SHEET FOR CALCULATING U - FACTOR

RPUF

EPS

25

0.732

0.42

50

0.42

0.489

THICKNESS

75

0.295

0.346

100

0.227

0.267

125

0.182

0.218

150

0.153

0.184

175

0.136

0.159

Interpolation
enter the thi

125

mm

RPUF / EPS
x1
x2

100
150

mm
mm

u1
u2

0.227
0.153

du / dx
dx req

-1.48
0.025

Ureq
200

0.119

W/m2 K
W/m2 K

0.1900 W/m2 K

0.14

To find the adp of the coil

Total sensible load inside the room


S.F
10%
TSH

0.94 kW
0.094
1.034

Room conditions
trm

2
Total latent load inside the room
S.F
TLH

10%

0.6 kW
0.06
0.66

EQUATION

( 0.204 * ( t
GTH

1.694
tadp

SHF

0.61 kW

Characteristics
Interpolation
enter the thi

125

mm

RPUF / EPS
x1
x2

50
75

mm
mm

u1
u2

0.489
0.346

du / dx
dx req

W/m2 K
W/m2 K

Insulation Material
Density in kg/m3
Temp range
Skin mtl
Type of Joints
Application Temp
0 to 10 deg C
(-) 20 deg C
(-) 30 / (-) 40 deg C

-5.72
0.075

Ureq

0.06 W/m2 K

oom conditions
wbt
1

rh
90%

wrm
0.0039

0.204 * ( trm - tadp ))/ ( 0.204 * (trm - tadp) + 50 * ( wrm - wadp ) )


1.79 C

wadp
0.00335

0.6103896104

EPS
Expanded Polystyrene
16 - 18
- 118 to 82
Precoated, profiled
Tongue & Groove
Commonly used
80 / 100 mm
200 mm
225 / 250 mm

PUF
Poly Urethane Foam
38 - 40
-80 to 95
GS / SS Sheets
Cam lock with Groove
panel thickness
60 / 80 mm
120 mm
150 mm