn gives
a Control Logic Signal to Motorized valve-2 to get closed.
If the Motorized Valve-1 open & there is no condensate in Tank 1; then in this case the Flow Switch
will send signal to Motorized Valve-2 to open through Cp-2. This will activate Potable Water Feed
in Tank-1 & once upper level is reached Potable water is stopped.
CP-1 & CP-2 are interlocked to control Potable Water feeding.

PAGE 28

Fig: 1.9

2.2 CONDENSATE RECOVERY & GREEN PLUMBING


MECHANICAL CODE.

Because condensate is onsite Water recovered water we need to follow extra code apart from
usual IPC/ASPE Standards & Code. AS a practice we have followed [IAPMO] Green Plumbing
Mechanical Code Supplement 2012. This code help is additional safety & further design &
Commissioning input that must be adhered in addition to IPC Code.

PAGE 29

Fig 503.9 is a reference from Sec: 503.7 explaining the signage required in Reclaimed Water
services. As far as Water quality is concerned of recovered Condensate water, Section: 504.10
DESIGN & INSTALLATION direct AHJ [Authority Having Jurisdiction] or local code for further
treatment before any end use on Toilet flushing.

2.3 INSTALLED SNAPS FOR REFRENCE

REFERENCE:

Review of Saudi Arabia Municipal Water Tarif- Omar K M Ouda, Department of Civil
Engineer, Prince Muhammad Bin Fahd University, Al Khobar, Kingdom Of Saudi Arabia.
Hourly Analysis Program Software Specific Humidity results for Quranic Girl Intermediate
School- Mutrafiah Project, Al Jubail- Kingdom of Saudi Arabia Designed by Abdul Rahman
AL Naim Consultant Engineers- Dammam, Kingdom Of Saudi Arabia.
San Antonio- United States of America- User Manual for Condensate Collection & Use
Manual for Commercial Buildings.
ASHRAE Journal on Condensate Recovery System by Karen Guz Vol 47, no-6 Published on
June 2005.

PAGE 30

White paper by Belfer Center for Science & international Affairs on Waste Water Reuse in
Saudi Arabia by Arani, Laura Diaz & Afreen Siddique.
Engineers Newsletter by TRANE Vol 36-4 for FAQ on LEED & HVAC design for
sustainability.
2012 Green Plumbing & Mechanical Code Supplement; Second Edition.
American Society of Plumbing Engineer; Vol-2 for Water Purification stds & treatment.

If you have any question & doubts or if you are looking for any opportunity for Energy &Water Conservation
at site , feel free to contact me
I have 8 yrs Exp in Mechanical System Design & Commissioning involved in Building services in both
Commercial & Industrial Project. I have commissioned advanced HVAC system with complete performance
testing verifying percentage of energy saved in New Building or Retrofits Project.
You can ask me for any consultancy & site visits for troubleshooting & design oriented services in HVAC,
Plumbing & Fire Fighting Design.
I will be available at

Mudassaridris.raut@gmail.com
Mob: +919590513212
Place of Residence:
Belgaum- Karnataka
Country India

PAGE 31

You might also like