Qurayyah Independent Power Project


Document Title:

MOTOR DATA SHEET


Document No.:

QIPP-MPN009-E10-0003

Owners Document No.:

QIPP-MPN009-E10-0003

AP621161/70/88 MHG 5/4

Q-456331 1/2 Rev 2

For Construction

AC INDUCTION MOTOR DATA SHEET


Model No.or RFQ No
TORISHIMA PUMP MFG.CO., LTD
Project Name
GENERAL SPECIFICATION
Frame Size
450
Type
HRQ3 451-28E
Enclosure(Protection) TEAAC
( IP 55 )
Method of Cooling
IC611
Rated Frequency
60 Hz
Number of Phases
3
Insulation Class
F
B
H
Temp. Rise at full load (by resistance method)
70 deg.C
at 1.0 S.F
Motor Location
Indoor
Outdoor
Less than 1,000meter
Altitude
Relative Humidity
Less than
70 %
Ambient Temp.
50 deg.C (Max.)
Duty Type
Continuous ( S1 )
Service Factor
1.0
Mounting
B3
B5
V1
Type
Split Sleeve
Bearing DE/N-DE
Sleeve
/ Sleeve
Lubricant
Self Lub.(ISO VG 22)
External Thrust
Not applicable
Coupling Method
Direct
V-Belt
Shaft Extension
Single
Double
Steel
Cast Iron
Terminal Main
Aux.
Yes
No
Box
Rotation(Viewed from DE)
CW
CCW
BI-Direction
Application
Boiler Feed Water Pump
Area classification
Non-Hazardous
Type of Ex-Protection N/A
Applicable Standard
IEC
ACCESSORIES

Rev. No.
[ 3 ]
20122230RMH640~643 Quantity
18 set
PERFORMANCE DATA
1450 kW
Rated Output
Number of Poles
2
Rotor Type
Squirrel Cage
Starting Method*
D.O.L
Rated Voltage
4000 V
239.0 A
Current Full Load
Locked-rotor**
550 %
Efficiency
50% Load
93.7 %
75% Load
94.8 %
95.2 %
100% Load
Power Factor(p.u)
50% Load
0.88
75% Load
0.91
100% Load
0.92
Speed at Full Load
3573 r.p.m
Torque
Full Load
395.3 kgm
Locked-rotor**
60 %
Breakdown**
220 %
Moment of Inertia (J)
Load
1.4 kgm
16.7 kgm
Motor
Sound Pressure Level (No-load & mean value at 1m from motor)
79 dB(A)
Vibration
1.8mm/s(rms)
Permissible number of
Cold
3 times
2 times
consecutive starts
Hot
Paint 3
RAL
RAL 7042
SUBMITTAL DRAWING
Outline Dimension Drawing
\ Motor Weight(Approx.)
B3
HM-087893
6800 kg

Item No.
Project No.

1.Winding Temp. Detector(Pt100,3-Wire) : 2ea/Phase


2 2.Bearing Temp. Detector(Pt100,3-Wire,Dual) : 1ea/Bearing
1 3.Space Heater : 1Phase, 120V, 400W
4.Differential Current Transformer(500/1A,5P10,15VA) : 3ea/Moto
5.Vibration Sensor(Bently Nevada-3300XL) : 2ea/Bearing
-.Proximity Probe Housing : 31000-16
-.Proximiter : 330180-50-00
-.Extension Cable : 330130-045-01-00
6. Jacking Bolt : 4ea/Motor

REMARK

SPARE PARTS
N/A
Date

DSND

CHKD

CHKD

APPD

2012.09.25

J.Y.KIM

--

J.B.KIM

Y.S.JOO

Note: Others not mentioned in this data sheet shall be in accordance with maker standard.
Above technical data are only design values and shall be guaranteed with tolerance of applicable standard.
Inspection and performance test shall be maker standard, if not mentioned.
* In case of Inverter-Fed Motor, performance data is based on sine wave tests.
** The data are based on rated voltage & frequency, and data are expressed as a percentage of full load value.