You are on page 1of 4

Technical Bulletin 3

Dehumidification and the


Psychrometric Chart
I

R ELATIVE HUMIDITY

NTRODUCTION

The psychrometric chart has been well documented in a wide


variety of technical textbooks and journals. This technical
bulletin will not attempt to cover the chart in detail, but, will
highlight those features of the chart which apply to refrigerant
type dehumidification applications. It will define the terms
which form the nucleus of properly applying a dehumidifier.

Relative humidity is a misapplied term. It is often used in


place of absolute humidity. The key is the word relative. To
understand this concept, a law of nature must be Reviewed.
Air is a compressible fluid and its volume is represented by
the following equation:

v = K(T/P)
V = Volume
T = Temperature
P = Pressure
K = Constant

HE CHART

49

Figure 1 shows a typical psychrometric chart. Dry Bulb


temperatures are shown on the chart as vertical lines.
The horizontal lines represent Dew Point temperatures. Lines
representing Wet Bulb temperatures are the straight diagonal
lines sloping downward from left to right. The curve forming
the top edge of the chart is called the saturation curve.
Air in a condition that falls on any point along this curve is
totally saturated with moisture. Any additional moisture
added could not be absorbed and would remain in a liquid
state as condensation. The sweeping curved lines that
follow the saturation curve are relative humidity lines
expressed as percentages. These lines represent the
degree of volume displaced by moisture with respect to the
total air volume.

48

80

42
RH

80
%
RH
%
70

RH

id

110

100

90

ulb

120

tB

60

ti v

Hu

130

0%

Te

mp

80

era

RH

tur

es

70

RH

%
40

60

30

RH

50

45

40

13

40

12

20%

RH

35

30

30
25

H
10% R

20

Dew Point Temperatures


10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

13.5 CU. FT.

85

90

95

100

14.0 CU. FT.

105

GRAINS OF MOISTURE PER POUND OF DRY AIR

75
RH
%
90

70

33
32
31
65

it

140

Dry Bulb Temperatures

TIO
RA
TU

38

SA
37

AT
PY

36

AL
35

TH
EN

39

40

(B

41

TU

/L

B)

43

44

45

170

14

12
11
10
9

180

46

47

105

We

60

e
la
Re

100

150

30
29
19

15

95

ti o

rv

90

160

28
27

26
25
24
23
22
21
20

18
17

16

Figure 1

at

a
u5r0

Cu55

14.5 CU. FT.


85

34

As the air temperature increases, its total volume increases


and decreases on reduction of temperature. Pressure has the
opposite effect. As pressure increases volume decreases.

This is important to understand because water damage


occurs at an absolute humidity concentration regardless of its
relative humidity. This is known as the constant Dew Point
Temperature.

Water, however, is not compressible. Therefore given a


specific amount, it will always occupy the same amount of
volume.

S ENSIBLE AND LATENT HEATING AND COOLING


There are four types of energy changes when heat of moisture
is added or removed. Sensible heat occurs when heat is added
without the addition or reduction of moisture. Sensible cooling
is the reverse. Latent heat, also known as humidification, is the
addition of moisture without changing the dry bulb temperature.
Latent cooling or dehumidification is the removal of moisture.
Figure 3 shows how these are displayed on the chart.

49

Figure 2 illustrates how this applies to the psychrometric


chart. As moisture laden air is heated or cooled the air volume
changes but the moisture does not. Thus there is a change in
relative humidity, without a change in actual water content.

48

95

100

105

46

180

170

(B
N

80

42

40

TIO

39

RA
TU

75

38

140

130

35

60
%

90
RH

32

80
%

31

RH
%
70

65

88 GR.
90

25

RH
%

60

24

80

23

%
50

RH

21

%
40

20

18

RH

40

60

50

16

19

17

70

55

30

15

92F

RH

50

40
40

12

10

13

11

12

14

45

20%

RH

35

30

30
25

H
10% R

20

78F

60

70F

27

26

28

29

30

100

22

Figure 2

110

10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

13.5 CU. FT.

85

90

95

100

14.0 CU. FT.

105

GRAINS OF MOISTURE PER POUND OF DRY AIR

RH

80

120

70

33

34

EN

TH

AL

PY

AT

SA

40% RH

37

60% RH

150

36

80% RH

160

41

TU

/L

B)

43

44

45

70F

90

47

92F

78F

14.5 CU. FT.


85

TECHNICAL BULLETIN 3

Dehumidification and the Psychrometric Chart


Rarely will these occur as shown but will rather be a mixture of
them. A refrigerant dehumidification system is a combination of
sensible and latent cooling and sensible heating. First the
system cools the air to reduce the dry bulb temperature to the
dew point. Then latent cooling reduces the absolute humidity
and finally the air is reheated increasing its dry bulb temperature.
Figure 4 graphs this process.

By obtaining the starting and finishing grains per pound, the


amount of moisture to be removed can be calculated. The
amount of moisture to be removed is the difference between
these two values known as GR.
Figure 5 shows how a dehumidification system was sized.
The ambient design was 91F dry bulb and 78F wet bulb. The
desired indoor value was 80F dry bulb and 50% relative
humidity. The outside ambient has a moisture content of
124 grains and the indoor design has 78 grains. Thus the
required moisture removal rate is 124-78 = 46 grains per
pound of dry air.

D EHUMIDIFIER SIZING

49

To properly apply a dehumidification system, the amount


of moisture to be removed must be calculated. For most
applications the only information available is the dry bulb and
relative humidity or dry bulb and wet bulb temperatures. The
psychrometric chart is used to plot these two values by finding
their intersection and then following the horizontal line to the
right to determine the moisture content in grains per pound.

48

14.5 CU. FT.


90

95

100

105

180

46

47

85

(B
N

80

42

40
39

TIO
TU

75

SA
37

AT
PY
AL
35

TH

130

120

80
%

31

RH

32

110

100
RH
%
70

65

29

RH
%
60

25

27

26

28

90

60

24

80

23

%
50

RH

22

70

%
40

60

16
15

30

RH

50

40
40

12

10

13

11

12

14

45

20%

RH

35

30

30
25

H
10% R

20

RH

50

19

17

20

18

21

55

10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

13.5 CU. FT.

85

90

95

100

14.0 CU. FT.

105

GRAINS OF MOISTURE PER POUND OF DRY AIR

RH

90

70

33

34

EN

36

Sensible Heating
Sensible Cooling
Humidification
Dehumidification

140

30

A.
B.
C.
D.

150

38

RA

Figure 3

160

41

TU

/L

B)

43

44

45

170

49

Figure 4

48

14.5 CU. FT.


90

95

100

105

180

46

47

85

170

/L
TU

80

41

(B
N

40

IO
39

AT
UR

38

75

SA
T
37

AT

130

AL

36

PY

140

35

TH

150

120
RH
80

31

RH

32

110

65

70
%

RH

30

100

RH

28

90
60

27

26

QS
25

Entering Air

60

24

80
RH

23

50

22

70

40

16
15

RH

60

Leaving
Evaporator
Coil

45

14

12

30

Reheated
Air (Supply)

RH

WA

GR

WB

50

40
40

13

11

12

10
9

50

19

17

20

18

21

55

GRAINS OF MOISTURE PER POUND OF DRY AIR

90

70

33

34

EN

QL

160

42

B)

43

44

45

Total Cooling A-B


Sensible Cooling C-B
Latent Cooling A-C
Specific Humidity A (room air)
Specific Humidity C (supply air)
Total Temperature Rise B-D
WA-WB

29

=
=
=
=
=
=
=

QT

QT
QS
QL
WA
WB
T
GR

20%

RH

35

30

30
25

10% RH

20

10

0
20

25

30

35

40

50

45

55

60

65

75

70

DRY BULB F

13.0 CU. FT.

80

85

90

95

100

105

14.0 CU. FT.

13.5 CU. FT.

49

12.5 CU. FT.

48

14.5 CU. FT.


90

95

100

105

47

85

180

46

Figure 5

80

40

(B
N
39

TIO
37

75

38

RA
TU
SA
AT

140

130

WA

91F DB/78F WB

35

36

PY
AL
TH

120
RH
80

31

RH

32

110

RH
70
%

65

90
RH
%
60

25

27

26

28

29

30

100

60

24

23

50

50
H

80

80F DB

22

70

40

RH

60

50

16

19

17

20

18

21

55

15

0%

RH

WB

50

40
40

13
12

GR

45

14

12
11
10
9

GRAINS OF MOISTURE PER POUND OF DRY AIR

%
90

70

33

34

EN

Constant
Total Air Volume
WA-WB
7000 GR/LB Air

=
=
=
=

150

20%

RH

35

30

30
25

10% RH

20

4.5
CFM
GR
7000

41

TU

LBS/HR = 4.5 x CFM x GR


7000

160

42

/L

B)

43

44

45

170

10

0
20

25

30

35

40
12.5 CU. FT.

45

50

55

60
13.0 CU. FT.

65

70

DRY BULB F

75

80

85

90

13.5 CU. FT.

95

100

105

14.0 CU. FT.

8300 West Sleske Court


Milwaukee, WI 53223
(414) 357-7400
FAX: (414) 357-8501
103 09/97

You might also like