SEC COA
Substation No.
S/S : 8515
Contractor
DELTA Co.
Contract No.
Sheet No.
SUD1-03-001
Page 1 of 6
HICO
2. Mechanical Checks and Visual Inspections as Per TCS P105 Rev 01, Item
no 4.1
Item
Description
Check tightness of all connections
1
Inspect for physical damage / defects
2
Panel condition, cleanliness, organization, labeling, readiness for service, panel
3
doors, handles...etc
4
CT shorting checked
Indications checked
5
6
Check the ferrules as per specification
Panel Earthing checked
7
Confirm that each panel has been properly secured to the floor in its final service
8
location.
Confirm that panels are constructed and wired as per SEC relevant
9
specification.
10
Check case cover and gasket for proper seal against dust.
Check all installed equipment nameplate information for compliance to
11
approved drawings and equipment /material lists.
For all internal and external panel wiring, confirm that all screw terminations are
tight and that crimp connectors are firmly secured to the wire and to the
12
termination point. Ensure that no part of the wire is bent
at the termination point. Check Ferrules.
Check that panel equipment is mounted securely and protected against
13
mal operation due to vibration, shock, etc
Use of ring type terminals for wire termination for current circuit wires.
14
15
16
ENG/MOHAMED AMIN
Checked
Yes
N/A
Yes
N/A
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
N/A
N/A
N/A
Yes
N/A
Yes
Yes
N/A
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Yes
N/A
Date of Test
12/06/2014
Control/Record No.: R/PP/TC/1.084
Customer
SEC COA
Substation No.
S/S : 8515
Contractor
DELTA Co.
Item
1
Contract No.
Sheet No.
Page 2 of 6
Tests:
Description
Insulation Resistance Test report of all wires to be submitted by the
contractor prior witnessing and made available
Dc power/ control supply checked.
AC Power/ Control supply checked.
Circuit Breaker, Disconnector and Earth Switch Open/Close status
checked
All CBS, DSWs and ESWs should be tested before starting function
Check
2
3
4
SUD1-03-001
Yes
Checked
N/A
Yes
Yes
Yes
N/A
N/A
N/A
Yes
N/A
Setting
values
Description
st
5.7 bar
5.5 bar
6.7 bar
20 SEC
----
CB blocked status
Closing
Tripping
Remarks
OK
OK
OK
OK
OK
ENG/MOHAMED AMIN
Date of Test
12/06/2014
Control/Record No.: R/PP/TC/1.084
Customer
SEC COA
Substation No.
S/S : 8515
Contractor
DELTA Co.
Equip.
ref
234
236
Operation
Command
Open/
close
Open/
close
Close
230
Open
231A
231B
Contract No.
Open/
close
SUD1-03-001
Sheet No.
Page 3 of 6
Indication
Condition
Remarks
Service
OK
Test
OK
Service
OK
Test
OK
Service
OK
Test
OK
Service
OK
Test
OK
LCC
CR
SAS
LCC
CR
SAS
OK
independent
condition
OK
Equipments
Ds 234 & 236
DS 234 & 236
Protection Relays
Status
FO
FC
Operated
Remarks
OK
OK
As Per Sch Dwg
ENG/MOHAMED AMIN
Date of Test
12/06/2014
Control/Record No.: R/PP/TC/1.084
Customer
SEC COA
Substation No.
S/S : 8515
Contractor
DELTA Co.
Contract No.
Sheet No.
SUD1-03-001
Page 4 of 6
Condition
Close/open
Test
Close/open
Service
Equipments
Es 231A & 141B
231B
CB230
ES 231A, 231B & 141B
Status
FC
FO
O
FO
Remarks
OK
OK
Condition
Close/open
Test
Close/open
Service
Equipments
ES 231B & 261B
231A
CB130
ES 231A, 231B & 261B
Status
FC
FO
Remarks
OK
O
FO
OK
Condition
Service
Equipments
DS 234 & 236
Status
FO
Remarks
OK
Condition
Service
Equipments
Status
Remarks
FO
OK
Note:
FO: fully open
O: open
ENG/MOHAMED AMIN
Date of Test
12/06/2014
Control/Record No.: R/PP/TC/1.084
Customer
SEC COA
Substation No.
S/S : 8515
Contractor
DELTA Co.
Contract No.
Sheet No.
SUD1-03-001
Page 5 of 6
Channel
no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Events
CB MOTOR SUPPLY FAIL
DS/ES MOTOR SUPPLY FAIL
CB CLOSE SUPPLY FAIL
DS/ES CONTROL SUPPLY FAIL
CB TRIP-1 SUPPLY FAIL
CB TRIP-2 SUPPLY FAIL
INDICATION & GAS ALARM SUPPLY FAIL
CONTACT MULTIPLICATION RELAY FAIL
ALARM DC SUPPLY FAIL
ALARM AC SUPPLY FAIL
BCU SUPPLY FAIL
LCC AC SUPPLY FAIL
DS SWITCHING INCOMPLETE
ES SWITCHING INCOMPLETE
CB MOTOR RUNTIME EXCEED &SPRING UNCHARGE
CB OPERATING MECHANISM FAIL
DS/ES MANUAL MODE
SPARE
VT ISOLATOR(194A) OPEN
VT ISOLATOR(194A) SWITCHING INCOMPLETE
VT ISOLATOR(226A) OPEN
VT ISOLATOR(226A) SWITCHING INCOMPLETE
SPARE
SPARE
COMP.G230-1 SF6 GAS PRESSURE LOW STAGE-1
COMP.G230-1 SF6 GAS PRESSURE LOW STAGE-2
COMP.G230-2 SF6 GAS PRESSURE LOW STAGE-1
COMP.G230-2 SF6 GAS PRESSURE LOW STAGE-2
COMP.G230-3 SF6 GAS PRESSURE LOW STAGE-1
COMP.G230-3 SF6 GAS PRESSURE LOW STAGE-2
COMP.G230-5 SF6 GAS PRESSURE LOW STAGE-1
COMP.G230-5 SF6 GAS PRESSURE LOW STAGE-2
COMP.G230-6 SF6 GAS PRESSURE LOW STAGE-1
COMP.G230-6 SF6 GAS PRESSURE LOW STAGE-2
COMP.G230-7 SF6 GAS PRESSURE LOW STAGE-1
COMP.G230-7 SF6 GAS PRESSURE LOW STAGE-2
ENG/MOHAMED AMIN
Status
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Date of Test
12/06/2014
Control/Record No.: R/PP/TC/1.084
Customer
SEC COA
Substation No.
S/S : 8515
Contractor
DELTA Co.
Contract No.
Projects
& Supplies Co.
Channel
Sheet No.
SUD1-03-001
Page 6 of 6
Status
no.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Note:
All interlock points were checked according to interlocking conditions table which is approved
by system Operation department
ENG/MOHAMED AMIN
Date of Test
12/06/2014
Control/Record No.: R/PP/TC/1.084