Professional Documents
Culture Documents
PREPARED BY:
MUDASSAR IDRIS RAUT LEED GREEN ASSOCIATE
Mechanical Engineer
Email Id:mudassaridris.raut@gmail.com
1.1 ABSTRACT
The biggest reliable source of potable water in Saudi Arabia is from Desalination Water
treatment. Since Ground source water resources are very minimal due to geographical location,
country largest demand depends on Desalination water from Sea. However the production cost to
convert saline water to Potable water is considerable [1.09 US$ per cubic meter]. Since water is
very crucial for daily activities & converting Saline Water into potable consume ample amount of
energy & money, it obviously increases an alarm to reduce water consumption at site & look for
other replaceable derivatives which can replace Potable water intake from Municipal Bodies. The
Saudi Minister of Water & Electricity estimated that 25% of Saudi Oil & Gas Production in fiscal yr.
2009 was used domestically to generate electricity & produce water, with present demand rates
suggesting that this figure will reach 50% by yr. 2030 as per research by [BELFER CENER for science
& International Affair].
To focus on this cause Mechanical Engineering Division of Abdul Al Rahman AL Naim
Consultant- Dammam has developed a conceptual design for Water Reclaim use at Quranic School
Project- a Royal Commissioning Project in Jubail, Kingdom Of Saudi Arabia.
PAGE 1
Fig: 1.1
PAGE 2
Fig: 1.2
PAGE 3
PAGE 4
QC Gallons/Hr. of Condensate.
Qa = Air Flow rate of mixed air [Return + Outdoor] in CFM
Density - Stds Density of Air = 0.075 lb/ft3 at atmospheric Pressure.
W1 - Specific humidity of Mix Air Entering Cooling Coil.
W2 Specific humidity of Cool Air Leaving Cooling Coil.
& 0.45, 0.2641 & 60 are conversion factors to be used to get values in Gallon/Hr.
PAGE 5
AHU-01
AHU-02
AHU-03
AHU-04
AHU-05
JAN
2,769
3,028
3,137
3,151
2,073
FEB
4,789
6,900
6,051
6,227
4,224
MAR
4,194
5,674
5,942
5,939
3,839
APR
4,103
5,743
6,010
5,969
3,756
MAY
5,072
7,837
7,977
7,761
4,745
JUN
6,047
9,502
9,926
9,597
5,794
JUL
1,373
2,158
2,256
2,182
1,317
AUG
6,007
9,468
9,922
9,612
5,787
SEP
3,445
5,266
5,523
5,470
3,273
OCT
6,425
9,388
9,823
9,134
5,990
NOV
5,890
8,042
8,390
8,457
5,422
DEC
2,515
3,034
3,147
3,275
2,212
52,629
76,039
78,104
76,772
48,431
TOTAL
GALLONS/YR BY
AHU
TOTAL
GALLONS/YR BY
ENTIRE SCHOOL
331,977 GALLONS/YR
Table: 1.1
PAGE 6
Fig: 1.3
PAGE 7
Sample Calculation for January month for AHU-3 is as shown Below in Table-1.2
JAN
TIME
W1 @ TM
W2 @ T0
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
0.00864
0.01105
0.01105
0.01107
0.01104
0.01104
0.01102
0.01103
0.01101
0.011
0.00864
0.00807
0.00806
0.00769
0.00879
0.00874
0.00877
0.00869
0.00869
0.00864
0.00863
0.0086
0.0086
0.00764
0.00763
0.00765
0.14
0.33
0.34
0.33
0.34
0.34
0.35
0.35
0.35
0.35
0.15
0.06
0.06
8.29
19.73
20.16
20.08
20.51
20.51
20.77
20.95
21.04
20.95
8.73
3.84
3.58
GPD
MONTHLY
209.14
3137.17
Table: 1.2
PAGE 8
2. The above data is when the building is occupied on full load & all Chillers are running on
peak Load. But this usually happens for only small amount of time & most of the time the
building is HVAC system is not running on full load.
3. AHU cooling coils must be perfectly clean & well maintained through the year as we cannot
guarantee the Exact Condensate generated with Poor maintained Cooling Coil.
HVAC CONDENSATION COMPARISION BETWEEN THEOROTICAL &
50% DIVERSITY FOR QURANIC GIRL INTERMEDIATE SCHOOL
70,000
40,866
40,795
40,759
60,000
36,200
40,000
GALLONS
33,393
50,000
28,191
25,588
25,582
22,977
30,000
14,158
20,000
10,000
20,433
20,398
20,380
16,696
14,095
12,794
9,286
12,791
7,079
14,182
18,100
11,488
7,091
4,643
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
MONTHS
Fig: 1.4
Moreover under worst case scenario even if we fail to get enough condensate, the proposed design
system by ACE Consultant is flexible enough to take in account Potable water as a back water to
flush the toilets. So the proposed design ensures that Human Comfort will not be disturbed by
implanting Condensate Water system for water flushing. So for Royal Commission its a Win-Win
situation where in they can not only save Water used at site but also end up in paying Less Water
& Tax to Govt municipal Bodies.
Fig-1.4 shows a comparison between theoretical & diversified Condensate values.50% diversity is
just a factor of safety to cushion our design & real-time values at site may exceed this diversity
factor.
PAGE 9
DEC
For all these holidays, school is considered to be completely shut down where in there is no
HVAC Equipment running & also there is no Occupant load in School to use Toilet Flushing. Also
it is assume that a month will have only 22 days of occupancy excluding all weekend.
Note that for this reason among 3 Basic uses of condensate water , we have opted to use condensate
water for Toilet Flushing because even if school is shut down we need water to maintain Landscape
but on contrary we dont need water to flush toilets as there is no Occupant Load in toilets during
vacation period.
A detailed graphical representation will help in explaining the Holiday Structure & Occupancy
Load. It is quite important to note at this stage, for Water budget estimating for flushing, we will
use this same occupancy load to balance demand water for Toilet flushing with produced
condensate water.
PAGE 10
Fig: 1.5
One of the prime motive to develop water budget is to estimate the Water demand used for
flushing of Water Closet. We are using highly efficient Toilets in this school with flush rate ranging
from 0.8-1.28 Gallons/Flush.
Quranic Girl Intermediate School is divided into 5 Zones for both HVAC & plumbing
Calculations. The detail Sub-Division of these zone is shown below in figure-1.51
PAGE 11
Fig: 1.51
Total number of Water Closet in all Zones & their respective demand Flow volume is as shown in
Table-1.31 & Total Flushing Demand for Entire School/monthly is shown in Table-1.32
PAGE 12
NO'S OF
WATER
CLOSET
5
0.8
246
738
590
0.8
246
738
590
0.8
225
675
540
0.8
20
60
48
ZONE
GALLONS/
FLUSH
NO OF OCCUPANT
Flush/
Person/Day
Flush/Day/
Zone
Gallons/Day/
Zone
0.8
20
60
48
Table: 1.31
Gallons/
Gallons/
Gallons/
Gallons/
Gallons/
MONTH
NO OF
OCCUPIED
DAYS
Month
ZONE-A
Month
ZONE-B
Month
ZONE-C
Month
ZONE-D
Month
ZONE-E
JAN
15
720
8,850
8,850
8,100
720
FEB
22
1,056
12,980
12,980
11,880
1,056
MAR
15
720
8,850
8,850
8,100
720
APR
14
672
8,260
8,260
7,560
672
MAY
22
1,056
12,980
12,980
11,880
1,056
JUN
22
1,056
12,980
12,980
11,880
1,056
JUL
240
2,950
2,950
2,700
240
AUG
22
1,056
12,980
12,980
11,880
1,056
SEP
11
528
6,490
6,490
5,940
528
OCT
22
1,056
12,980
12,980
11,880
1,056
NOV
22
1,056
12,980
12,980
11,880
1,056
DEC
12
576
7,080
7,080
6,480
576
9,792
120,360
120,360
110,160
9,792
TOTAL GALLONS/YR/
ZONE
TOTAL GALLONS/YR
FOR ENTIRE SCHOOL
370,464
Table: 1.32
PAGE 13
From Equ-A & Equ-C its clear that Condensate generated is enough to take all the flushes
assumed & still 1385-720= 665 Gallons will be left unused for any uncertain demand.
This explains that condensate generated in January Month for Zone-A in GIRL
INTERMEDIATE SCHOOL IS SUFFICIENT TO FLUSH THESE TOILETS
Flush/person/day = 3
Flush/Day/Zone = 246 x 3 = 738
Gallons/Day = 738 x 0.8 = 591
No of Occupied days in January Month = 15 Days
Total Demand Gallons/month = 15 x 591 = 8856 Gallons-----------A
Available Gallons of Condensate Generated in January month for this Zone
3028 Gallons-----------------B
Assuming 50% diversity factor as discussed above in section 1.7
Total Supply Condensate = 3028 x 0.5 = 1514---------------C
[Please read Point 1,2,3 in section 1.7 to know more about this Diversity Factor]
From Equ-A & Equ-C its clear that Condensate generated is not enough to take all the
flushes assumed & still 8856-1328= 7528 Gallons will be additional demand.
This explains that condensate generated in January Month for Zone-B in GIRL
INTERMEDIATE SCHOOL IS NOT SUFFICIENT TO FLUSH THESE TOILETS
PAGE 15
From Equ-A & Equ-C its clear that Condensate generated is not enough to take all the
flushes assumed & still 8856-1569= 7287 Gallons will be additional demand.
This explains that condensate generated in January Month for Zone-C in GIRL
INTERMEDIATE SCHOOL IS NOT SUFFICIENT TO FLUSH THESE TOILETS
PAGE 16
From Equ-A & Equ-C its clear that Condensate generated is not enough to take all the
flushes assumed & still 8100-1575.5= 6524.5 Gallons will be additional demand.
This explains that condensate generated in January Month for Zone-D in GIRL
INTERMEDIATE SCHOOL IS NOT SUFFICIENT TO FLUSH THESE TOILETS
From Equ-A & Equ-C its clear that Condensate generated is enough to take all the flushes
assumed & still 1037-720= 317 Gallons will be left unused for any uncertain demand.
PAGE 17
This explains that condensate generated in January Month for Zone-E in GIRL
INTERMEDIATE SCHOOL IS SUFFICIENT TO FLUSH THESE TOILETS
The Demand curve vs Condensate to support flushing Demand for all the zone is shown
below in Fig:1.6
ZONE-A
3,000
2409
2,500
GALLONS
2268
2,000
2253
2209
1902
1796
1573
1539
1,500
1292
1038
1,056
1,056
1,056
1,056
1,056
1,056
1,000
720
720
672
500
576
528
515
943
240
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
MONTH
PAGE 18
DEC
ZONE-B
14,000
12,980
12,980
12,980
12,980
12,980
12,980
12,000
10,000
GALLONS
8,850
8,850
8,260
8,000
7,080
6,490
6,000
4,751
4,000
3,450
2,837
2,000
4,734
4,694
4,021
3,919
2,950
2,871
1,514
2,633
1,517
1,079
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
MONTH
ZONE-C
Fig: 1.6
14,000
12,980
12,980
12,980
12,980
12,980
12,980
12,000
10,000
8,850
8,850
GALLONS
8,260
8,000
7,080
6,490
6,000
4,963
4,961
4,911
4,195
3,989
4,000
2,000
3,026
2,971
3,005
2,950
1,569
2,761
1,573
1,128
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
MONTH
PAGE 19
DEC
ZONE-D
14,000
12,000
11,880
11,880
11,880
11,880
11,880
11,880
GALLONS
10,000
8,000
8,100
8,100
7,560
6,000
4,806
4,798
4,000
4,567
3,881
3,114
2,000
6,480
5,940
2,970
2,985
2,735
2,700
1,575
4,228
1,637
1,091
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
MONTH
Fig: 1.6
PAGE 20
ZONE-E
3,500
3,000
2,897
2,995
2,893
2,711
2,500
GALLONS
2,373
2,112
2,000
1,920
1,878
1,636
1,500
1,000
1,037
1,056
720
1,056
720
1,056
672
1,056
1,056
1,056
658
576
528
500
1,106
240
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
MONTH
Fig: 1.6
From above graphical representation its clear that for Zone-A & Zone-E; condensate is available in
excess amount & same can be pumped to Zone B, C, and D as required as condensate in these
Zone is not sufficient due to heavy Occupant Load. This can be well understood with Fig 1.7 which
shows condensate deficit in Zone-B-C-D.
As Zone-B is close to Zone-A, excess condensate from Zone-A can be used in Zone-B. In a similar
way excess condensate from Zone-E can be used in Zone-D. This is explained in Table: 1.4 & Fig
1.7.
This will ensure that the excess of Condensate in Zone-A, E is not wasted & in-turn used in other
zone to meet the motive of water conservation
PAGE 21
DEC
EXCESS
ORIGINAL
COMPENSATED
CONDENSATE CONDENSATE CONDENSATE
IN ZONE-A
IN ZONE-B
OF ZONE-B
[X]
[Y]
[Z=X+Y]
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
665
1,338
1,377
1,380
1,480
1,968
447
1,947
1,195
2,156
1,889
682
1,514
3,450
2,837
2,871
3,919
4,751
1,079
4,734
2,633
4,694
4,021
1,517
EXCESS
CONDENSATE
IN ZONE-E
[M]
ORIGINAL
CONDENSATE
IN ZONE-D
[N]
COMPENSATED
CONDENSATE
OF ZONE-D
[O=M+N]
317
1,056
1,200
1,206
1,317
1,841
418
1,837
1,108
1,939
1,655
530
1,575
3,114
2,970
2,985
3,881
4,798
1,091
4,806
2,735
4,567
4,228
1,637
1,892
4,170
4,169
4,191
5,197
6,639
1,509
6,643
3,843
6,506
5,883
2,167
2,179
4,788
4,214
4,251
5,399
6,719
1,526
6,681
3,828
6,850
5,910
2,199
Table: 1.4
11,880
11,880
11,880
11,880
6,639
6,643
11,880
11,880
GALLONS
10,000
8,000
8,100
8,100
7,560
6,000
5,197
4,170
3,114
4,000
2,000
4,169
4,191
2,970
2,985
5,940
4,806
4,798
3,881
6,506
4,567
3,843
6,480
4,228
2,735
2,700
1,892
1,575
5,883
2,167
1,637
1,509
1,091
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
MONTH
Fig: 1.7
PAGE 22
12,980
12,980
12,980
6,719
6,681
12,980
12,980
12,000
GALLONS
10,000
8,850
8,850
8,000
8,260
6,000
4,788
4,000
2,000
3,450
2,179
1,514
5,399
4,214
2,837
4,251
4,751
6,490
4,734
3,919
5,910
4,694
3,828
2,950
2,871
7,080
6,850
4,021
2,633
2,199
1,517
1,526
1,079
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
MONTH
Fig: 1.7
At this stage we can build the condensate use of Entire School with the total demand. This is
explained with Fig: 1.8 below.
39,952
39,952
39,952
39,952
20,433
20,398
39,952
39,952
40,000
35,000
GALLONS
30,000
27,240
27,240
25,424
25,000
20,380
16,696
20,000
14,095
15,000
10,000
19,976
12,794
12,791
18,100
11,488
9,080
7,079
21,792
7,091
4,643
5,000
0
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
MONTH
Fig: 1.8
PAGE 23
After detailed Water Budget study, it can be concluded that if we can use
1. 100% Condensate water for Toilet Flushing we can save up to 331,977 Gallons/Yr. of Potable
water.
2. 50% Condensate water for Toilet Flushing we can save up to 165,989 Gallons/Yr. of Potable
water.
In addition its important to note that these thousands of Gallons is avoided both at input stage &
at Exit stage of School premises. This means
We dont need to pump this much of saved Gallons of water from Marafiq Municipal Govt
Organization which not only guarantee reduced Water charges to Quranic Project but also
reduces Water Desalination requirement at these many Gallons of water thus helping Saudi
Arabia energy demand crisis which is discussed in Section 1.1.
We can avoid draining these many Gallons of water into Local Sewer which could have again
increased Water Treatment Cost of these many Gallons.
Lease but not less, this condensate Reclaim may look like tiny save of water when compared with
Overall Mutrafiah Quranic School Demand but still this little saving of water can assure
Sustainability & Commitment to Environment.
PAGE 24
WITHOUT CONDENSATE
MONTH
Demand
Gallons/
Month
Entire
School
Potable Water
Demand CU
METER/MONTH
ENTIRE SCHOOL
SAR
[300 ABOVE]
CU.M
6 SAR
JAN
27,240
103
619
FEB
39,952
151
907
MAR
27,240
103
619
APR
25,424
96
577
MAY
39,952
151
907
JUN
39,952
151
907
JUL
9,080
34
206
AUG
39,952
151
907
SEP
19,976
76
454
OCT
39,952
151
907
NOV
39,952
151
907
DEC
21,792
82
495
TOTAL
370,464
1,402
8,414
Note: Water tariff are standards water tariff taken
exclusively for Royal Commissioning Projects considering
water consumption are always above 300 Cu
Meter/Monthly
Table: 1.5
8414 SAR annual cost will be of no comparison if it needs to be compared with Condensate
Recovery System Initial Cost. Because in Saudi Arabia water is charged at very low compared
with a price its produced at Desalination Plants. This extra amount Govt is subsidizing from over
exempting on its citizen & delivering water at very low tariff. This is why we cannot get a Pay Back
period for our Condensate Recovery System with actual Marafiq Tariff as this system obviously
will exceed 8414 SAR overall Cost even for a Payback Period of 5 yrs.
So to get a clear picture let us bring additional Cost for Sea Water Desalination & Water Treatment
to be done to this 1403 Cu meter water, so that this water to be eligible for Potable Water.
Note that this additional cost Saudi Govt is paying for every Cu Meter to convert Sea Water into
Potable water & treat Sewer after being used.
PAGE 25
Table: 1.5
PAGE 26
WITH CONDENSATE
MONTH
Demand
Gallons/
Month
Entire
School
Gallons OF 50%
Condensate/
Month
Entire School
POTABLE
WATER CU
METER/MONTH
ENTIRE SCHOOL
SAR
[300
ABOVE]
CU.M
6 SAR
JAN
27,240
7,079
76
458
FEB
39,952
14,095
98
587
MAR
27,240
12,794
55
328
APR
25,424
12,791
48
287
MAY
39,952
16,696
88
528
JUN
39,952
20,433
74
443
JUL
9,080
4,643
17
101
AUG
39,952
20,398
74
444
SEP
19,976
11,488
32
193
OCT
39,952
20,380
74
445
NOV
39,952
18,100
83
496
DEC
21,792
7,091
56
334
TOTAL
370,464
165,989
774
4,644
Note: Water tariff are standards water tariff taken exclusively for Royal
Commissioning Projects considering water consumption are always
above 300 Cu Meter/Monthly
Table: 1.6
PAGE 27
SEQUENCE OF OPERATION
Float switch in Tank-2 after reaching at lower level sends a control signal to Motorized
Valve-1 through Control Logic Panel-1[CP-1]. This will activate the valve to open & condensate
collected in Tank 1 reaches Tank-2. This flow is sensed by Flow-Switch installed & this in turn gives
a Control Logic Signal to Motorized valve-2 to get closed.
If the Motorized Valve-1 open & there is no condensate in Tank 1; then in this case the Flow Switch
will send signal to Motorized Valve-2 to open through Cp-2. This will activate Potable Water Feed
in Tank-1 & once upper level is reached Potable water is stopped.
CP-1 & CP-2 are interlocked to control Potable Water feeding.
PAGE 28
Fig: 1.9
Because condensate is onsite Water recovered water we need to follow extra code apart from
usual IPC/ASPE Standards & Code. AS a practice we have followed [IAPMO] Green Plumbing
Mechanical Code Supplement 2012. This code help is additional safety & further design &
Commissioning input that must be adhered in addition to IPC Code.
PAGE 29
Fig 503.9 is a reference from Sec: 503.7 explaining the signage required in Reclaimed Water
services. As far as Water quality is concerned of recovered Condensate water, Section: 504.10
DESIGN & INSTALLATION direct AHJ [Authority Having Jurisdiction] or local code for further
treatment before any end use on Toilet flushing.
REFERENCE:
Review of Saudi Arabia Municipal Water Tarif- Omar K M Ouda, Department of Civil
Engineer, Prince Muhammad Bin Fahd University, Al Khobar, Kingdom Of Saudi Arabia.
Hourly Analysis Program Software Specific Humidity results for Quranic Girl Intermediate
School- Mutrafiah Project, Al Jubail- Kingdom of Saudi Arabia Designed by Abdul Rahman
AL Naim Consultant Engineers- Dammam, Kingdom Of Saudi Arabia.
San Antonio- United States of America- User Manual for Condensate Collection & Use
Manual for Commercial Buildings.
ASHRAE Journal on Condensate Recovery System by Karen Guz Vol 47, no-6 Published on
June 2005.
PAGE 30
White paper by Belfer Center for Science & international Affairs on Waste Water Reuse in
Saudi Arabia by Arani, Laura Diaz & Afreen Siddique.
Engineers Newsletter by TRANE Vol 36-4 for FAQ on LEED & HVAC design for
sustainability.
2012 Green Plumbing & Mechanical Code Supplement; Second Edition.
American Society of Plumbing Engineer; Vol-2 for Water Purification stds & treatment.
If you have any question & doubts or if you are looking for any opportunity for Energy &Water Conservation
at site , feel free to contact me
I have 8 yrs Exp in Mechanical System Design & Commissioning involved in Building services in both
Commercial & Industrial Project. I have commissioned advanced HVAC system with complete performance
testing verifying percentage of energy saved in New Building or Retrofits Project.
You can ask me for any consultancy & site visits for troubleshooting & design oriented services in HVAC,
Plumbing & Fire Fighting Design.
I will be available at
Mudassaridris.raut@gmail.com
Mob: +919590513212
Place of Residence:
Belgaum- Karnataka
Country India
PAGE 31