ACC Controller Module Data Sheet

Features

User-selectable alarm parameters


Password controlled environment
USB or RS232* Interface and Form C dry
alarm contacts
Programmable alarm routing, logic unit and
analog inputs
Ethernet interface + web server support
1000-event alarm log
Audible Alarm
Remote firmware upgrade

Intelligent site management:

Battery tests and log


Battery voltage and symmetry monitoring
Remaining battery capacity measurement
Low voltage disconnect
Temperature compensation with programmable
compensation factor
Monthly data logging
Site log tools

Description
The Power-One Advance Controller Card (ACC) is a pluggable microprocessor controller that
provides monitoring and control for a broad range of Power-One DC Power Systems. The ACC
monitors all system parameters including: DC voltage, rectifier current, rectifier temperature, system
capacity, battery parameters, and circuit breaker status.
Alarm and warning notifications are indicated by front panel LEDs, and through potential free alarm
contacts that allow remote signaling. External monitoring of alarms is accomplished through a USB or
RS232 port using PC-based PowCom software. The ACC has an Ethernet port allowing control
over a TCP/IP network and web based support. Alarms can be mapped via SNMP traps to customer
OSS platforms such as HP Openview
To meet individual site requirements, the ACC contains a Programmable Logic Unit that can be used
to monitor and control specified requirements. This allows individual alarm routing and logic
operations to be set as actions, alarms to be triggered, and outputs to be activated based on internal
and external signal monitoring, comparing, and processing.

MCD10062 Rev. 1.1, 2-Oct-08

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

ACC Controller Module Data Sheet

Input

Other Technical Data

Voltage

18-60 VDC

Current

<200 mA

Interface
Display

Optional 3x16 character LCD

Internal
Communication

RS485 Data Bus (64 modules max.)

External
Communication

USB or RS232* interface for remote


control via modem or directly from a PC
TM
with PowCom software. Ethernet port
allowing monitoring and control over a
TCP/IP network. Web browser support +
SNMP.
Green LED Power ON
Yellow LED System warning
Red LED System alarm
Battery current reading (via shunt)
Output voltage reading
Analog inputs for battery symmetry
reading or general use
Battery temperature sensor
Load fuse failure
Battery fuse failure
2 x Digital inputs
LVD/PLD disconnect (max 4*)
LVD/PLD reconnect
2 x Digital outputs
Site upgradeable by Flash memory

Indications

Signal Input

Signal Outputs

Software

Alarms
Alarm Contacts
Alarms

4 (max 10*) potential free change-over


alarm contacts
Low/High Voltage Alarms
Batteries on Discharge
Overvoltage Shutdown Alarm
High Load (Rectifier Capacity Alarm)
Battery Test Failure
Battery Symmetry Alarm
Mains Failure
Module Alarm
Urgent Module Alarm
Battery Fuse Failure
Load Breaker Failure
Battery/Load Disconnect Alarm
High/Low Battery Temperature Alarms
Temperature Probe Failure
High/Low AC Voltage**
16 x Additional User Definable Alarms

Dimensions
(WxHxD)

Actual dimensions vary with respect


to the system used. Contact Sales.

Weight

0.2kg (0.44 lb)

Operating Temp.

-40 to +70 C

Storage Temp.

-40 to +85 C

Safety

IEC 60950-1, UL60950-1,


& CSA-C22.2 No. 60950-1-03
EN 61000-6-2, EN 61000-6-3,
EN 300 386-2
Storage:
ETS 300 019-2-1
Transport:
ETS 300 019-2-2
Operation:
ETS 300 019-2-3

EMC
Environment

Battery Management
Battery
Disconnection

Allows voltage controlled


disconnection of batteries.

Boost Charging

Manual time controlled or automatic


boost charging with adjustable time
and voltage levels.

Battery Tests

Automatic or manual testing of


batteries up to six times per year
with a 10 test memory. Variables
include test duration and end
voltage.
Battery discontinuance test to
ensure battery connection.

Enhanced Battery
Monitoring

Monthly logging of essential battery


parameters including temperature,
temperature hours, current, charging
voltage and symmetry voltage, Data
logged for 5 years.

Site Logs

System tools developed to assist


site management. Daily peak load
and statistic logs available.

Symmetry
Measurement

Optional tool that measures


batteries for early detection of
thermal runaway.

Temperature
Compensation
Charging

Allows continuous adjustment of


output voltage according to battery
temperature. Features include
adjustable compensation factor and
separate thresholds for high
temperature alarms.

Load Shedding
(PLD)

Optional feature that allows voltage


or time controlled disconnection of
non-essential load.

* Pending system configuration


** Pending rectifier used

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

MCD10062 Rev. 1.1, 2-Oct-08

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

Aspiro Shelf System

Features

RoHS compliant for all six substances

1RU and 2RU height solutions

Wide AC input; 85 to 300VAC

Wide operating temperature range -40 C to +75 C

Ethernet interface

Simple installation

Designed for 300 mm deep ETSI cabinets

Rear or side cable connection options

Various fuse options

International standards compliance

XR04.48 and XR08.48 Rectifier Modules

PCC Supervision Module

Description
Aspiro DC power systems offer a range of solutions for diverse applications such as broadband access, cable
head ends, micro/pico BTS Cells, Enterprise, E911, and GSM-R. Aspiro uses highly-efficient, dense, and
reliable XR04.48 & XR08.48 rectifier modules and is highly-adaptable to provide a complete solution for
today's global applications. Its system management is accomplished via a pluggable PCC system controller,
complete with remote accessing functionality with an Ethernet, web server, and SNMP interface.
Highly-flexible distribution options offer the optimum 1U or 2U shelf solution for space-critical applications. In
addition, installation within compact environments is made simple and includes reduced-depth distribution
shelves catering for rear or side cable connection.

MCD10014 Rev. 1.1, 14-Sep-07

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

System Components

XR04.48/XR08.48 Rectifier Modules


The Aspiro shelf system utilizes plug-in rectifier modules
based upon a soft-switching approach. Features include
wide input operating range, wide operating temperature,
full self-protection and three LEDs for immediate rectifier
status indication. Refer to the XR04.48/XR08.48 Rectifier
Module data sheet for further information.

Model

Voltage

Power
(max)

Current
(max)

XR04.48

48 VDC

420 W

9.1 A

XR08.48

48 VDC

837 W

18.2 A

PCC Supervision Module


The PCC Supervision Module is an advanced system
supervisor for complete local and remote system
monitoring. PCC features include:

Menu guided operation

Battery management including battery testing

Ethernet/web server and SNMP Interface

Low voltage disconnect

Hot-pluggable unit

Temperature compensation

Battery Symmetry measurement

User-programmable alarm routing

Refer to PCC Controller data sheet for further details.

MCD10014 Rev. 1.1, 14-Sep-07

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

System Components (Continued)


Distribution Modules
The Aspiro power system uses front
access fuse distribution modules in order
to allow in-service replacement of fuses.
The product can be supplied with a variety
of fuse arrangements.

Additional Features

AC Connection Rear or side screw terminals connection for simple field installation
19, 23 or ETSI mounting available
Flexible Connection Rear or side connection of load circuits and ancillary signals

Aspiro Shelf Options

1U Combination Shelf Option (1.6 kW)

2U Shelf Option (2.4 kW)

2U Shelf Option (3.2 kW)

MCD10014 Rev. 1.1, 14-Sep-07

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

Model
Options
1U Combi-Shelf

2U Power System

2U Power System

Output Power
(max. per system)

1.6 kW

2.4 kW

3.2 kW

Rectifier Modules
(max. per system)

2x 400 W Rectifier
or
2x 800 W Rectifier

3x 400 W Rectifier
or
3x 800 W Rectifier

4x 400 W Rectifier
or
4x 800 W Rectifier

Single Phase
or
3-Phase

Single Phase
or
3-Phase

Output

Input
Single Phase

AC Input Connections
(230 VAC)

Distribution
Battery Fuse (Qty)

Load Fuse (Qty)


(max.)

15

N/A

10

10

Load GMT Fuse (Qty)

Battery
Low Voltage Battery
Disconnect (LVBD)
Temperature
Compensation
Battery Symmetry
Connections

Yes
Yes
1

Dimensions
W x H x D (mm)

19/ETSI/23 x 44.45 x 280

19/ETSI/23 x 88.9 x 280

19/ETSI/23 x 88.9 x 280

Mounting

19 / ETSI / MID-MOUNT

19 / ETSI / MID-MOUNT

19 / ETSI / MID-MOUNT

Rear

Rear

Rear

Yes

Yes

Mechanical

Cable Entry

Options
Partial Load
Disconnect (PLD)

N/A

N/A

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

MCD10014 Rev. 1.1, 14-Sep-07

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

CMP 3.48 Rectifier Module

Features

RoHS lead-solder-exempt compliant


208/240 VAC input
48 VDC output
Input overvoltage disconnection
Thermal protection, with derating
Active load sharing
Hot-swappable
Up to 91% efficient
Natural convection cooling
Low weight
International standards compliance

Description

The Power-One CMP 3.48, for use in the Galero Series of power systems in our convection cooled
rectifier series, provides advanced resonance switch mode technology (softswitching). An onboard
microcontroller and an RS 485 data bus provide monitoring of basic functions, status, and identification
information to the system controller (GMC).
The CMP 3.48 rectifier module is optimized for telecom applications and is designed to work in numerous
subrack/shelf configurations incorporating the GMC controller and varying distribution options.

Galero Power System


NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

AUG 17, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

CMP 3.48 Rectifier Module

Input
Model

CMP 3.48

Current (max.)

205-240V AC +10% single


phase, 44-66 Hz
(185-160V at reduced
power output)
<2.5 A

Soft Start

<12 A peak max. 5 ms

Harmonics

EN 61000-3-2
(Power factor > 0.98
typical)
EN 61000-4-5

Input Voltage

Surge
Immunity
Fuse

T 3.15A

Connection

DIN 41612F

EMC

EN 61000-6-2, EN 610006-3, FCC Part 15 Class B

Output
Model

CMP 3.48

Output
Voltage

45-56 VDC

Power (max.)

364 W @ 56 VDC
354 W @ 54.5 VDC
6.5 A

Current (max.)
Efficiency
(at
55-100% load)

>91%

Tolerance

Vout +/- 1.0%

Transient
Response

+/- 5% at load variation


10-90% or 90-10%
recovery time 10 ms
Typical <5% of nominal
current
<100 mV p-p
(BW. 30 MHz)
<2 mV, according to
CCITT norms
FCI power connector

Load Sharing
Ripple
Psophometric
Connection
EMC

AUG 17, 2006

Mechanical
Dimensions
(WxHxD)

43 x 120.8 x 264.5 mm
(1.7 x 4.75 x 10.4 in.)

Weight

1.1 kg (2.4 lb)

Cooling

Natural convection

Insulation

Reinforced insulation, tested at:


4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.75 kVDC secondary-ground
IP20

Enclosure

Up to 7 modules per shelf


Mounting
Other Technical Data
EN 60950
Safety
UL 1950 and IEC60950 Class 1
CSA C22-2 No. 950
Short-circuit proof, automatic current
Protection
limiting, selective shutdown of
modules at excessive output
voltage. Thermal protection reduces
the output power at environmental
temperatures above maximum level.
Shut down at >75 C. Input overvoltage disconnecting at >265 VAC
with automatic reset at >250VAC.
Indications

Green LED

Red LED

EN 61000-6-2,
EN 61000-6-4

Power ON
High output voltage/
shut down, Low
voltage/ module
failure

Audible
Noise

<35 dBA

Operating
Temperature

-25 to +55 C up to 2000 m


-25 to +45 C above 2000 m

Storage
Temperature

-40 to +85 C

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B
ETS 300 019-2-1
Storage:
Environment
ETS 300 019-2-2
Transport:
ETS 300 019-2-3
Operation:
GR 63 Core Zone
Earthquake:
4
*Average performance for a single module.
Radiated EMC

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP16.48 Rectifier Module Data Sheet

Description
The Power-One FMP16.48 rectifier provides
extremely reliable DC power in the highest
possible density.
This rectifier module
incorporates the latest in power monitoring
solutions using an internal microprocessor that
gives up-to-the-second updates to the system
controller and adjacent rectifiers. This
guarantees tightly controlled load sharing
among rectifiers and provides status and
identification information to the controller.
At only four rack units high, these compact
rectifiers provide up to 1600 watts and allow up
to 10 rectifier modules in a 23-inch subrack or
eight modules in a 19-inch subrack. Designed
with diversity in mind, the FMP16.48 rectifier is
able to operate in a complete range of indoor
and outdoor applications.

Features

23-inch PPR16 Subrack

MCD10086 Rev. 1.1, 2-Oct-08

Page 1 of 2

RoHS lead free solder and lead solder


exempted products are available

Compact 4-rack unit height

717 W/L (11.75 W/in)

205/240 VAC single-phase input

Input overvoltage disconnection

Thermal protection

Hot-swappable

No adjustments required

93,5% typical efficiency

Active and droop current sharing

International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP16.48 Rectifier Module Data Sheet

Input

Mechanical

Model

FMP16.48

Input Voltage

100-240 VAC 15% single


phase (44-66 Hz)
(185-85 V at derated output
power)

Current (max.)

<10 A

Soft Start

<13A /1ms

Harmonics

EN 61000-3-2
(Power factor > 0.98 typical)

Dimensions
(WxHxD)

51 x 177 x 280 mm
(2.0 x 6.97 x 11.02 in)

Weight

2.2 kg (4.85 lb)

Cooling

Fan-cooled, speed-controlled, and alarmed

Insulation

Reinforced insulation, tested at:


4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.75 kVDC secondary-ground

Enclosure

IP20

Mounting

19in/ 4U subrack up to 8 modules


23in/ 4U subrack up to 10 modules

Surge Immunity

EN 61000-4-5

Fuse

2 x F 12.5A (line & neutral)

Connection

FCI 51939-066

Other Technical Data

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Safety

EN 60950-1
UL 60950-1, IEC60950-1,
and CSA C22.2 No. 60950-1

Protection

Short circuit proof, automatic current


limiting, selective shutdown of modules at
excessive output voltage. Thermal
protection reduces the output power at
environmental temperatures above
maximum level. Shut down at >75 C with
an automatic restart. Input overvoltage
disconnecting at >275 VAC with automatic
reset at >260 VAC.

Alarms

High output voltage/ shutdown, Low


voltage/ module failure. Each alarm has an
LED indicator on the front panel.

Indications

Green LED

Power ON

Yellow LED

Current limit/ thermal


protection. Com. failure
(flashing)

Red LED

Module failure/ high


output voltage/
shutdown

Output
Model

FMP16.48

Output Voltage

45-57 VDC

Power (max.)

1600 W @ 45-57 VDC


(input >185 VAC)
675 W @ 45-57 VDC
(input 185 - 85 VAC)

Current (max.)

32 A

Efficiency
(at 40-90% load)

>93%, typical 93.5%

Tolerance

Vout 1.0%

Transient
Response

5% at load variation
10-90% or 90-10%
recovery time 50 ms

Load Sharing

<5% of nominal current

Ripple

<100 mV p-p (BW 30 MHz)

Psophometric

<2 mV, according to CCITT


norms

Audible
Noise

<60dBA

Connection

FCI 51939-066

EMC

EN 61000-6-2, EN 61000-6-4

Operating
Temperature

-40 to +65 C up to 2000 m


-40 to +55 C above 2000 m

Storage
Temperature

-60 to +85 C

Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:
Earthquake:

NUCLEAR AND MEDICAL APPLICATIONS - Power-One


products are not designed, intended for use in, or authorized for
use as critical components in life support systems, equipment
used in hazardous environments, or nuclear control systems
without the express written consent of the respective divisional
president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including
safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject
to change without notice.

MCD10086 Rev. 1.1, 2-Oct-08

Page 2 of 2

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3
GR 63 Core Zone 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 18.48 Rectifier Data Sheet

Description
The FMP18.48 rectifier incorporates resonancesoft-switching technology to reduce component
stresses, providing increased system reliability
and a best-in-class efficiency. With a wide-input
operating voltage range of 84-300 VAC and linear
derating of output power with input voltage, the
FMP18.48 maximizes power availability in
demanding utility power environments.
These compact rectifiers support up to eight 4U
high rectifier units delivering up to 9 kW of power
while the 23 shelf can deliver up to 18 kW of
power. A wide variety of distribution options are
available to provide the maximum system
flexibility for a wide range of communications
applications that demand efficiency, reliability,
and flexibility including wireless base stations,
remote switches, and broadband access.

Features

23-inch PPR18 Subrack

MCD10087 Rev. 1.1, 2-Oct-08

Page 1 of 2

RoHS compliant for all six substances

Leading power density of 807 W/L


(13.2 W/in)

Rugged Input voltages of 84-300 VAC


with linear power derating

Input overvoltage disconnection

Thermal protection

Hot-swappable

93% typical efficiency

International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 18.48 Rectifier Data Sheet

Input

Mechanical

Model

FMP 18.48

Input Voltage

100-240 VAC 15% single


phase (44-66 Hz) up to
300VAC (185-85 V at
derated output power)

Current (max.)

<11.5 A

Soft Start

<13A /1ms

Harmonics

EN 61000-3-2
(Power factor > 0.98 typical)

Dimensions
(WxHxD)

51 x 177 x 280 mm
(2.0 x 6.97 x 11.02 in)

Weight

2.2 kg (4.85 lb)

Cooling

Fan-cooled, speed-controlled, and alarmed

Insulation

Reinforced insulation, tested at:


4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.75 kVDC secondary-ground

Enclosure

IP20

Mounting

19in/ 4U subrack up to 8 modules


23in/ 4U subrack up to 10 modules

Surge Immunity

EN 61000-4-5

Fuse

2 x F 12.5A (line & neutral)

Connection

FCI 51939-066

Other Technical Data

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Safety

EN 60950-1
UL 60950-1 and IEC 60950-1
CSA C22.2 No. 60950-1

Model

FMP 18.48

Protection

Output Voltage

45-58 VDC

Short circuit proof, automatic current


limiting, selective shutdown of modules at
excessive output voltage. Thermal
protection reduces output power at
environmental temperatures above
maximum level. Shut down at >70 C with
an automatic restart. Input overvoltage
disconnecting at >310 VAC with automatic
reset at >=300 VAC.

Alarms

High output voltage/ shutdown, Low


voltage/ module failure. Each alarm has an
LED indicator on the front panel.

Indications

Green LED

Power ON

Yellow LED

Fan pre-warning /
thermal derating.
Com. failure (flashing)

Red LED

Module failure/ high


output voltage/
shutdown

Output

Output Power
Characterisitc

1800W

(50-56 VDC)
1050W

750W

85V

130V

185V

300V

Po max = 1800
Linear derate: 1800 to 1050 W

Current (max.)

38 A

Efficiency
(at 40-90% load)

>92.5%, typical 93%

Tolerance

Vout 1.0%

Transient
Response

5% at load variation
10-90% or 90-10%
recovery time 50 ms

Audible
Noise

<60 dBA

Load Sharing

<5% of nominal current

Ripple

<100 mV p-p (BW 30 MHz)

Operating
Temperature

-40 to +55 C up to 2000 m


-40 to +45 C above 2000 m

Psophometric

<2 mV, according to CCITT


norms

Storage
Temperature

-60 to +85 C

Connection

FCI 51939-066

Radiated EMC

EMC

EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:
Earthquake:

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not


designed, intended for use in, or authorized for use as critical components
in life support systems, equipment used in hazardous environments, or
nuclear control systems without the express written consent of the
respective divisional president of Power-One, Inc.

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3
GR 63 Core Zone 4

TECHNICAL REVISIONS - The appearance of products, including safety


agency certifications pictured on labels, may change depending on the date
manufactured. Specifications are subject to change without notice.

MCD10087 Rev. 1.1, 2-Oct-08

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP25.48 Rectifier Module Data Sheet

Features

Leading power density of up to 27 W/in3


Rugged input voltage range of 90-300 VAC
Thermal protection
Hot-swappable
92.5% typical efficiency
International standards compliance

Description
The FMP25.48 rectifier incorporates resonant technology to reduce component stresses, providing
increased system reliability and a best-in-class efficiency. The rectifier features a wide input operating
voltage range to maximize power availability within demanding utility power environments.
These compact rectifiers support up to 12.5kW in a 1RU 23 shelf. A wide variety of distribution options
are available to provide the maximum system flexibility for a wide range of communications applications
that demand efficiency, reliability, and flexibility including wireless base stations, remote switches, and
broadband access.

Typical Configuration
25kW in 23, 6RU with Controller
Load & Battery Distribution

MCD10064 Rev. 1.5

10kW in 19", 5RU

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP25.48 Rectifier Module Data Sheet

Input

Mechanical Data

Model

FMP25.48

Input voltage

Nominal: 100-240V AC

Dimensions
Weight
Cooling

Permitted variation:
85-300V AC

Insulation

Derated Output:
85-180V AC
Current (max.)

<18A

Soft Start

ETSI ETS 300 132-1

Harmonics

EN 61000-3-2
Power Factor > 0.98 Typical

Surge immunity

EN61000-4-5

Fuse

Two 25A Fast Blow (Live &


Neutral)

EMC

EN61000-6-2, EN6100-6-3
FCC Part 15 Class B

Enclosure
Mounting

Other Technical Data


Safety

Output voltage

46-57 VDC
Po Max = 2500W

Efficiency

92.5%

Tolerance

Vout 1.0%

Transient response

5% at load variation 10-90%


or
90-10% recovery time 50 ms

UL 60950-1/ CAN/CSA-C22.2
No. 60950-1-03, 1st Ed.
EN60950-1: 2006
IEC 60950-1:2001

Output
Output power
(50-56 VDC)

107 x 337 x 40mm (WxDxH)


2 kg
Fan-cooled,
speed controlled
4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.2 kVDC secondary-ground
IP20
19in/ 1U subrack up to
4 modules

Protection

Short circuit proof, automatic


current limiting, selective
shutdown of modules at
excessive output voltage.
Thermal protection.

Alarms

High output voltage/ shutdown,


Low voltage/ module failure.

Indicators

Green LED Power ON


Yellow LED Current limit,
thermal protection

Load sharing

<5% of nominal current

Ripple

<100mV p-p (BW 20 MHz)

Psophometric

<2mV, according to CCITT norms

EMC

EN 61000-6-2, EN 61000-6-4

Com. failure flashing


Red LED Module failure/ high
output voltage/ shutdown
Audible noise

<60 dBA

Operating
temperature

-40 C to +55 C up to 2000 m


Reduced spec -40 C to -20 C
Derated output power 55 C to
75 C
For 3000m altitude derate by
5 C

Storage temperature

-60 to +85C

Environment

Storage: ETS 300 019-2-1


Transport: ETS 300 019-2-2
Operation: ETS 300 019-2-3
Earthquake: GR 63 Core Zone 4

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

MCD10064 Rev. 1.5

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 32.48 Rectifier Module

Features

RoHS lead free and lead-solder-exempt


products are available
697 W/L (11.42 Watts/in3)
Front or mid-mount
85 to 276 VAC single-phase input
Input overvoltage disconnection
Thermal protection
Hot-swappable
No adjustments required
93,5% typical efficiency
International standards compliance

Description
The Power-One FMP 32.48 rectifier provides extremely reliable DC power in the highest possible density.
The module incorporates the latest in power monitoring solutions using an internal microprocessor that
gives up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly
controlled load sharing among rectifiers and provides status and identification information to the
controller.
At only four rack units high, these compact rectifiers provide up to 3200 watts and allow up to five rectifier
modules in a 23-inch subrack or four modules in a 19-inch subrack. Designed with diversity in mind, the
FMP 32.48 rectifier is able to operate in a complete range of indoor and outdoor applications.

23-inch Forza Subrack

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

AUG 18, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 32.48 Rectifier Module

Input
Model

FMP32.48

Mechanical
Dimensions
(WxHxD)

105 x 177 x 280 mm


(4.14 x 6.97 x 11.02 in)

Weight

4.2 kg (9.26 lb)

Cooling

Fan cooled, speed controlled, and


alarmed
Reinforced insulation, tested at:
4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.75 kVDC secondary-ground
IP20

Current (max.)

2 separate inputs, each at


100-240 VAC 15% single phase
(44-66 Hz)
(185-85V at de-rated output
power)
<2 x 10 A

Soft Start

<2 x 13 A/1 ms

Harmonics

EN 61000-3-2
(Power factor > 0.98 typical)

Enclosure

Surge Immunity

EN 61000-4-5

Mounting

Fuse

4 x F 12.5A (line & neutral)

Connection

FCI 51939-066

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Output
Model

FMP 32.48

Output Voltage

45-57 VDC

Power (max.)

3200 W @ 50-57 VDC (input


>185 VAC)
1350 W @ 50-57 VDC (input
185 - 85 VAC)
64 A

Input Voltage

Current (max.)

Insulation

19 in/ 4U subrack up to 4 modules


23 in/ 4U subrack up to 5 modules
Other Technical Data
EN 60950
Safety
UL 1950 and IEC60950
CSA C22-2 No. 950
Short-circuit proof, automatic
Protection
current limiting, selective shutdown
of modules at excessive output
voltage. Thermal protection reduces
the output power at environmental
temperatures above maximum level.
Shut down at >75 C with an
automatic restart*. Input overvoltage disconnecting at >275 VAC
with automatic reset at >260 VAC.
High output voltage/ shutdown, Low
Alarms
voltage/ module failure. Each alarm
has an LED indicator on the front
panel and a common potential free
contact for external signaling.
Green LED
Power ON
Indications

Efficiency
(at 40-90% load)

>93%, typical 93,5%

Tolerance

Vout +/- 1.0%

Transient
Response
Load Sharing

+/- 5% at load variation


10-90% or 90-10%
recovery time 50 ms
<5% of nominal current

Ripple

<100 mV p-p (BW. 30 MHz)

Yellow LED

Psophometric
Connection

<2 mV, according to CCITT


norms
FCI 51939-066

Red LED

EMC

EN 61000-6-2, EN 61000-6-4

AUG 18, 2006

Current limit/
thermal
protection. Com.
failure (flashing)
Module failure/
high output
voltage/ shutdown

Audible Noise

<60 dBA

Operating
Temperature

-40 to +65 C up to 2000 m


-40 to +55C above 2000 m

Storage
Temperature

-60 to +85 C

Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:
Earthquake:

Page 2 of 2

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3
GR 63 Core Zone 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System

Galero Power System


Shelf Systems

Shelf Systems

Input
Model

Galero 1750

Galero 2450

Input

230/400V AC 3-phase
205-240V AC 1-phase
Site configurable

230/400V AC 3-phase
205-240V AC 1-phase
Site configurable

Single input

Single input

Inputs

(max.)

Output
Rectifier Modules

(max.)

Battery Outputs

Load Outputs

10

Yes

48V DC Version

Yes

Features
GMC

GMC

Low Voltage Battery


Disconnection (LVBD)

Yes

Yes

Temp. Comp. Charge

Yes

Yes

Supervision

Battery
Battery Symmetry Inputs

(max.)

Mechanical
Dimensions (WxHxD)

483x125x280mm

483x125x280mm

Mounting

19in., ETSI

19in., ETSI

Cable Entry

AC - Rear
DC and signals -Top

AC - Rear
DC and signals -Top

Temp. Comp. Charge

Yes

Yes

Battery Symmetry
Measurement

Yes

Yes

Ethernet Network Interface

Yes

Yes

Partial Load Disconnect

N/A

N/A

Integrated Surge Arrestors

N/A

N/A

Options

Description

Features

The Galero Power System provides


large power system features in costeffective, rack-mounted form factors.
These
power solutions provide
rectification,
control
and
power
distribution all in one compact system
while offering extensive local and remote
power system and battery monitoring.

System management is accomplished


through the system controller (GMC).
Status indication is made via LEDs, while
detailed information and remote operation
are accomplished through the PC-based
PowComTM software package.

High reliability
Simple installation and operation
Natural convection cooling - no fans
RS232 interface for remote operation
Form C dry alarm contacts
Intelligent battery management
Pluggable controller and DC distribution
modules
Optional Ethernet (SNMP compatible) interface
module
International standards compliance

Note: All specifications are subject to change without notification.

11V0005-033 Galero SY V3.0 Rev. C

www.power-one.com

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System


Shelf Systems

System Configurations

System Components

Rectifier Module
The Galero Shelf System utilizes plug-in rectifier
modules based on a soft-switching approach.
Features include 2xLED for rectifier status indication,
thermal protection with de-rating and input overvoltage disconnection with automatic reset.
Galero 1750 System
All-in-one 125 mm high shelf system for integration into standard
19 or ETSI cabinets.
Complete subrack for five rectifier modules, supervision module
and DC distribution with battery breakers (1-2) and load breakers
(9-10).

Rectifier Features
Model

Voltage

Power
(max.)

Current
(max.)

CMP 3.48

48V DC

364W

6.5A

Supervision Module - GMC


Advanced system supervision is accomplished using a
microprocessor based module that allows both local and
remote system monitoring.
GMC Features

Galero 2450 System


All-in-one 125 mm high shelf system for integration into
standard 19 or ETSI cabinets.
Complete subrack for seven rectifier modules, supervision
module and DC distribution including battery breakers (1-2) and
load breakers (2-3).

Advanced system monitoring


RS232 interface for remote operation
Battery management and testing
Automatic testing
Low voltage battery disconnect (LVBD)
Temperature compensation
Battery symmetry measurement
Monthly logging of battery parameters including temperature-hours
Site programmable Flash EPROM
Programmable alarms
Programmable logic circuit
Optional Ethernet interface through SNMP and/or TCP/IP

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System


Shelf Systems

System Configurations

System Components

Rectifier Module
The Galero Shelf System utilizes plug-in rectifier
modules based on a soft-switching approach.
Features include 2xLED for rectifier status indication,
thermal protection with de-rating and input overvoltage disconnection with automatic reset.
Galero 1750 System
All-in-one 125 mm high shelf system for integration into standard
19 or ETSI cabinets.
Complete subrack for five rectifier modules, supervision module
and DC distribution with battery breakers (1-2) and load breakers
(9-10).

Rectifier Features
Model

Voltage

Power
(max.)

Current
(max.)

CMP 3.48

48V DC

364W

6.5A

Supervision Module - GMC


Advanced system supervision is accomplished using a
microprocessor based module that allows both local and
remote system monitoring.
GMC Features

Galero 2450 System


All-in-one 125 mm high shelf system for integration into
standard 19 or ETSI cabinets.
Complete subrack for seven rectifier modules, supervision
module and DC distribution including battery breakers (1-2) and
load breakers (2-3).

Advanced system monitoring


RS232 interface for remote operation
Battery management and testing
Automatic testing
Low voltage battery disconnect (LVBD)
Temperature compensation
Battery symmetry measurement
Monthly logging of battery parameters including temperature-hours
Site programmable Flash EPROM
Programmable alarms
Programmable logic circuit
Optional Ethernet interface through SNMP and/or TCP/IP

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System

Galero Power System


Shelf Systems

Shelf Systems

Input
Model

Galero 1750

Galero 2450

Input

230/400V AC 3-phase
205-240V AC 1-phase
Site configurable

230/400V AC 3-phase
205-240V AC 1-phase
Site configurable

Single input

Single input

Inputs

(max.)

Output
Rectifier Modules

(max.)

Battery Outputs

Load Outputs

10

Yes

48V DC Version

Yes

Features
GMC

GMC

Low Voltage Battery


Disconnection (LVBD)

Yes

Yes

Temp. Comp. Charge

Yes

Yes

Supervision

Battery
Battery Symmetry Inputs

(max.)

Mechanical
Dimensions (WxHxD)

483x125x280mm

483x125x280mm

Mounting

19in., ETSI

19in., ETSI

Cable Entry

AC - Rear
DC and signals -Top

AC - Rear
DC and signals -Top

Temp. Comp. Charge

Yes

Yes

Battery Symmetry
Measurement

Yes

Yes

Ethernet Network Interface

Yes

Yes

Partial Load Disconnect

N/A

N/A

Integrated Surge Arrestors

N/A

N/A

Options

Description

Features

The Galero Power System provides


large power system features in costeffective, rack-mounted form factors.
These
power solutions provide
rectification,
control
and
power
distribution all in one compact system
while offering extensive local and remote
power system and battery monitoring.

System management is accomplished


through the system controller (GMC).
Status indication is made via LEDs, while
detailed information and remote operation
are accomplished through the PC-based
PowComTM software package.

High reliability
Simple installation and operation
Natural convection cooling - no fans
RS232 interface for remote operation
Form C dry alarm contacts
Intelligent battery management
Pluggable controller and DC distribution
modules
Optional Ethernet (SNMP compatible) interface
module
International standards compliance

Note: All specifications are subject to change without notification.

11V0005-033 Galero SY V3.0 Rev. C

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

www.power-one.com

GMC Controller Module Data Sheet

Features
User controls and interfaces:

Intelligent battery management:

User-selectable alarm parameters

Temperature compensation with programmable

40-event data logging

compensation factor

Password-controlled environment

Automatic and manual load testing

RS232 Interface and Form Cdry

Battery voltage and symmetry monitoring

alarm contacts

Capacity testing

Programmable alarm routing

Low-voltage disconnect

Programmable logic unit

Optional plug-in Ethernet interface (PNI module)

Description
The Galero Microprocessor Controller (GMC) from Power-One provides comprehensive monitoring
and control of the Galero Power System. This digital controller monitors total system conditions
including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and
circuit breaker status.
The GMC enables data storage of system configuration information such as battery type, installation
date, and system commission date. Visual notification of alarm and warning conditions are indicated
by front panel LEDs, while descriptions of the alarms are provided through RS232 communication
using PC-based PowCom software package.
To meet individual site requirements, the GMC contains a Programmable Logic Unit that can be
programmed to monitor and control specified requirements. This allows actions to be set, alarms to be
triggered, and outputs to be activated based on internal and external signal monitoring, comparing,
and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

MCD10018 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

GMC Controller Module Data Sheet

Input

Other Technical Data

Voltage

N/A

Current

<200mA at 48V

Interface
Display
Internal Communication
External Communication

Indications

Controls
Signal Inputs (via alarm
interface)

N/A
RS485 data bus
RS232 Serial interface for
remote control from a PC with
PowCom software. TCP/IP or
SNMP available by using the
optional plug-in Ethernet
interface (PNI card)
Green LED - Power ON
Yellow LED - System Warning
Red LED System alarm
N/A
2 battery symmetry (12V
increments)
1 battery temperature sensor
3 analogue inputs for general
use
2 digital inputs for general use

Software

Site upgradeable through


EPROM flash

Language

N/A

Alarms
Alarm History

Alarm Contacts

Alarms

The last 40 events are saved


and include a time and date
stamp.
Four potential free changeover
alarm contacts. Two open
collector outputs for LVD.
1*
High System Voltage Low
1*
System Voltage
1*
Load/ Battery Disc.
3*
Mains Error
2*
DC Fuse Failure
4*
Battery Failure
2*
Module Failure
4*
Battery Temp. Alarm
4*
Symmetry Failure
1*
Battery Fuse Failure
2*
High Load
1*
Urgent Module Failure
2*
Communication Failure

Dimensions
(WxHxD)

60 x 125 x 250mm
(2.4 x 4.9 x 9.8in.)

Weight

0.5kg (1.1lbs.)

Operating
Temperature

-25 to +55C

Environment

Storage:
Transport:
Operation:

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Battery Management
Battery
Disconnection

A feature that allows voltage


disconnection of batteries.

Boost Charging

Manual time controlled or automatic


boost charging with adjustable time and
voltage levels.

Battery Test

Automatic or manual testing of batteries


up to four times per year. Variables
include: test duration, end voltage, Ah,
and allowable symmetry variation.

Symmetry
Measurement

Optional tool that measures batteries for


early detection of thermal runaway.
Allows for separate measurements of up
to 2 parallel battery branches, each
divided into four blocks.

Temperature
Compensation
Charging

Allows continuous adjustment of output


voltage according to battery temperature.
Feature includes adjustable
compensation factor and separate
thresholds for alarms.

PLD

N/A

Enhanced Battery
Monitoring

Monthly logging of essential battery


parameters: average/ peak temperature,
temp. hours, current, charging voltage
and symmetry voltage. Stores
parameters for 5 years.

* All alarms are indicated using an LED . The numbers


represent an example of alarm routing:
1) Urgent alarm, 2) Service alarm, 3) Main AC Failure,
4) Battery related failure 16 additional user-defined alarms
available.

MCD10018 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Guardian Power System Data Sheet


(Cabinet System)

GUARDIAN POWER SYSTEMS


Protecting your network reliability

Powerful - High density (27W/in) with configurable


configurations of 12.5kW or 25kW and 720 Ah battery
backup per cabinet

Connected State of the art system controller with selfguided operation. SNMP and web compatible.

Sophisticated management features


extend the battery life and monitor critical site equipment
such as HVAC and generators

Intelligent

Rugged Design caters for poor grid quality supply

Guardian modular DC cabinet systems are designed to meet rigid telecom applications with very high
reliability and flexibility for future expansion.
Rectifier and battery combination cabinets are configurable to allow 12.5kW or 25kW rectifier
capacity together with DC distribution, controller and battery backup in a single footprint.
Options include battery and load disconnect, AC surge protection and various DC and AC
distributions.
Ideal for radio base stations, broadband nodes and core sites.

MCD10063 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Guardian Power System Data Sheet


(Cabinet System)

Technical Specification
600 x 600 x 1400/1800/2000mm (WxDxH)

Mechanical

Dimensions

Output

Voltage

-48VDC

Maximum Power

12.5kW / 25kW

Output Current

250 / 500A

Efficiency

92.50%

Rectifier types

FMP25.48G

Battery Breakers

1-6 off (max 125A)

(23.6 x 23.6 x 55.12/70.9/78.74)

DC Distribution

1-3 off (max 250A)

AC Input

Load Breakers

26 x breakers (2-63A) maximum

Battery Capacity

Upto 720Ah using 4 x 180Ah strings

Voltage

1 or 2 x 230VAC 3 phase TN ()
1 or 2 x 400VAC 3 phase IT (Y)

Monitoring & Control

Frequency

47-63Hz

Input Current

<18A per rectifier (FMP25)

Power Factor

0.97

Surge Protection

Optional

Controller

ACC or PCC

Alarm relays

4 standard. Option for 10 with ACC

Local Interface

4 x 20 LCD, 4 key menu, USB*/RS232

Remote interface

Ethernet / modem with POWCOM software

Visual Indication

Green LED System On


Yellow LED Message(s)
Red LED Alarm(s)

Battery Management

Connections

Compliance

External Digital I/O

2 x Inputs, 2 x Outputs (open collector)

Symmetry Inputs

6 or 12*

Programmable LVD

1 x 300A or 500A

Programmable PLD

Max 1 or 2* x 125A, 200A, 400A.

Battery Connections

Battery cable, M8 lugs

AC connection

16mm (4 AWG) max.

Load breaker connections


Alarm connections

Negative termination directly from breakers.


Common positive from busbar.
1.5mm (14 AWG) max.

EMC

EN 300 386
EN 61000-6-3 (Emission)
EN 61000-6-2 (Immunity)

Environmental

Safety

IEC 60950

Operating Temperature

-40C to +65C, derating after 55C

Storage Temperature

-40C to +85C

*Option for ACC only


NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending
on the date manufactured. Specifications are subject to change without notice

MCD10063 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series
iB-PDU, Power Distribution Unit Data Sheet

Features

Applications

Telecom

Safety compliance with EN60950, UL60950,


CAN/CSA-C22.2 No.60950, for use inside
end-use ITE/Telecommunication Equipment only

iB-48V series based Power Distribution


Unit, an electronic limiting, interrupting
and monitoring device for standard
telecom -48V systems

Up to 10 power users (-48 VDC Input)


in a 10A current range.

Dimensions: 19 x 2U x 121mm,
(482.6 x 88 x 121mm)

Current rating up to 40A+40A

Constant current delay before tripping


allows no bus voltage drop

Programmability of most relevant


parameters and remote control for
status and working values via RS232
port

Easy to replace

Manual ON/OFF/reset with no-lock


pushbutton switch; accidental tripping
free

CE branded

Conformity to the applicable


requirements of CAN/CSA-C22.2. No.
235 (Supplementary Protectors) and
UL 1077 (Supplementary Protectors
for Use in Electrical Equipment)

Description
Based on Power-Ones revolutionary iBreaker, the modular iB-PDU is a configurable distribution unit
19x2U. The standard configuration distributes two input A+B sources -36Vdc / -60Vdc to 10 users. The
electronic circuit breaker assures no bus voltage drop, remote controllability, durability, reliability and a
faster response to short-circuit versus electromagnetic breakers.
The iBreaker device measures current, voltage, and energy consumption; then transmits the information via
serial link for precise system monitoring. It allows control of tripping conditions and implements low voltage
disconnection functionality for load shedding strategies to preserve critical loads. The iBreaker software
provides adjustable configurations that maximize system flexibility. Custom configurations are available.

Model Summary and Ordering Code


Model Number
3B350010000

MCD10061 Rev. 1.1

Description
10 iBs in a 2U x 19 rack; in and out rear connectors

Page 1 of 3

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series
iB-PDU, Power Distribution Unit Data Sheet

Technical Specifications
iBreaker-PDU Characteristics

General Characteristics

Input Voltage

-36 / -60 VDC


( -48 VDC nominal )

Dimensions (WxHxD)

19 x 3.46 x 4.76 in
(482.6 x 88 x 121 mm)

Input Current Rating

50 A (line A); 50A (line B)

Weight

4.5 kg (12.05 lb)

Double separated input source line available

Operating Temperature

-5 C to +55 C

Filter for each source line

Durability (no. of on/off


switch operations

20,000 operations

MTBF

1,000,000 hours

Cooling

Natural convection

Safety Approvals and


Marks

EMC, CE Marked

Front Panel

10 bicolor LEDs; red lit when


switches are opened/tripped;
green lit when switches are
closed

Rear Panel

Input connectors: 2 x male inlet


(3Pins) FM3W3

No. of Electronic
switches

10

No. of electromagnetic circuit


breakers

Power source
/breaking capacity

5 kA

Reverse polarity protection


iB rating

10A

Max current rating


(IMax)

10A

Max inrush current


(ILimit)

17A x 10 ms

Output connectors: 10 x AMP p/n


350825-1

Max current after


trip (Istandby)

< 0.1A

Signal connector: 1 x DB-15Pins


type

Voltage Drop (typ)

0.15V

Short-circuit sense
time

300 s (followed by 10
ms pre-programmed
current limit interval

Remote monitor connector: DB9Pins RS232 with standard


grounding point

Current limit delay


time

5 ms (custom delay times


available)

Protection

Latched overcurrent and


short-circuit protection;
overtemperature
protection; system
catastrophic fuse present

MCD10061 Rev. 1.1

Page 2 of 3

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series
iB-PDU, Power Distribution Unit Data Sheet

Mechanical Drawings

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

MCD10061 Rev. 1.1

Page 3 of 3

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series Data Sheet


iB Family for Intelligent Distribution

Features

iB-48V series is an electronic limiting, interrupting


and monitoring device for standard telecom -48V
systems Two models for different input (24V & 48V)
and output of 230VAC

Ratings from 5A to 60A

Constant current delay before tripping allows no bus


voltage drop

Serial communication link with programmability of


most relevant parameters and remote reading of
status and working values

Height, width, and mounting holes compatible with


commercial electromechanical breakers

Telecom

Optional board controller to easily connect to up to


22 breakers

Safety compliance with EN60950, UL60950,


CAN/CSA-C22.2 No.60950, for use inside
end-use ITE/Telecommunication Equipment only

CE, cCSAus and Kema marks according to


EN/UL/CSA 60950 for ITE and Telecommunication
Equipment

Conformity to the applicable requirements of


CAN/CSA-C22.2. No. 235 (Supplementary
Protectors) and UL 1077 (Supplementary Protectors
for Use in Electrical Equipment)

Applications

Description
iBreaker Series Electronic Limiting, Interrupting and Monitoring Device
Power-Ones revolutionary iBreaker is a totally new product that increases performance and facilitates the design
of telecom 48V power systems. The iBreaker outperforms regular electromechanical interrupting devices by
delivering a higher level of reliability, consistency and durability in the field. The load is disconnected in a clean
way within 200 microseconds avoiding transients on the DC input bus. The iBreaker device measures current,
voltage and energy consumption then transmits the information via serial link for precise system monitoring. It
allows control of tripping conditions and implements low-voltage-disconnect functionality for load shedding
strategies to preserve critical loads. The iBreaker software provides adjustable configurations that maximize
system flexibility.

Model Selection
Model

Accessory List & Ordering Codes


Current Rating
(Amps)

Accessory
Model

Description

iB-48V-5A

iB-CTR

Controller. Controls up to 22 iBs

iB-48V-10A

10

iB-BS

iB-48V-20A

20

iB-48V-30A

30

Bus Strip, allows serial I/O


connection to the individual iB;
up to 10 iBs to one iB-CTR

iB-48V-40A

40

iB-WI

I/O Wire to connect the iB to


the iB-BS

iB-48V-50A

50

iB-48V-60A

60

MCD10066 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series Data Sheet


iB Family for Intelligent Distribution

Input

Other Technical Data

Input voltage range

-60 VDC to -36 VDC

Display

Isolation

1100 Vrms live circuits to


frame. Frame heat sink is
floating and can be
connected to Earth.

Status bicolor LED and


ON/OFF pushbutton

Operating Temperature

-5 C to 55 C; convection
cooling

EMI

Immunity: EN61000-6-2
Emissions: EN50081-1

MTBF

1,500,000 hours at 30 C
min according to Bellcore
TR-NWT-000332

Expected Operational Life

35 years min

Safety Approvals

CE and EN60950 for ITE


and Telecommunications
Equipment

Dimensions
WxHxD

0.79" x 2.48" x 4.22"


(20 x 63 x 107.38mm)

Input UV protection

Input OV protection

Automatic; programmable 48V to -36V. Factory


setting -35.8V 0.2V
Automatic, programmable.
Factory setting -65V 0.2V

Output
Tripping conditions

Time to trip = 10ms max

Overload

Automatic with current


limitation; programmable

Short circuit

Automatic with current


limitation

Manual ON/OFF

Pushbutton; protected
against accidental activation

Remote ON/OFF

Serial link

Overtemperature

Automatic

Mechanical Drawings

Dimensions are in mm.


NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

MCD10066 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet


12 kW; Low THD
Features

Applications

Telecom
IT
Industrial

Please contact Power-One for information


regarding Magnum Rack Systems.

Low profile: 3U overall height


High efficiency: > 91%
Active Power Factor Correction: > 0.99
Total harmonic distortion: < 5%
3-phase 380-480 V nominal voltage input
(50 or 60 Hz) with no neutral
One phase fault tolerant
Hot pluggable
Input and output circuit breaker on board
Display and control panel
Thermal overload protection with derating
Not available in the U.S.; please contact a
Power-One representative
19" or 23" shelf-mountable
Lightweight: 50.26 lb (22.8 kg)
Safety standards: EN 60950, CAN/CSA-C22.2 N
60950-00 / UL 60950

Description
The Magnum REC-J200EH Rectifier is a 12,000-watt electronic three-phase, switch-mode power supply module
which provides low total harmonic distortion (THD). Designed for superior performance in telecom, industrial, and IT
applications, its reduced size makes it one of the most compact force-cooled rectifiers in service to deliver 200
amps. Measuring 19" wide, 5.2" high, and with a depth of 19.09", this product has a power density in excess of
7 W/in3.
The REC-J200EH's combines a digitally-controlled, active Power-Factor-Correction circuit with an innovative
electronic design to achieve electrical efficiencies in excess of 90% and THD below 5%. It offers minimized cost and
reduced installation time, and its reliability ensures maximum system uptime for critical applications.
In addition, a "smart" user interface makes remote or local programming and monitoring of all major rectifier
parameters easy. Remote computer communications is available through an RS-485 serial connection interface
(SCI). The Magnum is UL listed and CSA, CE, IEC, and Broadcast NEBS Level 3 certified.

Magnum Model Selection and Ordering Information


Model

REC-J200EH

APR 12, 2007

Input Voltage
Nominal
3-Phase
(Vrms)

Input
Frequency
Range (Hz)

Factory Set
Programmable
Output Voltage
(VDC)

Programmable
Output Voltage
Adjustment Range
(VDC)

Output
Current
(Amps)

380 to 480

47 to 63

-54.5

-40 to -60

200

Page 1 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet


12 kW; Low THD

ELECTRICAL SPECIFICATIONS
Input Specifications
Parameter
AC Input Voltage

Conditions/Description
3-phase, line-to-line.

Input Frequency

Min.

Nom.

Max.

Units

340

380 to
480

530

Vrms

63

Hz

10

47

Line current unbalance


between phases
Line current harmonics

Meets IEC 61000-3-2.

Power Factor

Pout > 25%.

> 0.99

W/VA

Total Harmonic
Distortion (THD)

Pout > 50%.

<5

Turn-ON delay

4.5

sec

Input withstanding
voltage

560

Vrms

Max.

Units
VDC

60

VDC

Mains connector

P4/63-S-PCD from Multi Contact.

Output Specifications
Parameter

Conditions/Description

Min.

Factory set output


voltage
40

Nom.
54.5

Output VDC
Adjustment Range

Programmable.

Ripple

BW 20 MHz.
Wide band, BW 20 MHz.
Psophometric noise CCITT weighted.
Electrical noise.

500
100
2
32

mVpp
mVrms
mVpp
dBrnc

Efficiency

(92% @ full load, Vin 360 Vrms).

92

Output Voltage
Regulation

0.4

Output Current

200

ADC

Thermally derated
current limit

Linear derating from 50 C to 70 C.


220 ADC @ 50 C.
110 ADC @ 70 C.

Output Power

Continuous.

12

kW

Output Power

Continuous; 2-phase operation, 1-phase loss.

kW

Hold-up time

@ 340 Vrms input and full load.

20

ms

Output voltage rise


time

500

ms

Output voltage walk in


time

10

Current sharing

<5

Output connection

APR 12, 2007

Bus bar copper blades.

Page 2 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet


12 kW; Low THD

Fault Protection
Parameter

Conditions/Description

Min.

Nom.

AC Input Overvoltage
Protection
Input Breaker
Protection

Internal circuit breaker with mains On/Off


switch.

Output Overcurrent
Protection

Current limitation:
220 ADC @ Vout 54.5 VDC.
200 ADC @ Vout = 60 VDC.

Output Short Circuit


Protection

220 ADC, resumes operation when short is removed.

Output Overvoltage
Protection

Three levels of protection:

Max.

Units

530

Vrms

37.5

70

Catastrophic OV: 65 VDC hardware latch.


Programmable OV: 56 to 66.1 VDC, default 62 VDC,
turn-Off, non-latching.
Second OV (delayed 100 ms): 60 VDC (SELV)
turn-Off and latch.
Output Undervoltage
Protection

Adjustable, just alarm indication, constant


current behavior down to 0V.

Overtemperature (OT)
Protection

Shutdown if ambient temperature exceeds


70 C; with automatic self-recovery.

Overtemperature
driven by fan failure

Shutdown with latch-up.

36V

Overtemperature
threshold
Output Protection

Internal circuit breaker with power switch and


mechanical latch.

350

Environmental Specifications
Parameter

Conditions/Description

Operating Temp
at Full Load

Linearly derated to 6 kW at 70 C.

Altitude

Operating.
Non-Operating.

Storage Temp

-5

-40

Humidity

85% relative humidity @ 40 C, non-condensing.

Output Voltage
Temperature
Coefficient

0.01% per C within rated load.

EMI

EN 55022, class B.

Cooling

Forced cooling front to rear.

APR 12, 2007

Min.

Page 3 of 5

Nom.

Max.

Units

55

13K
40K

ASL ft
ASL ft

85

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet


12 kW; Low THD

Interface Signals/Controls
Parameter

Conditions/Description

Alarms

Optorelay contact: OV, OT, OC, rectifier fail (AC


loss, OV, OT, fan failure).

Connection

Molex Mini Fit 15-24-9245 or equivalent.

Min.

Nom.

Max.

Units

Min.

Nom.

Max.

Units

Regulatory & Safety


Parameter

Conditions/Description

cCSAus

EN 60950, CSA-C22.2 No. 60950-00, UL 60950 Approved.

Kema

Approved.

CB Report Approval

Approved.

CE Mark for LVD

Approved.

RoHS

Compliant.

Isolation

Primary-to-Secondary: 3000 Vrms.


Primary-to-Ground: 1500 Vrms.
Secondary-to-Ground: 500 Vdc.

Mechanical Specifications
Parameter
Dimensions

Weight

APR 12, 2007

Max.

Units

Depth (inches).

Conditions/Description

19.09

in

Depth (mm).

484.9

mm

Width (inches).

19.00

in

Width (mm).

482.6

mm

Height (inches).

5.21

in

Height (mm).

132.3

mm

Pounds.

50.26

lb

Kilograms.

22.8

kg

Page 4 of 5

Min.

Nom.

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet


12 kW; Low THD

Reliability
Parameter
Calculated MTBF

Conditions/Description
TR-TSY-000332 (excluding fans)

Min.
250,000

Nom.

Max.

Units
Hours

Mechanical Outline Drawing:

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

APR 12, 2007

Page 5 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

MIDI PODS Enclosure Platform Data Sheet


Advance Product Release

Features

Modular, versatile design allows selection


of various cabinets to suit most applications

19 and 23 power cabinet options provide


up to 9RU payload to match network
equipment requirements

Matched power and battery cabinets


provide a low impact solution; either can
serve as a standalone product

Flexible thermal management solutions


matched to load and environmental
parameters

IP55/NEMA 3R protection rating (power


cabinet)

Simple trouble-free installation, operation,


and maintenance

Description
Extend the life of your network with the MIDI PODS enclosure platform, an ideal solution for all
wireless, fiber, and transmission networks.
The versatile MIDI PODS outdoor enclosure system supports valuable network equipment, backup
batteries, and power systems in a range of severe environmental conditions. The MIDI PODS has
a flexible and modular design matched with network equipment to provide a low impact solution.
The MIDI PODS rugged construction and a thermally-insulated power cabinet with sealed loop
heat exchangers or air conditioners ensures network integrity in the most challenging
environments. Its naturally-cooled battery cabinet provides a very cost-effective storage platform.

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as
critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the
express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.

SEP 15, 2006 revised to OCT 02, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

MIDI PODS Enclosure Platform Data Sheet


Advance Product Release
Electrical

23

DC Power

Various DC systems options to


match line & load requirements
Circuit breakers & fuse options
available

Distribution

19

Environmental Control

Mechanical

Heat exchanger
Air conditioners

Closed loop door mounted,


55 W/K
600 W
2000 BTU @ L35/L35

Accessories

Power Cabinet
Dimensions (WxDxH)
Battery Cabinet
Dimensions (WxDxH)
Security

680 x 650 x 800

Cable Entry

Bottom

Service light

65
55
70/95
60
15
15
Aluzinc, powder coated

Circulating fans

For improved battery


ventilation and temperature
control

Grounding bars

Located in plinth for Mains, DC


& RF

Weight
(kg)

Power
Battery
Plinth

Material

600 x 600 x 800 Cable bridges

680 x 650 x 800 600 x 600 x 800 Cable gland plates


680 x 650 x 1100
Lockable, vandal-proof hinges,
Heater
multi-point locking mechanism

Mating with major OEM BTS


equipment.
Tailored to suit site RF, DC,
AC Coaxial
900 W

Mounting

PAD mounted, Installation via lifting Standards Compliance


eyes
Safety
IEC 950, UL 950
Equipment Mounting
Height

9RU (with 2RU power subrack)

Rugged Cabinet
Construction

Environmental
Protection

IP55 (IEC529) / NEMA Type


3R

Distribution

Flexible AC & DC Load


center options

Rugged, thermally insulated


construction
Lockable cabinet including
vandal-proof hinges and multipoint locking mechanism
A4 document holder

Environmental
Management
Sealed loop heat exchangers
or air conditioners ensure
network integrity in the most
challenging environments.

DC Power
Rugged, flexible rectifier
options to match various load
& line conditions
65 C operating temperature
ensures maximum uptime in
high temperature environments
93.5% efficiencies reduces
thermal loads

SEP 15, 2006 revised to OCT 02, 2006

Flexible Payload Options

Page 2 of 2

Up to 450 Ah batteries
DC Power Systems
AC load centers
9RU network equipment such
as radio base stations &
microwave equipment

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCC Controller Module Data Sheet

Features

RoHS compliant for all six substances

User controls and interfaces:

User-selectable alarm parameters

Password controlled environment

RS232 Interface and Form C dry


alarm contacts

Programmable alarm routing, logic unit


and analog inputs

Ethernet interface version available

Intelligent battery management:

Description

Temperature compensation with


programmable compensation factor

Automatic and manual load testing

Battery voltage and symmetry monitoring

Remaining battery capacity


measurement

Low voltage disconnect

The Power-One Prime Controller Card (PCC) is a pluggable microprocessor controller that provides
monitoring and control for a broad range of Power-One DC Power Systems. The PCC monitors all system
parameters including: DC voltage, rectifier current, rectifier temperature, system capacity, battery
parameters, and circuit breaker status.
Alarm and warning notifications are indicated by front panel LEDs, and through potential free alarm
contacts that allow remote signaling. External monitoring of alarms is accomplished through an RS232
port using PC-based PowCom software. The PCC has an optional Ethernet port allowing monitoring
and control over a TCP/IP network. Alarms can mapped via SNMP traps to customer OSS platforms such
as HP Openview
To meet individual site requirements, the PCC contains a Programmable Logic Unit that can be used to
monitor and control specified requirements. This allows individual alarm routing and logic operations to be
set as actions, alarms to be triggered, and outputs to be activated based on internal and external signal
monitoring, comparing, and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as
critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the
express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.

OCT 26, 2006 revised to FEB 07, 2007

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCC Controller Module Data Sheet

Input
Voltage
Current
Interface
Display

Other Technical Data


18-30 VDC (+24 V Version)
30-60 VDC (-48 V Version)
<200 mA at 48 V/ <400 mA at 24 V

Dimensions
(WxHxD)

Actual dimensions vary with respect


to the system used. Contact Sales.

Weight

0.2kg (0.44 lb)

Optional 3x16 character LCD

Operating
Temperature

-40 to +70 C

Storage
Temperature

-40 to +85 C

EMC

EN 61000-6-2, EN 61000-6-3,
EN 300 386-2
Storage:
ETS 300 019-2-1
Transport:
ETS 300 019-2-2
Operation:
ETS 300 019-2-3

Internal
Communication

RS485 Data Bus (20 modules max.)

External
Communication

RS232 Serial interface for remote


control via modem or directly from a
TM
PC with PowCom software.
Optional Ethernet port allowing
monitoring and control over a TCP/IP
network and alarm mapping via
SNMP traps.
Green LED Power ON
Yellow LED System warning
Red LED System alarm
Battery current reading (via shunt)
Output voltage reading
6 x analog inputs for battery
symmetry reading or general use
1 x battery temperature sensor
1 x load fuse failure
1 x battery fuse failure
1 x LVD disconnect
1 x PLD disconnect
1 x LVD/PLD reconnect
4 x Alarm contact (Form C)
3 x LED
1 x LCD (option)
Site upgradeable by EPROM/ Flash

Indications

Signal Input

Signal Outputs

Software

Environment

Battery Management
Battery
Disconnection

Allows voltage controlled


disconnection of batteries.

Boost
Charging

Manual time controlled or automatic


boost charging with adjustable time
and voltage levels.

Battery Test

Automatic or manual testing of


batteries up to six times per year.
Variables include test duration and
end voltage.

Symmetry
Measurement

Optional tool that measures


batteries for early detection of
thermal runaway. Allows for
separate measurements of up to 6
parallel battery branches using midpoint measurement.

Temperature
Compensation
Charging

Allows continuous adjustment of


output voltage according to battery
temperature. Features include
adjustable compensation factor and
separate thresholds for high
temperature alarms.

Load
Shedding
(PLD)

Optional feature that allows voltage


or time controlled disconnection of
non-essential load.

Alarms
Alarm Contacts
Alarms

4 potential free change-over alarm


contacts
Low Voltage Alarm
High Voltage Alarm
Batteries on Discharge
Overvoltage Shutdown Alarm
High Load (Rectifier Capacity Alarm)
Battery Test Failure
Battery Symmetry Alarm
Mains Failure
Module Alarm
Urgent Module Alarm
Battery Fuse Failure
Load Breaker Failure
Battery/Load Disconnect Alarm
High Battery Temperature Alarm
Low Battery Temperature Alarm
Temperature Probe Failure
16 x Additional User Definable
Alarms

OCT 26, 2006 revised to FEB 07, 2007

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCS Controller Data Sheet

Features

RoHS lead free and lead-solderexempted products are available


User Controls and Interfaces:
Simple menu-guided operation using
front panel mounted pushbuttons and
an LCD
User-selectable alarm parameters
40 event data logging
Password controlled environment
Multiple language options
RS232 Interface and Form C dry
alarm contacts
Intelligent Battery Management
Temperature compensation with
programmable compensation factor
Automatic and manual load testing
Battery voltage and symmetry
monitoring
Capacity testing
Low voltage disconnect
Monthly data logging

Description
The Power-One Power Controller System (PCS) provides comprehensive monitoring and control for a
broad range of Power-Ones DC power systems. This digital controller monitors total system conditions
including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters and
circuit breaker status.
The PCS enables data storage of system configuration information such as battery type, installation date
and system commission date. In addition, the PCS is capable of monitoring up to 128 rectifiers and 128
sub-controllers within a power system. Visual notification of alarm and warning conditions are indicated
by front panel LEDs, while descriptions of the alarms are provided through an LCD or can optionally be
accessed remotely using a PC modem, or over a network using an optional Network Interface (PNI)
module.
To meet individual site requirements, the PCS contains a logic operator that can be programmed to
monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and
outputs to be activated based on internal and external signal monitoring, comparing and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

APR 04, 2007

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCS Controller Data Sheet

Input
Voltage
Current

Interface
Display
Internal
Communication

External
Communication
Indications

Controls
Signal
Collection
Software
Language

Other Technical Data


Dimensions
508 x 133 x 57mm
(WxHxD)
(20 x 5.25 x 2.25in.)
Weight
1.6kg (3.5lbs.)
Operating
-25 to +55C
Temperature
Storage
-50 to +85C
Temperature
Environment
Storage:
ETS 300 019-2-1
Transport:
ETS 300 019-2-2
Operation:
ETS 300 019-2-3

18 - 72 VDC
<200 mA at 48V, <400 mA at
24V

2x20 character LCD with


backlight
RS485 Data Bus for
communication with a maximum
of 128 rectifiers and 128 subcontrollers
RS232 serial interface for
remote control from a PC with
PowCom software
Green LED - Power ON
Yellow LED - System warning
message
Red LED - System failure
message
Four pushbutton controls
Wide range of interface units
with analog and digital
input/outputs
Site upgradeable by EEPROM
flash
Multiple language options

Battery
Battery Disconnection
Boost Charging

Battery Test

Symmetry Measurement
Alarms
Alarm History

The last 40 events are saved


and include a time and date
stamp.
Alarm Contacts 6 potential free change-over
alarm contacts. Two open
collector outputs for LVD
operation.
Alarms
High System Voltage
1*
Low System Voltage
2*
Load/ Battery Disc.
4*
Mains Error
3*
Distribution Fuse Failure
4*
Battery Failure
6*
Module Failure
5*
Battery Temp. Alarm
6*
Symmetry Fault
6*
Battery Fuse Failure
4*
High Load
5*
Battery Fuse Disc.
5*
Urgent Module Failure
4*
Communication Failure
5*
Partial Load Disc.
4*
* All alarms are indicated using an LED and
displayed in the LCD. The numbers represent an
example of alarm routing.
Sixteen additional
alarms are available and are configurable by
changing the PCS EEPROM.
APR 04, 2007

Page 2 of 2

Temperature
Compensation Charging

PLD

Enhanced Battery
Monitoring

Allows voltage controlled


disconnection of batteries.
Manual time controlled or
automatic boost charging
with adjustable time and
voltage levels.
Automatic or manual
testing of batteries up to
four times per year with a
10 test memory. Variables
include: test duration, end
voltage, and amount of
Ahs to be discharged
during test.
Optional tool that measures
batteries for early detection
of thermal runaway. Allows
for separate measurements
of up to 12 parallel battery
branches, each divided into
four blocks.
Allows continuous
adjustment of output
voltage according to
battery temperature.
Features include adjustable
compensation factor and
separate thresholds for
high temperature alarms.
Optional feature that allows
voltage or time controlled
disconnection of nonessential load.
Monthly logging of
essential battery
parameters, including
temperature, temp. hours,
current, charging voltage,
and symmetry voltage.
Parameters are stored for 5
years.

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PODS Enclosure Platform Data Sheet

Features

Modular, versatile design allows cabinets to


be paralleled

27, 40 & 49 RU payload options to match


power, battery, and network equipment
requirements

Flexible thermal management solutions


matched to load & environmental parameters

Seismic rated (Zone 4)

IP55/NEMA 3R protection rating

Flexible top and bottom cable entry ports


facilitate cable routing to adjoining equipment

Description
Extend the life of your network with the PODS enclosure platform, an ideal solution for all wireless,
fiber, and transmission networks.
The versatile PODS outdoor enclosure system supports valuable network equipment, backup
batteries, and power systems in a range of severe environmental conditions. The PODS flexible and
modular design allows cabinets to be paralleled and matched with network equipment.
The PODS rugged seismic-rated aluminium construction with direct fan cooling, sealed loop heat
exchangers or air conditioners ensures network integrity in the most challenging environments.

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.

MCD10069 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PODS Enclosure Platform Data Sheet

Electrical
DC Power
Distribution

Various DC systems options to


match line & load requirements
Circuit breakers & fuse options
available

Environmental Control
Heat exchanger
Air conditioners
Fan filter

Mechanical
Dimensions
(WxDxH)
Security
Cable Entry
Weight (excl
equipment)
Material
Mounting

Equipment
Mounting
Height
Width
Depth

800 x 850 x 1364/1940/2350 mm


32" x 34" x 54/77/93"
Lockable, vandal-proof hinges,
multi-point locking mechanism
Top (left, right, or rear) and bottom

Accessories
Cable bridges

Closed-loop door mounted air-air,


55, 150, 220 W/K options
650, 1500, 2000 W options
2200/5100/6800 BTU @ L35/L35
200, 350 W/K

Heater

Mating with major OEM BTS


equipment.
Tailored to suit site RF, DC, AC
Coax needs
400 W, 900 W

Up to 200 kg

Grounding bars

Mains, DC, RF

Marine-grade aluminum
PAD mounted; installation via
removable lifting eyes

Service light
Smoke Detector

Cable gland plates

Standards Compliance
27, 40, & 49 RU
23" (with various 19" options)
600 mm, 24"

Safety
Environmental protection
Seismic

Environmental
Management

IEC 950, UL 950


IP55 (IEC529) / NEMA Type 3R
Zone 4

DC Power
Rugged, flexible rectifier
options to match various
load & line conditions
o
65 C operating
temperature ensures
maximum uptime in high
temperature environments
93.5% efficiencies reduce
thermal loads
Flexible DC load center

Direct fan cooling, sealed


loop heat exchangers or
air conditioners ensure
network integrity in the
most challenging
environments.

AC Distribution
Configurable with Surge
protection, RCCD, circuit
breakers, generator socket,
bypass switch

Flexible Payload Options


Up to 720 Ah batteries
Network equipment such as
radio base stations &
microwave equipment

Rugged Cabinet
Construction
Rugged seismic-rated aluminum
construction
Lockable cabinet including vandalproof hinges and multi-point locking
mechanism

MCD10069 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet


1500 Watt, 1U Compact Inverters
Features

Applications

Telecom
IT
Industrial

Safety in compliance with IEC60950:1999, 3rd edition;


EN60950:2000; UL60950, 3rd edition; CSA Standard
C22.2 No.60950-00, 3rd edition

New, compact design: 1U height x 19" width


x 14.94" depth; 19" rack-mountable
High efficiency: up to 93%
True sine wave output
Parallelable output with current share and
synchronization of multiple inverters working in
parallel
Front panel LCD display to monitor and set the
main parameters
RS-485 serial link
Constant input current sink from battery for
extended life
Optional hot-swappable configuration
Optional internal Static Transfer Switch
In the -STS version, ON line (primary source to the
load) or OFF line mode (UPS like)
Configurable for being used as Three Phase
source, 3 units

Description
The SLI 15 Inverter Series provides an ideal solution for telecom, IT, and industrial applications. Due to innovative
technology solutions like the patent-pending "Compact Coil", the SLI 15 inverters pack 1500 watts of power into a
light (5.6 kg) and compact package that is mountable in 19" racks and is only one rack unit high. The SLI 15
Inverter Series offers four models for different input (24 and 48VDC) and output (115 and 230VAC) voltage
combinations. An integrated controller, along with an optional internal Static Transfer Switch (STS) enable flexible
and scalable systems which are truly "plug and play", and require no external subsystems. The inverters can be
stacked up to the power level needed by each application and also have the capability to be configured for
generating a 3-phase voltage source.
Electrical performance of the SLI 15 is exemplary of a top-of-the-market product with efficiency that peaks at 93%
and a patent-pending control algorithm that compensates current harmonics on the DC side without using bulky and
expensive filters. The SLI 15 includes a powerful on-board Digital Signal Processor (DSP) that allows easy
programming of main parameters through use of its front-panel keypad and LCD display. In addition, the SLI 15 can
be interfaced with an RS-485 serial communications link.

SLI Inverter Model Selection and Ordering Information


Input Voltage
(VDC)

Output Voltage
Nominal (VAC)

Overall Output
Voltage Range
(VAC)

Frequency
Range (Hz)

SLI-24-115

24

115

100 to 120

47 to 63

SLI-24-230

24

230

200 to 240

47 to 63

SLI-48-115

48

115

100 to 120

47 to 63

SLI-48-230

48

230

200 to 240

47 to 63

Model

The following suffixes should be added to the model number to order options. For an internal Static Transfer
Switch, please add the suffix "-STS". For AC terminal blocks, please add the suffix "-SC". For Hot Plug version,
please add the suffix -HP. For Neutral tied to Ground, please add the suffix -GN.

MCD10058 Rev. 1.0

Page 1 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet


1500 Watt, 1U Compact Inverters

ELECTRICAL SPECIFICATIONS
Input Specifications
Parameter

Conditions/Description

DC Input Voltage
Range
Input Current

Min.

Nom.

Max.

Units

20
40

24
48

36
72

VDC

100
48

Amps

<10

Amps

24 VDC Models @ 18 VDC:


48 VDC Models @ 36 VDC:

Inrush current

Output Specifications
Parameter

Conditions/Description

Min.

Nom.

Max.
1500

Units
Watts

115
230

120
240

VAC

60

Hz

93

Output Power
Output AC Voltage
Range

Standard is Vac floating from Ground; -GN


version is available with Neutral connected to
Ground (Grid Input shall be supplied by means
of an isolation transformer)

110
200

Frequency

50Hz/230Vac, 60Hz/115Vac

50

Efficiency
Load Power Factor

lagging or leading

Crest Factor

Ipk/Irms

Regulation in single
mode

Load: over full operating range. R-Load


Line: over full operating range. R-Load

Regulation in parallel
mode

Load: over full operating range. R-Load

Total Harmonic
Distortion

On Resistive Load.

MCD10058 Rev. 1.0

0.33

1
4

Page 2 of 5

230
115

-3
-0.1

+1
+0.1

-6
-8.5

0
0

<2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet


1500 Watt, 1U Compact Inverters

Fault Protection
Parameter

Conditions/Description

Min.

Nom.

Max.

Units

Input Overcurrent
Protection

24 VDC Models; Internal Fuse.


48 VDC Models; Internal Fuse.

140
70

Amps

Input Overvoltage
Protection

24 VDC Models:
48 VDC Models:

37,5
74

VDC

Input Undervoltage
Protection

24 VDC Models:
48 VDC Models:

18
36

VDC

Output Overload

115 VAC Models:


230 VAC Models:

1610
1840

Surge

115 VAC Models for 200 ms:


230 VAC Models for 200 ms:

1750
2300

VA

Overvoltage Protection

All outputs are set at 115%, 2 % of nominal.

Undervoltage
Protection

All outputs are set at 85%, 2 % of nominal.

Overcurrent Protection

115 VAC Models: 1 A to 14 A selectable.


230 VAC Models: 1 A to 8 A selectable.

Safety Overcurrent
Protection

By safety circuit breaker:


115 VAC Models: 15 A.
230 VAC Models: 10 A.

Short-Circuit
Protection

Peak Current type protection:


115 VAC Models: 60 A.
230 VAC Models: 30 A.

Overtemperature
Protection

Visual and acoustic indication 5 C before shutdown at Tamb > 65 C and at Tint > 100 C.

Protection Restore
Modes

The restore mode of each protection can be individually selected to "latch" or "auto-restart".

Environmental Specifications
Parameter

Conditions/Description

Operating Temp
at Full Load

Power Derating: 75W/C: +55 C to +65 C.

Altitude

Operating.
Non-Operating.

Storage Temp

-25

-40

Humidity

90% relative humidity @ 40 C, non-condensing.

Output Voltage
Temperature
Coefficient

0.02% per C within rated load.

MCD10058 Rev. 1.0

Min.

Page 3 of 5

Nom.

Max.

Units

55

13K
40K

ASL ft
ASL ft

85

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet


1500 Watt, 1U Compact Inverters

Interface Signals/Controls
Parameter

Conditions/Description

LCD Panel

2-line LCD panel with keypad for menu navigation.

LED Indicators

4 LED indicators:
Front panel GREEN LED indicates inverter is ON.

Min.

Nom.

Max.

Units

Front panel RED LED indicates a generic fault categorized as:


a. Overtemperature (OT),
b. Fan fail,
c. Input OV, UV, OC, or Output OV, UV, or OC.
General Alarm Signal

Activated by an open photo-relay if in fault mode, available at rear signal connector

Serial link

RS485 port, 500Vdc isolated, available at rear signal connector

Regulatory & Safety


Parameter

Conditions/Description

cCSAus

Approved.

Kema

Approved.

CB Report Approval

Approved.

CE Mark for LVD

Approved.

RoHS

Compliant.

Isolation

Primary-to-Secondary: 3000 Vrms.


Primary-to-Ground: 1000 Vrms.
Secondary-to-Ground: 1500 Vrms.
Signal-to-Ground: 0 Vrms.

Min.

Nom.

Min.

Nom.

Max.

Units

Mechanical Specifications
Parameter
Dimensions

Weight

Max.

Units

Depth (inches)

Conditions/Description

14.94

in

Depth (mm)

379.5

mm

Width (inches)

19.00

in

Width (mm)

482.6

mm

Height (inches)

1.71

in

Height (mm)

43.5

mm

Pounds

12.34

lb

5.6

kg

Kilograms
Connections

DC input: back left, one 6mm diameter hole at each input bar; hot plug version has PCB bars with
pre charging system; subrack for -HP version hosts one inverter, separate purchasing part; plastic
DC input cover is available, separate purchasing part
AC output: back right, IEC320 plug is the standard; screw terminal blocks are with the option SC;
-STS version has IEC320 socket marked Grid Input
Signal: back centre, female Sub-D 15 poles connector, Molex 89263-6062 or equivalent; general
failure alarm, serial port, synchronism for paralleling or three phase, remote on/off.
For paralleling inverters, up to 6, ask for paralleling kit, one per inverter, separate purchasing part
Important: -STS and -GN options are compatible just supplying Grind Input by means of an
isolation transformer, same indication if Neutral is tied to Ground at customer site.

MCD10058 Rev. 1.0

Page 4 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet


1500 Watt, 1U Compact Inverters

Reliability
Parameter
Calculated MTBF

Conditions/Description
At 40 C excluding fan
-STS version, at 40C excluding fan

Min.
250,000
200,000

Nom.

Max.

Units
Hours

Mechanical Outline Drawing:

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

MCD10058 Rev. 1.0

Page 5 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 50 Inverter Series Data Sheet


5000 Watt, 2U Compact Inverters

Features

Applications
Telecom
IT
Industrial

Compact design: 2U height; 19" rack mountable


Front panel LCD display to monitor and set
main parameters
High efficiency: up to 93%
True sine wave output
RS485 serial link
Input reflected ripple current <300 ma rms
@ maximum load
Advanced cooling system to optimize fan life
and minimize noise
Parallelable output
Optional external Static Transfer Switch

Description
The SLI 50 Series of Slim Line inverters provides an ideal solution for telecom, IT, and industrial
applications. Due to innovative technology solutions like the patent-pending Compact Coil", the SLI 50
Series inverters pack 5000 watts of power into a compact package that is 19 rack mountable and only
two rack units high. Electrical performance of the SLI Series inverter products is at the top of the
market with efficiency that peaks at 93% and a patent-pending control algorithm that compensates
current harmonics on the DC side without using bulky and expensive filters. The inverter includes an
on-board powerful Digital Signal Processor (DSP) that allows easy programmability of the main
parameters on the front panel LCD display and keypad.The SLI Series inverters can be interfaced with
RS485.

MCD10067 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 50 Inverter Series Data Sheet


5000 Watt, 2U Compact Inverters

Input

Signal & Control

Nominal input voltage

40-60 VDC (48 VDC)

LCD panel *

Inrush current

ETSI EN 300 132-2


Ver, 2.12, Clause 4.7

4-line LCD panel with


keypad for menu navigation

LED indicators *

Power-On

Input OC protection

Internal MCB 150A (48 VDC)

Generic Fault

Input OV protection

65 VDC (48 VDC)

Over Temperature

Input UV protection

36 VDC (48 VDC)

Fan Fail
Data Communications

Output

* General alarm signal:


by a photo-relay (open if in fault mode)

Output power

5000 W

Output voltage range

230 VAC models:


200 to 240 VAC

Frequency

50 or 60 Hz%

Overload

230 VAC Models: 5500 VA

Efficiency

Up to 93%

Load PF

0.33 1 leading or lagging

Load CF

Operating humidity

0 - 90% non-condensing

Load regulation

-3% 1% over full operating


range

Altitude: operating

13000 feet (3900 meters)

Altitude: non-operating

40000 feet

Output voltage
temperature coefficient

0.02% per C within rated


load

Safety & Environmental


Operating temperature
range

Full load: -25 C to 55 C


Power derating: 75 W/ C;
+55 C to +65 C
Storage: -40 C to 85 C

Line regulation

0.1% over full operating


range

Output noise and ripple

2% pk-pk (20 Hz /20 MHz)

Distortion

<2% on resistive load

Safety agency
compliance

cCSAus, Kema, CB Report,


CE Mark

Overvoltage protection

All outputs set at 115%


2% of nominal

Isolation

Primary-to-secondary
3000 Vrms

Undervoltage protection

All outputs set at 85%


2% of nominal

Primary-to-ground
1000 Vrms

Overcurrent protection

Yes; 230 VAC models; 5A to


25A selectable

Secondary-to-ground
1500 Vrms

Safety overcurrent
protection

By safety fuse; 230 VAC


Models: 30A

Signal-to-ground
0 Vrms

Short-circuit protection

Yes; Ipk; 230 VAC models:


60A

Overtemperature
protection

(Visual and acoustic


indication 5 C before
shutdown) at: Tamb > 65 C
and at Tint > 100 C

Protection restore
modes

The restore mode of each


protection can be individually
selected to "latch" or "autorestart".

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

MCD10067 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 7 Inverter Series Data Sheet


700 Watt, 1U Compact Inverters

Features

Applications

Telecom
IT
Industrial

Compact design: 1U height x 19" width x


380mm depth; 19" rack mountable
Two models for different input (24V & 48V) and
output of 230VAC
High efficiency: up to 90%
True sine wave output
Constant current sunk from DC source for
extended battery life and reduced input filters
(patent pending)
Integrated controller, DSP controlled
Front-panel LED indicators
Force-cooled (rear to sides)
Front connection: AC front plug - DC terminal
blocks
700W continuous duty
PF 1 to 0.33 (Power Factor)
CF up to 4 (Crest Factor)
Thermal overload protection with derating
Lightweight: 4 kg
3kV insulation DC-AC; 1.5kVAC AC-PE
Safety standards: EN 60950,
CAN/CSA-C22.2 No. 60950-00 / UL60950

Description
The SLI 7 Series, Slim Line Inverter, provides ideal solutions for telecom, IT, and industrial applications.
It has lightweight (4 kg) and compact (1U x 19" x 14.8") design, and features peak efficiency up to 90%
with a true sine wave output.
A unique, patent-pending algorithm compensates current harmonics at the DC side, resulting in
extended battery life, reduced dimensions, and improved power density.

Model Selection
Model
SLI 7 24-230
SLI 7 48-230

MCD10065 Rev. 1.1

Input Voltage
(VDC)
24
48

Output
Vo (VAC)
230
230

Page 1 of 2

Io (AAC)
3
3

Power
max (W)
700
700

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 7 Inverter Series Data Sheet


700 Watt, 1U Compact Inverters

Input

Other Technical Data

Nominal input voltage

48 VDC, 24 VDC

Efficiency

90%

Input voltage range

40-72 VDC, (20-36 VDC)

Safety compliances

Input current

< 25A, <50A

Input UV protection

36V 1V, (18V 1V);


hysteresis 3.5V (1.75V)

EN60950:2000,
CSA-C22.2 No. 60950-00,
UL60950, IEC60950

EMI

EN55022 class A

Input OV protection

74V 1.5V, 37.5V 1.5V

Operating temperature

Input withstanding
voltage

75 VDC, (< 40 VDC),


unlimited duration

-25 C to 55 C, 700W.
Linear derating of
-40W/ C up to 65 C

Input protection

30A, (60A); "not


replaceable" fuses

Storage

-40 C to 85 C

Cooling

Forced cooling, rear to side

0.4%

MTBF

250,000 hours

Dimensions
WxHxD

19" x 1U x 14.76"
(482.6 x 43.5 x 37.5mm)

Input voltage regulation

Output
Output power

700W / 800VA
max continuous

Weight

4 kg

Output connection

Front IEC 320 plug

Output voltage

230 VAC or 220 VAC;


front selectable

Input connection

Front screw terminals

Output frequency

50-60 Hz 0.2%

Load regulation

-3% / +1%

Output noise and ripple

2% pk-pk
(20 Hz / 20 MHz)

Total harmonic distortion

<2% on resistive load

Load PF

0.3

Load CF

Overvoltage protection

-370Vpk 2% catastrophic;
latching, 2 ms delayed ;
-115% 2% of nominal;
auto-restart, 200ms delayed

Undervoltage protection

85% 2% of nominal;
auto-restart, 1S delayed

Overload

4A, 200ms delayed

Short circuit protection

Peak current 15A

Safety short circuit


protection

4A, "not replaceable" fuse

Overtemperature
protection

Inlet air temperature >67 C


(shut down)

Internal Overtemperature
Protection

Shut down

Signal & Control


LEDs

230/220, Power, O.T., fault

General failure alarm

Pin 1-4, subD-15 pin

Serial port

Pin 2-3-4, subD-15 pin

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.

MCD10065 Rev. 1.1

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

XR04.48/XR08.48 Rectifier Module Data Sheet

Description
The XR04.48G (400 W) and XR08.48G (800 W) are a
family of single-phase, hot-pluggable, fan-cooled
rectifiers. The high power density of this product offers
the optimum 1U or 2U shelf solution for space-critical
applications.
Both rectifiers offer excellent efficiency as well as wide
operating temperature and wide input voltage range.
Together with advanced technology they enable cost
effective and reliable solutions.
XR04.48 Rectifier Module
The typical applications for this rectifier are both in
indoor and outdoor environments, which is ideal for
broadband access, cable head ends, micro/pico BTS
Cells, and Enterprise, E911, and GSM-R applications.

Features

Wide AC input; 85 to 300 VAC

Wide operating temperature range


-40 to +75 C

Designed for 300 mm deep ETSI


compliant systems

Input overvoltage disconnection

Thermal protection

Hot Swappable

90% typical efficiency

International standards compliance

MCD10017 Rev. 1.1

19/1U Aspiro Subrack Shown

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

XR04.48/XR08.48 Rectifier Module Data Sheet


Input

Other Technical Data

Model

XR04.48G

Input Voltage

85 to 300 VAC
(Nominal: 100-240 VAC)

Input Frequency
Max Input Current
(Nominal Input)
Max Inrush current

47 to 63 Hz
<5.5

Hold-up time
Fuse

20 ms (typ.)
Two 8A fast
blow (line &
neutral)

Operating
Temperature
Range
Storage
temperature
Relative
Humidity
Cooling

XR08.48G

<9.3A

<20 Arms (100 ms)

-40 to 65C (derated +65 to +75C)


(for 3000 m altitude derate by 5C)
-40 to 85C
10 to 90 %RH (operating)
5 to 95 % RH (storage )
Fan-cooled, speed-controlled, alarm
controlled, air flow direction rear to front
<55dBA according ISO7779
Short circuit proof, automatic current limiting,
selective shutdown of modules at excessive
output voltage
Green
Power ON
Yellow
Current limit/ thermal protection
Fan failure / Over temperature
Prewarning / thermal protection
Communication Failure
(flashing)
Red
Module failure/ high output
voltage shutdown

Audible noise
Protection

Two 16 A fast
blow (line &
neutral)

LED
Indication

Output
Output Voltage

46-57 VDC; 53.5 VDC nom

Output Power (nom)

400 W

800 W

Output current

9.1 A max

18.2 A max

Efficiency

Load sharing

88 %(typ.) at
90 %(typ.) at
Iout nom
Iout nom
7.3 W/in3
14.6 W/in3
3% at load variation (10-90% /
90-10%) recovery time 50ms
<5% of nominal current

Output ripple
Psophometric noise

< 100 mV p-p (BW 20 MHz)


<2 mV (accord. ETS300-132-2)

Power Density
Transient Response

Alarms via
RS485

Environment
Storage
Transport
Operation
Damp Heat

Mechanical
Dimension WxHxD
Weight

40.6 (1.6") x 101.62(4") x


228.5(9") mm
1.1 kg

Pmax

Po

Po

Product
Safety

EN60950-1:2001
IEC60950-1-2001

EMC

EN61000-6-3:2001
EN61000-6-2:2001
EN60950-1/A11:2004

Emission
Immunity

4.25kVDC input to output

Reinforced

Insulation

-40V

Temp

+65 +75

85V

Vin

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3
IEC60068-2-78, MIL-STD- 810D section 507.2

Safety

Output Characteristic
Pmax

High output voltage/ shutdown


Low voltage/ module failure

300V

Approvals

2.12 kVDC input to chassis

Basic

0.5 kVDC output to chassis

Functional

UL (tested according EN60950-1/A11:2004) E131905


CAN/CSA-C22.2 No.60950-1-3
TV (tested according EN60950-1/A11:2004)

NUCLEAR AND MEDICAL APPLICATIONS - Power-One


products are not designed, intended for use in, or authorized for
use as critical components in life support systems, equipment
used in hazardous environments, or nuclear control systems
without the express written consent of the respective divisional
president of Power-One, Inc.

CB (tested according EN60950-1/A11:2004)


CE

TECHNICAL REVISIONS - The appearance of products, including


safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject
to change without notice

MCD10017 Rev. 1.1

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Rectifier Data Sheet

Description
The Power-One Xscend rectifier provides
extremely reliable, high density DC power. The
rectifier incorporates the latest in power
monitoring solutions through an internal
microprocessor giving up-to-the-second updates
to the system controller and adjacent rectifiers.
This guarantees tightly-controlled load sharing
among rectifiers and provides status and
identification information to the controller.
At only two rack units high, these compact
universal input rectifiers provide up to 1600
watts and allow up to five rectifier modules in a
23-inch shelf or four modules in a 19-inch shelf.
Designed with diversity in mind, the Xscend
rectifier is able to operate in a complete range of
indoor and outdoor applications.

Features

Xscend Power System

SEP 14, 2006

Page 1 of 2

Compact 2-rack unit height

703 W/L (11.5 W/in3)

Front or mid-mountable

110V/200-240 VAC single-phase input

Input overvoltage disconnection

Thermal protection in all load situations

Hot-swappable

No adjustments required

93.5% typical efficiency

Active and droop current sharing

International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Rectifier Data Sheet

Mechanical

Input
Model

XR1648

Input Voltage

100-240 VAC 15% single phase


(44-66 Hz)
(180-85 VAC at derated output
power)

XR1424

Dimensions
(WxHxD)

102.87 x 88.9 x 241.3 mm

Weight

2.3 kg (4.12 lb)

Cooling

Fan cooled, speed controlled, and alarmed

Insulation

Reinforced insulation, tested at:

(4.05 x 3.5 x 9.5 in)

Current (max.)

<10 A

Soft Start

<13 A/1 ms

4.25 kVDC primary-secondary

Harmonics

>0.98 typical

2.12 kVDC primary-ground

Surge Immunity

EN 61000-4-5

0.75 kVDC secondary-ground

Fuse

12.5 A -line, 12.5 A -neutral

Connection

FCI power connector

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Mounting

23 in/ 2U subrack up to 5 modules

Other Technical Data


Safety

CSA C22-2 No. 950, UL 1950 and


IEC60950/ EN 60950

Protection

Short circuit proof, automatic current limiting,


selective shutdown of modules at excessive
output voltage. Thermal protection derates
the output power 65C ambient temperature.
Shutdown at >75C with automatic restart.
Shutdown is load dependant, at low load typ
85C. Input overvoltage disconnection at
>275VAC with automatic reset at >260VAC.

Alarms

High output voltage/ shutdown, Low voltage/


module failure. Each alarm has an LED
indicator on the front panel.

Indications

Green LED

Power ON

Yellow LED

Current limit/ thermal


protection

Red LED

Module failure

Output
Model

XR1648

Output Voltage

45-57 VDC

22.5-28 VDC

Power (max.)

1600 W

1400 W

at >180 VAC
(50-57 VDC)

at >180 VAC
(25-28 VDC)

675 W

675 W

at 180-85 VAC
(50-57 VDC)

at 180-85 VAC
(25-28 VDC)

Current (max.)

32 A

56 A

Efficiency
(at 40-90% load)

>93%

>90%

(93.5% typical)

(91% typical)

Tolerance

Vout +/- 1.0%, constant voltage


regulation

XR1424

19 in/ 2U subrack up to 4 modules

Transient
Response

+/- 5% at load variation

Audible Noise

<60dBA

10-90% or 90-10%
<5% of nominal current

Operating
Temperature

-40 to +65 C up to 2000 m

Load Sharing
Ripple

<100 mV p-p (BW. 30 MHz)

-40 to +85 C

Psophometric

<2 mV, according to CCITT


norms

Storage
Temperature
Radiated EMC

EN 61000-6-2, EN 61000-6-3,

Connection

FCI power connector

EMC

EN 61000-6-2, EN 61000-6-4

-40 to +55 C above 2000 m

FCC Part 15, Class B


Environment

Storage:
Transport:
Operation:
Earthquake:

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3
GR 63 Core Zone 4

*Average performance for a single module.

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

SEP 14, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System

Xscend Power System


Shelf System

Shelf System
Input
Model

Xscend 23 Shelf

Xscend 19 Shelf

Input

205-250 VAC +/-10%

205-250 VAC +/-10%

Single or multiple inputs

Single or multiple inputs

20

16

10

(max.)

25

20

24V DC Version

Yes

48V DC Version

Yes

Yes

Supervision

XCS

XCS

Expansion

Yes

Yes

Inputs

(max.)

Output
Rectifier Modules

(max.)

Battery Outputs - MCB


(max.)

Load Outputs - MCB


(max.)

External Distribution

(up to 2 shelves)

Yes

Features

Description
Xscend modular DC power shelf systems
provide large power system features in costeffective, rack-mounted form factors. These
shelf power solutions provide rectification,
system management and power distribution
while maintaining high reliability and offering
flexibility for future expansion. The Xscend
systems are based on hot-swappable
rectifier modules with constant output power
available at 1400 (24V) or 1600W (48V) per
module.

Battery
Battery Symmetry Inputs
(max.)

Low Voltage Battery


Disconnection (LVBD)

Yes

Yes

Mechanical
Dimensions (WxHxD)

584x133x274mm
(23x5.25x10.8in.)

483x133x274mm
(19x5.25x10.8in.)

Mounting

23

19

Cable Entry

Rear

Rear

System management is accomplished


through messages and alarms displayed on
the system controllers (XCS) LCD screen
and can also be displayed remotely via the
PC-based PowCom software package.

Options
Temp. Comp. Charge

Yes

Yes

Ethernet Network
Interface

Yes

Yes

Modem Interface

Yes

Yes

Features

TM

AC Input 185-275 VAC

(85-185VAC at de-rated output)

48VDC rectifier with up to 1600W output


24VDC rectifier with up to 1400W output
Fan cooled rectifier modules
Front access design
Temperature hardened -40C to +65C
19 or 23 mounting arrangement
Extensive remote monitoring capabilities
Modular DC distribution with LVD
Power Factor Correction
ETSI Compatible
Modular system from 32A to 640A

Note: All specifications are subject to change without notification.

11V0005-060 Xscend SY V3.1

www.power-one.com

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System


Shelf System

System Configurations

System Components
Rectifier Modules
The Xscend system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs for
power-on, current limit & thermal protection, and module failure.
Rectifier Features
Model

Voltage

Power
(max.)

Current
(max.)

XR 1648

48V DC

1600W

32A

XR 1424

24V DC

1400W

56A

Supervision Modules
Advanced system supervision is accomplished using a
microprocessor based control module that allows both local
and remote system monitoring.
PCS Features

Xscend 23in. System

Xscend 19in. System

An all-in-one 3U-9U (single and four shelf configurations)


high shelf system that can be installed in 23 telecom
cabinet solutions. The system subrack can accommodate
up to 20 rectifier modules, a supervision module (XCS) and
DC distribution with up to 10 circuit breakers (0-4 battery
and 6-10 load breakers). Optional expansion distribution
shelf allows 25 circuit breakers.

An all-in-one 3U-9U (single and four shelf configurations)


high shelf system that can be installed in 19 telecom
cabinet solutions. The system subrack can accommodate
up to 16 rectifier modules, a supervision module (XCS)
and DC distribution with up to 10 circuit breakers (0- 4
battery and 6-10 load breakers). Optional expansion
distribution shelf allows 20 circuit breakers.

Menu guided operation


RS232 interface for remote operation
Battery management and testing
Temperature compensation
Battery symmetry measurement
Optional Ethernet interface through SNMP and/or TCP/IP
Advanced battery management and testing
Digital signal collection via internal RS485 bus
Site programmable flash EPROM
Multiple language choices
Programmable alarms
Programmable logic functions and operations
Monthly data logging

Distribution Module
Advanced distribution is accomplished using a 5U high
external distribution shelf. The shelf is based on
standard plug in circuit breakers and is available in 23in.
and 19in. configurations.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System


Shelf System

System Configurations

System Components
Rectifier Modules
The Xscend system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs for
power-on, current limit & thermal protection, and module failure.
Rectifier Features
Model

Voltage

Power
(max.)

Current
(max.)

XR 1648

48V DC

1600W

32A

XR 1424

24V DC

1400W

56A

Supervision Modules
Advanced system supervision is accomplished using a
microprocessor based control module that allows both local
and remote system monitoring.
PCS Features

Xscend 23in. System

Xscend 19in. System

An all-in-one 3U-9U (single and four shelf configurations)


high shelf system that can be installed in 23 telecom
cabinet solutions. The system subrack can accommodate
up to 20 rectifier modules, a supervision module (XCS) and
DC distribution with up to 10 circuit breakers (0-4 battery
and 6-10 load breakers). Optional expansion distribution
shelf allows 25 circuit breakers.

An all-in-one 3U-9U (single and four shelf configurations)


high shelf system that can be installed in 9 telecom
cabinet solutions. The system subrack can accommodate
up to 16 rectifier modules, a supervision module (XCS)
and DC distribution with up to 10 circuit breakers (0- 4
battery and 6-10 load breakers). Optional expansion
distribution shelf allows 20 circuit breakers.

Menu guided operation


RS232 interface for remote operation
Battery management and testing
Temperature compensation
Battery symmetry measurement
Optional Ethernet interface through SNMP and/or TCP/IP
Advanced battery management and testing
Digital signal collection via internal RS485 bus
Site programmable flash EPROM
Multiple language choices
Programmable alarms
Programmable logic functions and operations
Monthly data logging

Distribution Module
Advanced distribution is accomplished using a 5U high
external distribution shelf. The shelf is based on
standard plug in circuit breakers and is available in 23in.
and 19in. configurations.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System

Xscend Power System


Shelf System

Shelf System
Input
Model

Xscend 23 Shelf

Xscend 19 Shelf

Input

205-250 VAC +/-10%

205-250 VAC +/-10%

Single or multiple inputs

Single or multiple inputs

20

16

10

(max.)

25

20

24V DC Version

Yes

48V DC Version

Yes

Yes

Supervision

XCS

XCS

Expansion

Yes

Yes

Inputs

(max.)

Output
Rectifier Modules

(max.)

Battery Outputs - MCB


(max.)

Load Outputs - MCB


(max.)

External Distribution

(up to 2 shelves)

Yes

Features

Description
Xscend modular DC power shelf systems
provide large power system features in costeffective, rack-mounted form factors. These
shelf power solutions provide rectification,
system management and power distribution
while maintaining high reliability and offering
flexibility for future expansion. The Xscend
systems are based on hot-swappable
rectifier modules with constant output power
available at 1400 (24V) or 1600W (48V) per
module.

Battery
Battery Symmetry Inputs
(max.)

Low Voltage Battery


Disconnection (LVBD)

Yes

Yes

Mechanical
Dimensions (WxHxD)

584x133x274mm
(23x5.25x10.8in.)

483x133x274mm
(19x5.25x10.8in.)

Mounting

23

19

Cable Entry

Rear

Rear

System management is accomplished


through messages and alarms displayed on
the system controllers (XCS) LCD screen
and can also be displayed remotely via the
PC-based PowCom software package.

Options
Temp. Comp. Charge

Yes

Yes

Ethernet Network
Interface

Yes

Yes

Modem Interface

Yes

Yes

Features

TM

AC Input 185-275 VAC

(85-185VAC at de-rated output)

48VDC rectifier with up to 1600W output


24VDC rectifier with up to 1400W output
Fan cooled rectifier modules
Front access design
Temperature hardened -40C to +65C
19 or 23 mounting arrangement
Extensive remote monitoring capabilities
Modular DC distribution with LVD
Power Factor Correction
ETSI Compatible
Modular system from 32A to 640A

Note: All specifications are subject to change without notification.

11V0005-060 Xscend SY V3.1

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

www.power-one.com

DMAC
Controller

Description
The Power-One Digital Meter, Alarm and Control Panel (DMAC) provides comprehensive
monitoring and control for Power-Ones Compac power systems. This digital controller
monitors system conditions including DC voltage and load current, while providing a
variety of alarm and control functions.
DMAC features include user-configurable battery testing, measurement of battery voltage
and current & battery equalization.

Features
Single point system voltage adjust
Programmable timer for battery test or
equalization

Digital meters and test points monitor plant


voltages and current

User-adjustable set points for under/over voltage


and low voltage disconnect

Front panel LEDs for alarms, including:


Equalize alarm
OV/UV alarm
Major alarm
Minor alarm
Rectifier fail
Breaker alarm

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

DMAC
Controller
Interface

Other Technical Data

Display

Digital amp and digital volt meters

Operating
Temperature

-0 to +50C

Digital Meters

3.5 digits, +/-2% accuracy

Storage
Temperature

-50 to +85C

UV/OV
Adjustment

22V/29V for 24VDC +/- 1.5V


44V/58V for 48VDC +/- 1.5V

Humidity

10-90% RH, operating, 5-95%


storage, non-condensing

Equalization &
Battery Test
Timer Range

Altitude
Range

13,000 ft., derate 7C/100 ft.


above 8000 ft.

0.5 seconds to 130 hours

Current
Measurement
DC Shunt

1200A:50mA

User Controls

Timer reset button


System voltage adjustment
Normal/Bypass test switch
Equalize/Battery test switch
Equalize Under/Over voltage adjustment
Undervoltage/Overvoltage

Connection
Points

System voltage test points


System amperage test points

Temperature Compensation

Alarms

Alarms

11V0005-050 DMAC V3.0

Equalize alarm
OV/UV alarm
Major alarm
Minor alarm
Rectifier fail
Breaker alarm

Overview

The temperature
compensation panel works in
conjunction with the DMAC
controller. Temperature
compensation automatically
adjusts the float voltage
according to the ambient
temperature.

Temperature
Compensation
Alarms

Alarms include temperature


delta, which indicates battery
thermal runaway and sensor
failure. In the event of a
sensor or panel failure, the
compensation defaults to the
normal float voltage set by the
controller.

Note: All specifications are subject to change without notification.

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

External Alarm Unit

EAU Module

EAU - Shelf Mount

Description

Features

The External Alarm Unit (EAU) is a network


adapter that allows a Power-One Controller
module to be accessed remotely through a
TCP/IP network.

Allows power systems to be accessed from a

The EAU module has nine digital inputs for


supervision of external equipment and a seven
port HUB for interconnection of other network
devices. Using a 10BASE-T ethernet connection,
the EAU connects any Power-One controller to a
TCP/IP network. This allows the system to be
configured locally through PowCom software or
remotely through a telnet session.
In addition, the EAU module incorporates IP
address filtering to prevent unauthorized access
to the power system.

TCP/IP Network

Compliant with PowCom software


Wall mount or 1U, 19 shelf mount
Uses SNMP protocol for reliable remote
access

10Base-T Ethernet
Nine external inputs
Telnet for system setup
10Mbit 7-port HUB
Easy implementation

EAU
Wall Mount

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

External Alarm Unit


EAU Module

System Monitoring
PowCom Monitoring
Remote system monitoring is accomplished through
PowCom and Alarm Central software packages.
PowCom is a graphic user interface site monitoring
program that allows remote access to system
parameters, alarm history, and battery test data at a
single system location.
Alarm Central allows multiple power systems to be
monitored using a hierarchy based window system
that informs a user of system events, using both
audible and visual alarms.
SNMP Monitoring Software
System monitoring can also be accomplished
through standard SNMP protocols and an enterprise
specific Management Information Base (MIB).
SNMP allows the user to access and monitor system
parameters as well as tracking system variables.

Other Technical Data


Electrical
Communication

Supply Voltages

40 to 60VDC, max 5W

Ethernet Controller

IEEE 802.3, half-duplex

Ethernet HUB

7-ports, 10Base-T

External Inputs

9 contact closure inputs for remote monitoring

Weight

Wall mount 0.42kg (0.93lbs.)


Shelf mount 1.14kg (2.51lbs.)

Dimensions (WxHxD)

Wall mount 200x40x160mm (7.87x1.57x6.3in.)


Shelf mount 19in.x44x155mm (19x1.75x6.1in.)

Ambient Temperature

-10C to +70C

Storage Temperature

-40C to +85C

Mechanical

Environmental

Note: All specifications are subject to change without notification.

11V0005-031 EAU V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Integrity-One Power System


Rack Systems

Description
The Integrity-One Power System is the next
generation solution for today's power system
needs. Using a modular design, the system is
easily upgradeable for future growth. With a
capacity up to 1250 amps, the Integrity-One
system is ideal for either central office or cell
site applications. This system includes multiple
options for user-friendly local and remote
access.
Basic design concepts allow the user to develop
system configurations that meet initial network
capacity requirements with minimum installation
costs while allowing future capacity expansion
through module additions or multi-bay
configurations. This is accomplished by a wide
variety of hot swappable modules, rectifiers and
distributions.
Standard features in each Integrity system
include an advanced microprocessor controller
(PCS). This controller offers an extensive list of
monitoring and control features that can be
accessed locally or remotely through the
standard RS232 connection or through the
optional Power-One Network Interface box,
which allows communication through Ethernet
and SNMP protocols. External reporting can
also be accomplished by using on-board FormC contacts.
In addition to the three systems listed here,
other layouts and individual components are
also available for integration into customer
provided equipment racks, cabinets, outdoor
enclosures, or other power requirements.
Please contact Power-One for assistance with
your unique requirements.

Features

Modular systems from 50-1250A


Up to 91% efficient
Intelligent, programmable controller
Front access distribution panels with optional
load shedding
Local and remote programming and
monitoring
Hot-swappable rectifiers
User-selectable alarm parameters
208/240 VAC input
Extensive battery testing and monitoring
Programmable temperature compensation
Compatible with PowCom PC-based
software

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

The Integrity-One system is available in three different


configurations allowing customers to choose the solution that
is right for them. Each system uses the same basic
components, including:
System Interface Shelf
Alarm Output Connections
Network Interface (Optional)
Battery LVD (Optional)
PCS Controller
PMP25 Rectifier Modules
SDS / PDS Distribution Shelves
Single or Individual Rectifier AC Inputs
Full Rack System
The Integrity-One full rack system allows for up to 1250A at
48V in a single bay by using combinations of Secondary or
Primary Distributions. Each rack is capable of holding up to
five rectifier shelves for 48V applications providing 1250A or
two rectifier shelves for 24V applications providing 1100A.
Multiple racks may be paralleled to produce a maximum total
system capability of 5000A using a single controller in the
primary rack.
Half-Height Rack System
The Integrity-One Half-Height rack system is available at up
to 1100A and can be installed above existing battery stands.
The Half-Height system is ideal for systems requiring
extended battery backup. Up to 44 load breakers can
distribute up to 500A at -48V, or up to 1000A at +24V.
Integrity-One Rack with Battery Trays
The Integrity-One System with battery trays accommodates
up to two rectifier shelves and up to three battery trays
creating a complete power system in a single rack.
Distribution can be achieved through up to 44 load breakers
or fuses (up to 100A rating).

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Integrity-One Power System


Rack Systems

System Components

Distribution Panels
Hot-swappable distribution shelves
Front, middle and rear distribution
positions (waterfall effect) allow for
system cable management
SDS: Secondary Distribution Shelf
Rated at 500A
Plug in CBs up to 100A rating
Plug in fuses up to 100A rating
Accommodates up to 22 circuit
breakers or fuses

PCS Controller
RS485 digital signal data bus
Fully programmable
6 programmable
alarms(upgradeable to 24)
Battery test: manual or automatic
Alarm relay test
Adjustable battery current
Software controlled start-up after
mains outage

PDS: Primary Distribution Shelf


(rated at 1000A)
Up to qty 8 single pole fuses
(100-600A)
Up to qty 8 single pole CBs
(up to 250A rating)
Up to qty 3 double pole CBs
(up to 400A rating)
Up to qty 2 triple pole CBs
(up to 600A rating)
System Interface Shelf
Easy connection of system alarm
signals and wiring
Optional battery symmetry and
temperature probes
Optional Power-One Network
Interface box (featuring ethernet and
SMNP protocol capability)
Optional low voltage disconnect
Battery shunt

Rectifier Shelves
RS485 communication bus
23 shelf allows up to 5 rectifiers
each
Digital current sharing
Individual rectifier or single shelf
AC feed options

Integrity Shown with Optional


AC Distribution Box

PMP25 Rectifier
5 rectifiers into each 4U 23 shelf
Available in 24 or 48VDC
Thermal protection
Fan cooled modules with speed
control and alarms
Hot-swappable
RS485 interface
Low weight
Up to 91% efficiency

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Integrity-One Power System


Rack Systems
Input
Model

Integrity-One 48V

Integrity-One 24V

Input

Single or individual

Single or individual

Inputs

Single input for every 6 rectifier positions (4


inputs for 20 rectifier cabinets)

Single input

Current (at full load)

16A per rectifier (max.)

16A per rectifier (max.)

Fuse

25A per rectifier

25A per rectifier

Rectifier Modules

50-1250A

110-1100A

Voltage

48V

24V

Efficiency

>91%

>89%

Controller

PCS Controller

PCS Controller

Rectifier

PMP 25.48

PMP 25.24

Output

Components

Compliance
EMC

EN 55022 Class B, FCC Part 15 Class B

Safety

CSA C22-2 No. 950, UC1950 and IEC60950 / EN 60950

Mechanical
Dimensions (WxHxD)

23 x 84 x 23 in.
(584 x 2133 x 584mm)

23 x 46 x 23 in.
(584 x 1168 x 584mm)

Mounting (rack)

23

23

Mounting (base)

Mounting holes provided

Mounting holes provided

Audible Noise

<60dBA

<60dBA

Operating Temperature

-25 to +60C

-40 to +65C

Storage Temperature

-40 to +85C

-40 to +85C

Note: All specifications are subject to change without notification.

11V0005-011 INTSYS V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Mini System Data Sheet


We are sorry for the inconvenience; the Mini System data sheet is currently being revised. In the interim,
please e-mail adam.barnes@power-one for additional Mini System information.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU10 Controller Module Data Sheet

Features
User controls and interfaces:

Simple menu-guided operation using


front panel mounted pushbuttons and
an LCD

User-selectable alarm parameters

Data logging of last 40 events

SNMP interface adapter available

RS232 interface and Form C dry


alarm contacts

Compatible with PowComTM PC-based


software

Intelligent battery management:

Temperature compensation with


programmable compensation factor

Automatic and manual load testing

Battery voltage and symmetry monitoring

Remaining battery capacity


measurement

Low voltage disconnect

Description
The PCU10 provides monitoring and control for the PPS 10, 11, and 13 power systems. These hotswappable controller modules supervise AC inputs, output voltages and currents, rectifier performance,
battery condition, and breaker status. Visual notification of an alarm condition is provided with an LED. A
description of the exact alarm condition is provided through an LCD. Additionally, four Form C contacts
are provided to indicate a failure.

NOV 01, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU10 Controller Module Data Sheet

Input
Voltage
Current

Other Technical Data


18-72V DC
<200 mA at 48V, <400 mA at 24V

Dimensions
(WxHxD)
Weight

Interface
Display
Communications

Indications

Controls

2x16 character LCD


RS232 serial interface for remote
control from a PC with PowCom
software.
Green LED Power ON
Yellow LED - System warning
Red LED System alarm
Four pushbutton controls allow
menu navigation

Operating
Temperature

62 x 262 x 232mm
(2.4 x 10.3 x 9.1in)
0.5kg (1.1 lb.)
-25 to +55 C

Storage
Temperature

-50 to +85 C

Environment

Storage:
Transport:
Operation:

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Battery Management

Alarms
The last 40 events are saved and
include a time and date stamp.
Four potential free change over
Alarm Contacts
alarm contacts. Two open collector
outputs for LVD.
Alarms
1*
High DC Voltage
1*
Low DC Voltage
1*
Load/ Battery Disc.
1*
Battery Fuse Failure
1*
DC Fuse Failure
2*
Module Failure
1*
Urgent Module Failure
3*
Main AC Failure
4*
Battery Failure
4*
Symmetry Failure
4*
High Temperature
2*
High Load
* All alarms are indicated using an LED and displayed in
the LCD. The numbers represent an example of alarm
routing: 1) Urgent alarm, 2) Service alarm,
3) Main AC failure, 4) Battery related failure
Alarms are configurable by changing the EPROM
Alarm History

Battery
Disconnection

An optional feature that allows


voltage disconnection of batteries.

Boost
Charging

Manual time controlled or


automatic boost charging with
adjustable time and voltage levels.
Automatic or manual testing of
batteries up to four times per year.
Variables include: test duration, end
voltage, Ah, and allowable
symmetry variation.
Optional tool that measures
batteries for early detection of
thermal runaway. Allows for
separate measurements of up to
three parallel battery branches, each
divided into four blocks.
Allows continuous adjustment of
output voltage according to battery
temperature. Feature includes
adjustable compensation factor and
separate thresholds for alarms.
Optional feature that allows voltage
or time controlled disconnection of
non-essential load.

Battery Test

Symmetry
Measurement

Temperature
Compensation
Charging

Load
Shedding
(PLD)

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

NOV 01, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU 5/7

Controller

The PCU 5/ 7
Controllers are used
in PPS5 and PPS7
Power Systems.

Description
The Power-One Control Unit (PCU 5/7) provides monitoring and control for the PPS 5 and PPS 7
power systems. These hot-swappable controller modules supervise output voltages, currents, rectifier
performance, battery condition, and breaker status. Visual notification of an alarm condition is
provided with an LED. A description of the exact alarm condition is provided through an LCD.
Additionally, four Form C contacts are provided to indicate a failure.

Features
Intelligent battery management:

User controls and interfaces:

Simple menu-guided operation using front panel

Temperature compensation with programmable

User-selectable alarm parameters

Automatic and manual load testing

Data logging of last 40 events

Battery voltage and symmetry monitoring

SNMP interface adapter available

Capacity testing

RS232 interface and Form C dry alarm contacts

Low voltage disconnect

mounted pushbuttons and an LCD

compensation factor

Compatible with PowCom PC-based software


TM

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU 5/7
Controller
Input

Alarms

Voltage

18-72V DC

Current

<200 mA at 48V, <400 mA at 24V

Alarm
History

The last 40 events are saved and


include a time and date stamp.

Alarm
Contacts

Four potential free change over


alarm contacts. Two open
collector outputs for LVD.

Alarms

High DC Voltage
Low DC Voltage
Load/ Battery Disc.
Battery Fuse Failure
DC Fuse Failure
Module Failure
Urgent Module Failure
Main AC Failure
Battery Failure
Symmetry Failure
High Temperature
High Load

Interface
Display

2x16 character LCD

Communication

RS232 Serial interface for


remote control from a PC with
PowCom software.

Indications

Green LED Yellow LED Red LED -

Power ON
System warning message
System alarm

Controls

Four pushbutton controls allow menu


navigation

Battery Management
Battery
Disconnection

A feature that allows voltage


controlled disconnection of batteries.

Boost Charging

Manual time controlled or automatic


boost charging with adjustable time
and voltage levels.

Battery Test

Symmetry
Measurement

Automatic or manual testing of


batteries up to four times per year.
Variables include: test duration, end
voltage, Ah, and allowable symmetry
variation.
Optional tool that measures batteries
for early detection of thermal
runaway. Allows for separate
measurements of up to three parallel
battery branches, each divided into
four blocks.

Temperature
Compensation
Charging

Allows continuous adjustment of


output voltage according to battery
temperature. Feature includes
adjustable compensation factor and
separate thresholds for alarms.

PLD

Optional feature that allows voltage


or time controlled disconnection of
non-essential load.

11V0005-027 PCU 5/7 V3.0

1*
1*
1*
1*
1*
2*
1*
3*
4*
4*
4*
2*

* All alarms are indicated using an LED and


displayed in the LCD. The numbers represent an
example of alarm routing:
1) Urgent alarm, 2) Service alarm,
3) Main AC failure, 4) Battery related failure
Alarms are configurable by changing the EPROM

Other Technical Data


Dimensions
(WxHxD)

62 x 129 x 231mm
(2.4 x 5.1 x 9.1in.)

Weight

0.45kg (1.0lbs.)

Operating
Temperature

-25 to +55C

Storage
Temperature

-50 to +85C

Environment

Storage:
Transport:
Operation:

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Note: All specifications are subject to change without notification.

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 11

Rectifier Module

Description
The Power-One PMP 11 rectifier module
provides cost-effective power in a high
density solution. Built on the latest
advances in the resonance switch mode
approach (soft-switching), the PMP 11 is
the next evolution in our convection
cooled rectifier series.
Optimized for telecom applications, the
module is designed to work in a multitude
of different subrack/shelf configurations
incorporating the PCU/PCS controller and
varying distribution options.

Features
208/240 VAC input
24V, 48V, or 60V DC output
Input overvoltage disconnection
Thermal protection
Active load sharing
Hot-swappable
Up to 92% efficient
International standards compliance
Natural convection cooling
Low weight
PPS 10 6500 System
Shown

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 11
Rectifier Module
Input

Mechanical
Dimensions

205-250V AC 10% single phase,


(44-66Hz)
185-160V AC at reduced output power

62 x 261 x 231mm
(2.4 x 10.3 x 9.1in.)

Weight

3.1kg (6.8lbs.)

Current
(max.)

<6.8A

Cooling

Natural convection

Soft Start

<12A peak maximum 220ms

Harmonics

EN 61000-3-2
Power Factor >0.99 at max. load

Surge
Immunity

EN 61000-4-5

Enclosure

IP20

Fuse

T 8A

Mounting

Up to 8 modules per shelf

Connection

IEC-320/C14

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Model

PMP 10.24A

Input
Voltage

PMP 11.48

<7.0A

PMP 11.60

<7.0A

Insulation

Reinforced insulation tested at:


4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
0.75 kV DC secondary ground

Other Technical Data


Safety

EN 60950
UL 1950 and IEC60950 , Class 1
CSA C22-2 No. 950

Protection

Short circuit proof, automatic


current limiting, selective shutdown
of modules at excessive output
voltage. Thermal protection
reduces the output power at
environmental temperatures above
maximum level. Thermal
protection with shut down at
>55C. Automatic restart.* Input
over-voltage disconnection at
>275VAC with automatic reset at
>260VAC.

Output
Model

PMP 10.24A

PMP 11.48

PMP 11.60

Output Voltage

22-28V DC

44-56V DC

56-71V DC

Power (max.)

1000W
(25-28V)

1100W
(50-57.7V DC)

1100W
(60-71V DC)

Current (max.)

43A

23A

18.5A

Efficiency
(at 40-90% Load)*

>88%

>91%

>92%

Tolerance

Vout +/- 1%

Green LED

Power ON

Red LED

High output
voltage/ shutdown

Red LED

Low voltage/
module failure

Indications
Transient
Response

+/- 5% at load variation 10-90%


or 90-10%, recovery time 10ms

Load Sharing

<5% of nominal current

Ripple

<100mV p-p (BW. 30MHz)

Psophometric

<2mV, according to CCITT norms

Connection
EMC

Audible
Noise

<35dBA

Operating
Temperature*

-25 to +55C up to 2000m


-25 to +45C above 2000m

Storage
Temperature

-40 to +85C

Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:

DIN 41612F
EN 61000-6-2, EN 61000-6-4

*Average performance for a single module.

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Note: All specifications are subject to change without notification.

11V0005-034 PMP 11 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 13.48 Rectifier Data Sheet

Description
The PMP 13.48 is a convection-cooled rectifier
delivering superior reliability in harsh environmental
conditions where fan-cooled products may not
deliver the reliability required to ensure maximum
network asset performance.
With leading-edge patented resonant conversion
topology, the PMP13 industry-leading efficiencies of
93.5% deliver significant operating expenditure
savings in the network on utility and HVAC costs.
Power-One also recognizes that typical network
loads operate between 20-60%; hence the PMP13
unique flat efficiency ensures minimal energy loss
down to 15% of installed capacity
The PMP 13 is optimized for telecom applications,
and is designed to work in PPS10 systems
incorporating the PCS controller and various
distribution options with up to 6 units per 19/6U shelf
and up to 8 units per 23/6U shelf.

Features

PPS 10 3900 System Shown

NOV 07, 2006

Page 1 of 2

RoHS lead free solder and lead solder


exempted products are available

208/240 VAC input

48 VDC output

Input overvoltage disconnection

Thermal protection

Active load sharing

Hot swappable

Up to 92% efficient

International standards compliance

Natural convection cooling

Low weight

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 13.48 Rectifier Data Sheet

Mechanical

Input
Model

PMP 13.48

Input Voltage

Current (max.)

205-250 VAC 10% single phase,


(44-66 Hz)
(185-160 V at reduced output power)
<6.8 A

Soft Start

<12 A peak max. 100 ms

Harmonics

EN 61000-3-2
Power Factor >0.99 at max. load

Surge
Immunity

EN 61000-4-5

Fuse

T 10A

Connection

IEC-320/C14

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Dimensions
(WxHxD)

62 x 261 x 231 mm
(2.4 x 10.3 x 9.1 in)

Weight

3.1 kg (6.8 lb)

Cooling

Natural Convection

Insulation

Enclosure

Reinforced insulation, tested at:


4.25 kVDC primary-secondary
2.12 kVDC primary-ground
0.75 kVDC secondary-ground
IP20

Mounting

Up to 8 modules per shelf

Other Technical Data


Safety

Protection

Output
Model

13.48

Output Voltage

44 - 56 VDC

Power (max.)
Current (max.)

1300 W at
50-56 VDC
28 A

Efficiency

>92%

(at 40-90%
load)*

Indications

Tolerance

Vout 1.0%

Transient
Response

5% at load variation 10-90% or 90-10%,


recovery time 10 ms

Load Sharing

<5% of nominal current

Ripple

<100 mV p-p (BW. 30 MHz)

Psophometric

<2 mV, according to CCITT norms

Connection

DIN 41612F

EMC

EN 61000-6-2, EN 61000-6-4

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are


not designed, intended for use in, or authorized for use as
components in life support systems, equipment used in hazardous
environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including
safety agency certifications pictured on labels, may change depending
on the date manufactured. Specifications are subject to change
without notice.

NOV 07, 2006

Page 2 of 2

EN 60950
UL 1950 and IEC60950 , Class 1
CSA C22-2 No. 950
Short-circuit proof, automatic
current limiting, selective shutdown
of modules at excessive output
voltage. Thermal protection
reduces the output power at
environmental temperatures above
maximum level. Shut down at
>75 C with an automatic restart.*
Input overvoltage disconnection at
>275 VAC with automatic reset at
>260 VAC.
Green LED
Power ON
Red LED

High output
voltage/
shutdown

Red LED

Low voltage/
module failure

Audible
Noise

<35 dBA

Operating
Temperature

-25 to +55 C up to 2000 m


-25 to +45 C above 2000 m

Storage
Temperature

-40 to +85 C

Radiated
EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

*Average performance for a single module.

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 25
Rectifier Module

Description
The Power-One PMP 25 rectifier uses
resonance switch mode technology (soft
switching), and incorporates thermal
protection while providing extremely reliable
DC power in a small space. Rectifier
communication is accomplished using digital
interfaces over an RS485 data bus.
Information is transmitted to adjacent
rectifiers while providing status and
identification information to the system
controller (PCS).
At only 4 rack units high, these compact
rectifiers allow for up to five modules in each
23in. rack (4 units in 19in. rack) providing up
to 250A at 48V or up to 550A at 24V. With
full power available up to 65C, PMP 25
rectifiers are ideal for any indoor or outdoor
application.

Features
Compact 4 rack-unit height
50A output at 48V
110A output at 24V
208 / 240 single phase input
Input over-voltage disconnect
Hot-swappable rectifiers
High efficiency, up to 91%
Active current sharing
International standards compliance

PPS 25 System
Shown

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 25
Rectifier Module
Input

Mechanical
Dimensions

196 - 250V AC 10% single phase,


(44-66Hz)
176-160V AC at reduced output power

105 x 176 x 455mm


(6.9 x 4.13 x 17.9in.)

Weight

6.2kg (13.6lbs.)

Current
(max.)

<22A

<20A

Cooling

Fan: speed controlled and monitored

Soft Start

<22A

<20A

Interface

RS485 for communication with the


supervision module

Harmonics

EN 61000-3-2
Power Factor >0.98 at 50-100% load

Surge
Immunity

EN 61000-4-5

Fuse

F 25A

Connection

Harting MH - 21 Signal pins, 3 HC pins

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Model

PMP 25.24

Input
Voltage

PMP 25.48

Output
Model

PMP 25.24

PMP 25.48

Power (max.)

3080W

2800W

Output Voltage

22-30V DC

44-58V DC

Current (max.)

110A

50A

Efficiency

>89%

>91%

(@ 40-90%Load)*

Tolerance

+/- 6% at load variation 10-90%


or 90-10%, recovery time 150ms

Load Sharing

<5% of nominal current

Psophometric
Connection
EMC

<100mV p-p (BW. 30MHz)


<2mV, according to CCITT norms
8mm HC-pins

IP20

Mounting

In 19/ 4U subrack up to 4
In 23/ 4U subrack up to 5

Other Technical Data


Safety

EN 60950
CSA C22-2 No. 950, UL 1950

Protection

Short circuit proof, automatic current


limiting, selective shutdown of
modules at excessive output voltage.
Thermal protection reduces the
output power at environmental
temperatures above maximum level.
Shut down at >75C with automatic
restart.* Input over-voltage
disconnection at >275VAC with
automatic reset at >260VAC.
Green LED

Power ON

Yellow LED

Thermal Protection

Yellow Flashing

Comm. Error

Red LED

Module Failure

Indications

Audible
Noise

<60dBA

Operating
Temperature*

48V: -25 to +60C


24V: -40 to +65C

Storage
Temperature

-40 to +85C

Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:

EN 61000-6-2, EN 61000-6-4

* Average performance for a single rectifier

Reinforced insulation tested at:


4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
0.75 kV DC secondary ground

Enclosure

Vout +/- 0.5%

Transient
Response

Ripple

Insulation

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Note: All specifications are subject to change without notification.

11V0005-029 PMP 25 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 5

Rectifier Module

Description
The Power-One PMP 5 rectifier module
provides a cost-effective power solution
in a high density footprint. Built on the
latest advances in the resonance switch
mode approach (soft-switching), the
PMP 5 is the next evolution in our small
convection cooled rectifier series.
Optimized for telecom applications, the
module is designed to work in a
multitude of different subrack/shelf
configurations incorporating the PowerOne PCU controller and various
distribution options.

Features
115/230 VAC input
24V, or 48VDC output
Power factor correction
Active load sharing
Hot-swappable
PPR 5/7 System
Shown

Low weight
Natural convection cooling
International standards compliance

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 5

Rectifier Module
Input

Mechanical
PMP 5.48

PMP
5.24-110

PMP
5.48-110

Model

PMP 5.24

Input
Voltage

195-276V AC single
phase, (44-66Hz)

93,5-148,5V AC single
phase, (44-66Hz)

Current
(max.)

<2.9A

<5.8A

Dimensions

62 x 129 x 232mm
(2.4 x 5.1 x 9.1in.)

Weight

1.5kg (3.3lbs.)

Cooling

Natural convection

Insulation
Soft Start

<8A peak max. 5ms

<16A peak max. 5ms

Harmonics

EN 610555
Power Factor >0.99 at 50-100% load

Surge
Immunity

EN 61000-4-5

Fuse

T 3,15A

Connection

IEC-320/C14

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

T 6A

Reinforced insulation tested at:


4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
2.12 kV DC secondary ground

Enclosure

IP20

Mounting

In 19 subrack up to 6 modules

Other Technical Data


Safety

EN 60950

Protection

Short circuit proof, automatic


current limiting, selective
shutdown of modules at
excessive output voltage.

Output
Model

PMP 5.24

PMP 5.48

PMP
5.24-110

PMP
5.48-110

Output
Voltage

22.5-28
VDC

45-56
VDC

22.5-28
VDC

45-56
VDC

Power (max.)

448W

448W

448W

448W

Current
(max.)

16A

8A

16A

8A

Efficiency

>87%

>89%

>85%

>87%

Tolerance

Vout +/- 1%

Transient
Response

Green LED

Power ON

Red LED

High output
voltage/ shutdown

Red LED

Low voltage/
module failure

Indications

Audible
Noise

<35dBA

Operating
Temperature

-25 to +55C

+/- 5% at load variation 10-90% or 90-10%,


recovery time 10ms

Storage
Temperature

-40 to +85C

Load Sharing

<5% of nominal current

Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Ripple

<100mV p-p (BW. 30MHz)


Environment

Storage:
Transport:
Operation:

Psophometric

<2mV, according to CCITT norms

Connection

DIN 41612F

EMC

EN 61000-6-2, EN 61000-6-4

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Note: All specifications are subject to change without notification.

11V0005-066 PMP 5 V3.0 RevD

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 7

Rectifier Module

Description
The Power-One PMP 7 rectifier module
provides a cost-effective power solution
in the highest possible density. Built on
the latest advances in the resonance
switch mode approach (soft-switching),
the PMP 7 is the next evolution in our
small convection cooled rectifier series.
Optimized for telecom applications, the
module is designed to work in a multitude
of different subrack/shelf configurations
incorporating the Power-One PCU
controller and various distribution
options.

Features
208/240 VAC input
24V, 48V, or 60V DC output
Input overvoltage disconnection
Thermal protection
Active load sharing
Hot-swappable
Up to 92% efficient
International standards compliance
Natural convection cooling
PPS 7 3500 System
Shown

Low weight

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 7

Rectifier Module
Mechanical

Input
Model

PMP 7.24

PMP 7.48

Input
Voltage

205-250V AC 10% single phase,


(44-66Hz) (-15% for PMP7.60)
185-160V at reduced output power

Current
(max.)

<3.55A

<4.35A

Dimensions

62 x 129 x 232mm
(2.4 x 5.1 x 9.1in.)

Weight

1.65kg (3.6lbs.)

Cooling

Natural convection

<4.35A

Soft Start

<11A peak
max. 5ms

Harmonics

EN 61000-3-2
Power Factor >0.99 at max. load

Surge
Immunity

EN 61000-4-5

Fuse

T 6,3A

Connection

IEC-320/C14

EMC

<15.5A peak
max. 5ms

PMP 7.60

<20A peak
max. 5ms

Insulation

Enclosure

IP20

Mounting

In 19 subrack up to 5 modules

Other Technical Data

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

Safety

EN 60950
UL 1950 and IEC60950 , Class 1
CSA C22-2 No. 950

Protection

Short circuit proof, automatic


current limiting, selective shutdown
of modules at excessive output
voltage. Thermal protection
reduces the output power at
environmental temperatures above
maximum level. Shut down at
>75C with an automatic restart.*
Input over-voltage disconnection at
>275VAC with automatic reset at
>260VAC.

Output
Model

PMP 7.24

PMP 7.48

PMP 7.60

Output
Voltage

22.5-28VDC

45-56VDC

56-70.5VDC

Power (max.)

560W

672W

635W

Current
(max.)

20A

12A

9A

Efficiency

>89.5%

>92%

>92%

(at 40-90% load)*

Reinforced insulation tested at:


4.25 kV DC primary-secondary,
2.12 kV DC primary-ground,
0.75 kV DC secondary ground

Green LED

Power ON

Red LED

High output
voltage/ shutdown

Red LED

Low voltage/
module failure

Indications

Tolerance

Vout +/- 1%

Transient
Response

+/- 5% at load variation 10-90%


or 90-10%, recovery time 10ms

Load Sharing

<5% of nominal current

Audible
Noise

<35dBA

Ripple

<100mV p-p (BW. 30MHz)

Operating
Temperature*

-25 to +55C up to 2000m


-25 to +45C above 2000m

Psophometric

<2mV, according to CCITT norms

-40 to +85C

Connection

DIN 41612F

Storage
Temperature
Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation:

EMC

EN 61000-6-2, EN 61000-6-4

*Average performance for a single module.

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Note: All specifications are subject to change without notification.

11V0005-028 PMP 7 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Power Network Interface Data Sheet

Description

Features

The Power Network Interface (PNI) is an embedded


network server that allows Power-One Controller
modules to be accessed remotely via Ethernet or
SNMP.

Access can be achieved via any web browser which


has access to the TCP/IP network and. An intuitive
graphic user interface provides access and control to
system parameters, alarm history, and battery test
data.
Alarm Central allows multiple power systems to be
monitored using a hierarchy-based window system
that informs a user of system events, using both
audible and visual alarms.
SNMP protocol allows enhanced managing
capabilities and enables the system to be accessed
from any location. Using standard protocols and an
enterprise specific Management Information Base
(MIB), SNMP allows the user to access and monitor
system parameters as well as tracking system
variables.
The PNI can be supplied as standalone device or
installed as a daughter board in PCS controllers.

OCT 24, 2006

Page 1 of 2

RoHS lead-free solder and leadsolder-exempted products are


available.

User controls and interfaces:

Systems can be accessed via any


browser which has access to the
Ethernet network

Multiple elements can be viewed


and controlled using Alarm
Central

Instantaneous access to:

System parameters

Alarm history

Battery discharge curves

Uses SNMP protocol for reliable


remote access

Uses
RS232,
RS485,
10Base-T Ethernet

Allows an external modem for


backup

FTP for updating software

Telnet for system diagnostics

and

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Power Network Interface Data Sheet

Web Interface

Alarm Central Window

Other Technical Data

Serial Port

<2 W
18 to 72 VDC, max 2 W
10 BaseT Driver/ Receiver with line transformer and EMI filter
half-duplex Ethernet.
2 RS232 ports (1 for PCU/ Setup and 1 for Modem/ PC)

Mechanical

Weight

233 g (0.50 lb)

Environmental

Dimensions
Ambient Temperature
Storage Temperature

147 x 38 x 84 mm (5.79 x 1.5 x 3.31 in)


-10 C to +70 C
-40 C to +85 C

Compliance

Humidity
Ethernet
Serial Port

0% to 95% (non-condensing)
Supports IEEE 802.3 Ethernet Standard
Industry standard 16550 A-compatible UART

Electrical
Communication

Power Consumption
Supply Voltages
Ethernet

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as
critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the
express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.

OCT 24, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPR 5/7

3 & 6 Position Power Systems

Description
The Power-One PPR 5/7 3 and 6
position rectifier backplane provides a
cost-effective power solution in a high
density wall-mounted footprint. These
power solutions provide rectification,
system management, and power
distribution while maintaining high
reliability and offering flexibility for
future expansion. The PPS 5/7 3 & 6
Position systems are based on hotswappable rectifier modules output
power available at 450, 560 or 670W per
module.

Features
115/230 VAC input
24V, or 48VDC output
Serial or parallel alarm configurations
Active load sharing
Hot-swappable
International standards compliance
Natural convection cooling
6 Position System
Shown

Systems can be paralleled


Individual rectifier output adjustment

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPR 5/7

3 & 6 Position Power Systems


Input
Model

PPR 5/7 3-Position

PPR 5/7 6-Position

Input

115 or 230VAC single phase


(Depending on rectifier
module)"

115 or 230VAC single phase


(Depending on rectifier
module)"

Input Connections

3x4mm terminal blocks

3x4mm terminal blocks

Load Outputs

2x10mm - Qty 3

2x10mm - Qty 6

24V DC Version

Yes

Yes

48V DC Version

Yes

Yes

Output
Rectifier Modules

(max.)

Features
Alarms

Common alarm for High Voltage/ Shutdown, Low Voltage/


Module Failure, Unequal Load Sharing Normally Opened
or Normally Closed.

Mechanical
Dimensions (WxHxD)

271x193.5x305mm

484.4x193.5x305mm

Weight

1.2kg (2.65lbs.)

2.5kg (5.5lbs.)

Mounting

Wall Mount

Wall Mount

Note: All specifications are subject to change without notification.

Available Rectifiers
Model

Voltage

Power (max.)

Current (max.)

PMP 5.24

24V DC

448W

16A

PMP 5.24 SIC 110*

24V DC

448W

16A

PMP 5.48 SIC 110*

48V DC

448W

8A

PMP 7.24 SIC

24V DC

560W

20A

PMP 7.48 SIC

48V DC

672W

12A

*110V AC input

11V0005-065 PPR 5/7 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System

PPS 10 Power System

Cabinet System

Cabinet System
Input
Model

PPS 10-10400

PPS 10-18200

PPS 10-23400

Input

230/400V 3-phase
208-240V 1-phase
Site configurable

230/400V 3-phase
208-240V 1-phase
Site configurable

230/400V 3-phase
208-240V 1-phase
Site configurable

Single input

Single input per


rectifier subrack

Single input per


rectifier subrack

14

18

Adjustable for site

20

21

Adjustable for site

24V DC Version

Yes

Yes

(with PCS and max.


one rectifier shelf)

Yes

48V DC Version

Yes

Yes

Yes

60V DC Version

Yes (on request)

Yes (on request)

Yes (on request)

Inputs

(max.)

Output
Rectifier Modules

(max.)

Battery Outs - MCB


Load Outs - MCB

(100A)

(2-63A)

PCS

PCU/PCS

PPS 10 modular DC power cabinet systems


provide large power plant features in costeffective, rack-mounted form factors. These
cabinet power solutions provide rectification,
system management, and power distribution while
maintaining high reliability and offering flexibility
for future expansion. The PPS 10 systems are
based on hot-swappable rectifier modules with
constant output power available at 1000, 1100 or
1300W per module.
System management is accomplished through
messages and alarms displayed on the system
controllers (PCU/PCS) LCD screen and can also
be displayed remotely via the PC-based PowCom
software package.

Features
Supervision

Description

PCS

TM

Expansion
Expansion subrack

N/A

Yes

Yes

Expansion Cabinet

Yes

Yes

N/A

Battery Symmetry Inputs

3/4

Low Voltage Battery


Disconnection (LVBD)

Features

Yes

Yes

Yes

In-Cabinet Battery

Yes

Yes

N/A

Dimensions (WxHxD)

Power Cabinet:
600x700x400mm
Battery Cabinet:
600x1130x400mm
600x1130x600mm

600x1800x400mm
600x1800x600mm
600x2000x400mm
600x2000x600mm

600x1750x400mm
600x2150x400mm

Cable Entry

Top

Top

Top/Bottom

Temp. Comp. Charge

Yes

Yes

Yes

Integrated Surge
Arrestors

Yes

Yes

N/A

Partial Load Disconnect

Yes

Yes

Yes

Hinged Door Access

Yes

Yes

Yes

Battery Cover

Yes

Yes

N/A

Ethernet Network
Interface

Yes

Yes

Yes

Modem Interface

Yes

Yes

Yes

Battery

Mechanical

Options

High reliability
Simple installation and operation
LCD display for self-guided controller operation
Interfaces standards include RS232, and Form
C dry alarm contacts with grouped alarms
Intelligent battery management:
Temperature compensation
(requires optional cables)
Programmable battery load testing
with data logging
Symmetry (requires optional cables)
Programmable low voltage disconnect
Optional Ethernet (SNMP compatible) interface
module
Natural convection cooled - no fans
International standards compliance

Note: All specifications are subject to change without notification.

11V0005-038 PPS10 SY V3.0

www.power-one.com

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System


Cabinet System

System Components

System Configurations

Rectifier Modules
The PPS 10 system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs for
rectifier status indication, thermal shutdown and input
overvoltage disconnection with an automatic reset.
Rectifier Features
Model

Voltage

Power
(max.)

Current
(max.)

PMP 10.24A SIC

24V DC

1000W

43A

PMP 11.48 SIC

48V DC

1100W

22A

PMP 11.60 SIC

60V DC

1100W

19.5A

PMP 13.48 SIC

48V DC

1300W

28A

PMP 13.48 SIC WIR*

48V DC

1250W

27A

* WideInput Range (100 - 240V AC)

Supervision Modules

PPS 10-10400 System

PPS 10-18200 System

PPS 10-23400 System

A split cabinet solution, that


allows the power cabinet to be
used as a stand alone wall
cabinet, or to be installed directly
above a battery cabinet. This
system can accommodate up to
eight rectifiers, a supervision
module
(PCS)
and
DC
distribution with up to six battery
breakers and twenty load
breakers. This system can also
be easily expanded by paralleling
additional slave cabinets.

A floor cabinet solution that


contains two rectifier subracks
and space for mounting batteries
at the base of the cabinet. This
system can accommodate up to
fourteen rectifiers, a supervision
module (PCU/PCS) and DC
distribution with up to six battery
breakers and twenty-one load
breakers. This system can also
be easily expanded by paralleling
additional slave cabinets.

A floor cabinet solution with a


built-in DC-bus that enables the
plug-in connection of rectifier
subracks and battery/ load
breaker shelves. This system can
accommodate up to eighteen
rectifiers, a supervision module
(PCS) and DC distribution with a
wide range of plug-in DC load
distributions (low and high ohmic).
This system offers flexible system
configurations to fit most site
requirements.

Advanced system supervision is accomplished using a


microprocessor based control module that allows both local and
remote system monitoring.
PCU Features

RS232 interface for remote operation


Battery management and testing
Low voltage battery disconnect (LVBD)
Partial load disconnect (PLD)
Temperature compensation
Battery symmetry measurement
Optional Ethernet interface through SNMP and/or TCP/IP

PCS Features
All of the features listed under PCU above, plus:

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Menu guided operation

Advanced battery management and testing


Digital signal collection via internal RS485 bus
Site programmable flash EPROM
Multiple language choices
Programmable alarms
Programmable logic functions and operations
Monthly data logging

PPS 10 Power System


Cabinet System

System Components

System Configurations

Rectifier Modules
The PPS 10 system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs for
rectifier status indication, thermal shutdown and input
overvoltage disconnection with an automatic reset.
Rectifier Features
Model

Voltage

Power
(max.)

Current
(max.)

PMP 10.24A SIC

24V DC

1000W

43A

PMP 11.48 SIC

48V DC

1100W

22A

PMP 11.60 SIC

60V DC

1100W

19.5A

PMP 13.48 SIC

48V DC

1300W

28A

PMP 13.48 SIC WIR*

48V DC

1250W

27A

* WideInput Range (100 - 240V AC)

Supervision Modules

PPS 10-10400 System

PPS 10-18200 System

PPS 10-23400 System

A split cabinet solution, that


allows the power cabinet to be
used as a stand alone wall
cabinet, or to be installed directly
above a battery cabinet. This
system can accommodate up to
eight rectifiers, a supervision
module
(PCS)
and
DC
distribution with up to six battery
breakers and twenty load
breakers. This system can also
be easily expanded by paralleling
additional slave cabinets.

A floor cabinet solution that


contains two rectifier subracks
and space for mounting batteries
at the base of the cabinet. This
system can accommodate up to
fourteen rectifiers, a supervision
module (PCU/PCS) and DC
distribution with up to six battery
breakers and twenty-one load
breakers. This system can also
be easily expanded by paralleling
additional slave cabinets.

A floor cabinet solution with a


built-in DC-bus that enables the
plug-in connection of rectifier
subracks and battery/ load
breaker shelves. This system can
accommodate up to eighteen
rectifiers, a supervision module
(PCS) and DC distribution with a
wide range of plug-in DC load
distributions (low and high ohmic).
This system offers flexible system
configurations to fit most site
requirements.

Advanced system supervision is accomplished using a


microprocessor based control module that allows both local and
remote system monitoring.
PCU Features

Menu guided operation


RS232 interface for remote operation
Battery management and testing
Low voltage battery disconnect (LVBD)
Partial load disconnect (PLD)
Temperature compensation
Battery symmetry measurement
Optional Ethernet interface through SNMP and/or TCP/IP

PCS Features
All of the features listed under PCU above, plus:

Advanced battery management and testing


Digital signal collection via internal RS485 bus
Site programmable flash EPROM
Multiple language choices
Programmable alarms
Programmable logic functions and operations
Monthly data logging

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System

PPS 10 Power System

Cabinet System

Cabinet System
Input
Model

PPS 10-10400

PPS 10-18200

PPS 10-23400

Input

230/400V 3-phase
208-240V 1-phase
Site configurable

230/400V 3-phase
208-240V 1-phase
Site configurable

230/400V 3-phase
208-240V 1-phase
Site configurable

Single input

Single input per


rectifier subrack

Single input per


rectifier subrack

14

18

Adjustable for site

20

21

Adjustable for site

24V DC Version

Yes

Yes

(with PCS and max.


one rectifier shelf)

Yes

48V DC Version

Yes

Yes

Yes

60V DC Version

Yes (on request)

Yes (on request)

Yes (on request)

Inputs

(max.)

Output
Rectifier Modules

(max.)

Battery Outs - MCB


Load Outs - MCB

(100A)

(2-63A)

PCS

PCU/PCS

PPS 10 modular DC power cabinet systems


provide large power plant features in costeffective, rack-mounted form factors. These
cabinet power solutions provide rectification,
system management, and power distribution while
maintaining high reliability and offering flexibility
for future expansion. The PPS 10 systems are
based on hot-swappable rectifier modules with
constant output power available at 1000, 1100 or
1300W per module.
System management is accomplished through
messages and alarms displayed on the system
controllers (PCU/PCS) LCD screen and can also
be displayed remotely via the PC-based PowCom
software package.

Features
Supervision

Description

PCS

TM

Expansion
Expansion subrack

N/A

Yes

Yes

Expansion Cabinet

Yes

Yes

N/A

Battery Symmetry Inputs

3/4

Low Voltage Battery


Disconnection (LVBD)

Features

Yes

Yes

Yes

In-Cabinet Battery

Yes

Yes

N/A

Dimensions (WxHxD)

Power Cabinet:
600x700x400mm
Battery Cabinet:
600x1130x400mm
600x1130x600mm

600x1800x400mm
600x1800x600mm
600x2000x400mm
600x2000x600mm

600x1750x400mm
600x2150x400mm

Cable Entry

Top

Top

Top/Bottom

Temp. Comp. Charge

Yes

Yes

Yes

Integrated Surge
Arrestors

Yes

Yes

N/A

Partial Load Disconnect

Yes

Yes

Yes

Hinged Door Access

Yes

Yes

Yes

Battery Cover

Yes

Yes

N/A

Ethernet Network
Interface

Yes

Yes

Yes

Modem Interface

Yes

Yes

Yes

Battery

Mechanical

Options

High reliability
Simple installation and operation
LCD display for self-guided controller operation
Interfaces standards include RS232, and Form
C dry alarm contacts with grouped alarms
Intelligent battery management:
Temperature compensation
(requires optional cables)
Programmable battery load testing
with data logging
Symmetry (requires optional cables)
Programmable low voltage disconnect
Optional Ethernet (SNMP compatible) interface
module
Natural convection cooled - no fans
International standards compliance

Note: All specifications are subject to change without notification.

11V0005-038 PPS10 SY V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

www.power-one.com

PPS 10 Power System Data Sheet


(Shelf System)

Features

High reliability
Simple installation and operation
LCD display for self-guided controller
operation
Interfaces standards include RS232, and
Form C dry alarm contacts with grouped
alarms
Intelligent battery management:
Temperature compensation (requires
optional cables)
Programmable battery load testing
with data logging
Symmetry (requires optional cables)
Programmable low voltage disconnect
Optional Ethernet (SNMP compatible)
interface module
Natural convection cooled - no fans
International standards compliance

Description
PPS 10 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted
form factors. These shelf power solutions provide rectification, system management, and power distribution
while maintaining high reliability and offering flexibility for future expansion. The PPS 10 systems are based on
hot-swappable rectifier modules with constant output power available at 1300 W per module.
System management is accomplished through messages and alarms displayed on the system controllers
(PCU/PCS) LCD screen and can also be displayed remotely via the PC-based PowComTM software package.

DEC 11, 2006

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet


(Shelf System)

PPS 10-3900 System


An all-in-one 6U high shelf system that
can be installed in both 19 and ETSI
telecom cabinet solutions. The system
subrack can accommodate up to 3 rectifier
modules, a supervision module (PCU),
and DC distribution with up to 2 battery
breakers and 8 load breakers.

PPS 10-7800 System


An all-in-one 12U high shelf system that
can be installed in 19 telecom cabinet
solutions.
The system subrack can
accommodate up to 6 rectifier modules, a
supervision module (PCS) and DC
distribution with up to four battery
breakers and 15 load breakers. Optional
expansion subrack allowing max 12
modules (15.6 kW).

DEC 11, 2006

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet


(Shelf System)

System Components
Rectifier Modules
The PPS 10 system utilizes plug-in rectifier modules that are based
on a soft-switching approach. Features include 3 LEDs for rectifier
status indication, thermal shutdown, and input overvoltage
disconnection with an automatic reset.

Rectifier Features
Model
PMP 13.48 SIC

Voltage
48 VDC

Power (max.)
1300 W

Current (max.)
28 A

Supervision Modules
Advanced system supervision is accomplished using a
microprocessor-based control module that allows both local and
remote system monitoring.

PCU Features

Menu-guided operation
RS232 interface for remote operation
Battery management and testing
Low voltage battery disconnect (LVBD)
Partial load disconnect (PLD)
Temperature compensation
Battery symmetry measurement
Optional Ethernet interface through SNMP and/or
TCP/IP

PCS Features
All of the features listed under PCU above, plus:
Advanced battery management and testing
Digital signal collection via internal RS485 bus
Site programmable flash EPROM
Multiple language choices
Programmable alarms
Programmable logic functions and operations
Monthly data logging

DEC 11, 2006

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet


(Shelf System)

Input
Model
Input

Inputs (max.)

PPS 10-3900
230/400V 3-phase
208-240V 1-phase
Site configurable
Single input

PPS 10-7800
230/400V 3-phase
208-240V 1-phase
Site configurable
Single input

3
2
8

6
4
15

PCU

PCS

3
Yes

4
Yes

485 x 266 x 341 mm


19" or ETSI
Top

487 x 531 x 308 mm


19"
Top

Yes
N/A
N/A
Yes
Yes

Yes
Yes
Yes
Yes
Yes

Output
Rectifier Modules (max.)
Battery Outs - MCB (100 A)
Load Outs - MCB (2-63 A)

Features
Supervision

Battery
Battery Symmetry Inputs
Low Voltage Battery Disconnection
(LVBD)

Mechanical
Dimensions (WxHxD)
Mounting
Cable Entry

Options
Temp. Comp. Charge
Integrated Surge Arrestors
Partial Load Disconnect
Ethernet Network Interface
Modem Interface

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

DEC 11, 2006

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet


(Cabinet & Shelf Systems)

Features

Up to 18 kW/ 320 A power and 680 Ah


battery backup per cabinet
Simple installation and operation
LCD for self-guided controller operation
Interface standards include RS232, and
Form C dry alarm contacts with
grouped alarms
Site programmable supervision unit
Intelligent battery management
Optional Ethernet (SNMP compatible)
interface module
International standards compliance

Description
PPS 16 modular DC power shelf and cabinet systems are designed to meet rigid telecom applications with very
high reliability and flexibility for future expansion.
The PPS 16 Power Systems are based on hot-swappable rectifier modules with output power available up to
1800 watts per module.
System management is accomplished through messages and alarms displayed on the system controllers LCD
screen and can also be viewed and controlled remotely via the PC-based PowCom software package.

SEP 27, 2006

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet


(Cabinet & Shelf Systems)

Shelf Solutions (19)

Shelf Solutions (23)

4U and 8U systems accommodating up to 8


rectifier modules, a supervision module, and
DC distribution with battery breakers and
load breakers.

4U and 8U systems that can accommodate up


to 10 rectifier modules, a supervision module,
and DC distribution with up to 6 battery
breakers and 20 load breakers.

Up to 288 A/ 14.4 kW/ 48 V per shelf


2-6 battery breakers
Max 21 load MCB

Up to 256 A/ 12.8 kW /48 V per shelf


2-6 battery breakers
Max 26 load MCB

Cabinet Solutions
(With Batteries)
Floor cabinet solutions that
combine rectifiers, DC
distribution, backup batteries,
and monitoring in a single
footprint.
This system can accommodate
up to 10 rectifier modules, a
supervision module, and DC
distribution with up to 6 battery
breakers and 26 load breakers.

SEP 27, 2006

Up to 360 A/ 18 kW/ 48 V
per cabinet
Space for 680 Ah backup
batteries per cabinet
Footprint - 600 x 600 mm
or 600 x 400 mm
Height - 1800 or 2000
mm

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet


(Cabinet & Shelf Systems)

System Components
Rectifier Modules
The PPS 16 system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs
for rectifier status indication, thermal shutdown, and input
overvoltage disconnection with an automatic reset.

Rectifier Features:
Model

Input

Voltage

FMP16.48
FMP18.48

85-275 VAC

48 VDC

Power
(Max)
1600 W
1800 W

Current
(Max)
32 A
36 A

FMP Rectifier Module

Controllers

Menu guided operation


RS232 interface and Form C dry alarm contacts
Password controlled environment
Battery management:
Automatic and/or manual capacity test
Optional battery symmetry measurement with alarm
Optional temperature compensation
Programmable low voltage disconnect from batteries
Optional programmable PLD function for load
shedding
Optional network interface capability
Programmable alarm routing, logic unit, and analog
inputs
Alarm logging history

PCS Features;

PCC Features;

Site programmable flash EPROM


Multiple language choices
LCD and front-mounted controls
Monthly battery data logging

SEP 27, 2006

PCS Module

PCC Module

Hot pluggable unit


Control unit with ethernet connection (option)

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet


(Cabinet & Shelf Systems)

Input
19 Shelf

Model
AC Inputs

23 Shelf

23 Cabinet

10

10

1-3

2 to 6

2-4

2 to 6

2-4

2 to 6

13

21

16

20

16

20

PCC

PCS

PCC

PCS/PCC

PCC

PCS/PCC

12

6 or 12

6 or 12

Output
Rectifier Modules
(max. per system)

Battery Outputs
Load Outputs (Max)
(MCB type dependant)

Controller
Model

Battery
Battery Symmetry
Inputs
Low Voltage Battery
Disconnect (LVBD)
In-Cabinet Battery

Yes

Yes

Yes

N/A

N/A

Up to 680 Ah using
4 x 170 Ah

Mechanical
Dimensions
W x H x D (mm)

483x355x300 483x355x300
(19 in. x 4U)
(19 in. x 8U)

483x355x300
(23 in. x 4U)

483x355x300
(23 in. x 8U)

600 x 600 x 1800


600 x 600 x 2000
600 x 400 x 1800
600 x 400 x 2000

Options
Temp. Comp. Charge

Yes

Yes

Yes

Ethernet Network
Interface

Yes

Yes

Yes

Modem Interface

Yes

Yes

Yes

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written
consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on
the date manufactured. Specifications are subject to change without notice.

SEP 27, 2006

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 25 Power System

PPS 25 Power System


Cabinet System

Cabinet System
Input
Model

PPS 25 System

Input

230/400V 3-phase (site configurable)

Inputs

Single input for each 6 rectifier positions


(4 inputs for 24 rectifier cabinets)

(max.)

Description

Output
Rectifier Modules

(max.)

24 (bulk output feed to battery and load)

Battery Outputs

Several battery breaker modules are available and are based on:
MCCBs: 1x1500A, 2x600A, 4x384A
MCBs: 12x100A
Knife fuses: 5xNH1-3

Load Outs - MCB

Several battery breaker modules are available and are based on:
MCCBs: 1x1500A, 2x600A, 2x384A, 4x384A
MCBs: 24x2-63A, 16x80-100A, 24x2-16A high ohmic
Knife fuses: 5xNH1-3, 9xNH00

(2-63A)

24V DC Version

Yes (max. 1200A per cabinet)

48V DC Version

Yes

PPS 25 modular DC power cabinet systems are


designed to meet rigid telecom applications with
very high reliability and flexibility for future
expansion. These cabinet power solutions
provide rectification, system management and
power distribution while allowing configurable
solutions within the same cabinet or through the
use of external distribution cabinets. The PPS 25
systems are based on hot-swappable fan-cooled
PMP 25 rectifier modules with constant output
power available at 24V/110A or 48V/50A per
module.

Features
Supervision

PCS

Expansion

System management is accomplished through


messages and alarms displayed on the system
controllers (PCS) LCD screen and can also be
displayed remotely via the PC-based PowCom
software package.

TM

Expansion Rack

Up to six subracks per cabinet, each with four rectifier modules

Expansion Cabinet

Expansion cabinet can be be placed to the left or right of existing


cabinets, allowing up to 128 rectifier modules

Features

Battery
Battery Symmetry Inputs

4 (expandable to 12 by adding the optional interface circuit board)

Low Voltage Battery


Disconnection (LVBD)

Yes (through a trip coil in each MCCB or contactor)

Mechanical
Dimensions (WxHxD)

600x2150x600mm

Cable Entry

Top and/or bottom for cables <50sq/mm (using cable duct)


Top or bottom entry for cables >50sq/mm

Plug-in for multiple racks,


subracks, and PDUs

A total of 35U is available for rectifier subracks, distribution, and battery


breaker modules (29U at bottom cable entry)

Yes

Partial Load Disconnect

Yes

Hinged Door Access

Yes

Ethernet Network
Interface

Yes

Modem Interface

Yes

Options
Temp. Comp. Charge

High reliability
Simple installation and operation
LCD display for self-guided controller operation
Interfaces standards include RS232, and Form
C dry alarm contacts with grouped alarms
Up to 1200A per cabinet
Live expansion up to 6400A
Plug-in ready for various DC distributions and
subracks
Inter-cabinet DC paralleling bus
Site programmable supervision unit
Intelligent battery management
Optional Ethernet (SNMP compatible) interface
module
International standards compliance

Note: All specifications are subject to change without notification.

11V0005-039 PPS25 SY V3.0

www.power-one.com

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 25 Power System


Cabinet System

System Components

System Configurations

Rectifier Modules
The PPS 25 system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs
for rectifier status indication, thermal shutdown, and input
overvoltage disconnection with an automatic reset.
Model

Voltage

Power
(max.)

Current (max.)

PMP 25.24 SIC

24V DC

3080W

110A at 28V DC

PMP 25.48 SIC

48V DC

2800W

50A at 56V DC

PMP 25 Rectifier

Supervision Module
Advanced system supervision is accomplished using a microprocessor
based control module that allows both local and remote system monitoring.
PCS Features

PPS 25 with integrated


DC distribution
PPS 25 with bulk
outputs feeding remote
DC distributions

PPS 25 System
The PPS 25 system offers flexible solutions that fit a large number of site
requirements. Some of these features include:

Easy configuration with internal or remote DC distribution


Internal DC bus for simple plug-in of load distribution modules, battery
breaker modules, and rectifier subracks

Menu guided operation


RS232 interface for remote operation
Enhanced battery management and testing
Temperature compensation
Site programmable flash EPROM
Supervision for up to 128 rectifiers and 128 micro processors
Multiple language choices
Programmable alarms, logic functions, and operations

100mm Cable Duct

Monthly data logging


Optional Ethernet interface through SNMP and/or TCP/IP

Battery Breaker Modules


Plugable battery breaker
module, based on MCCBs,
MCBs or knife fuses

Cabinet

Inter-cabinet paralleling bus for live connection of expansion cabinets

Innovative and flexible cabinet design.

Internal data bus for advanced system monitoring and control


Wide range of plug-in DC load distributions, low and high ohmic

Cabinet Features

In cabinet vertical DC bus allows live expansion of distribution

DC Distribution
Plugable load distribution
module, based on MCBs,
MCCBs or knife fuses. Low
or high ohmic.

and rectifier modules

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCS Supervision Module

Separate cable duct for output load cables


Inter cabinet DC bus for live cabinet expansion
Top or bottom cable entry
Matching DC distribution cabinets

PPS 25 Cabinet

PPS 25 Power System


Cabinet System

System Components

System Configurations

Rectifier Modules
The PPS 25 system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs
for rectifier status indication, thermal shutdown, and input
overvoltage disconnection with an automatic reset.
Model

Voltage

Power
(max.)

Current (max.)

PMP 25.24 SIC

24V DC

3080W

110A at 28V DC

PMP 25.48 SIC

48V DC

2800W

50A at 56V DC

PMP 25 Rectifier

Supervision Module
Advanced system supervision is accomplished using a microprocessor
based control module that allows both local and remote system monitoring.
PCS Features

PPS 25 with integrated


DC distribution
PPS 25 with bulk
outputs feeding remote
DC distributions

PPS 25 System
The PPS 25 system offers flexible solutions that fit a large number of site
requirements. Some of these features include:

Easy configuration with internal or remote DC distribution


Internal DC bus for simple plug-in of load distribution modules, battery
breaker modules, and rectifier subracks

Menu guided operation


RS232 interface for remote operation
Enhanced battery management and testing
Temperature compensation
Site programmable flash EPROM
Supervision for up to 128 rectifiers and 128 micro processors

PCS Supervision Module

Multiple language choices


Programmable alarms, logic functions, and operations

100mm Cable Duct

Monthly data logging


Optional Ethernet interface through SNMP and/or TCP/IP

Battery Breaker Modules


Plugable battery breaker
module, based on MCCBs,
MCBs or knife fuses

Cabinet

Inter-cabinet paralleling bus for live connection of expansion cabinets

Innovative and flexible cabinet design.

Internal data bus for advanced system monitoring and control


Wide range of plug-in DC load distributions, low and high ohmic

Cabinet Features

In cabinet vertical DC bus allows live expansion of distribution

DC Distribution
Plugable load distribution
module, based on MCBs,
MCCBs or knife fuses. Low
or high ohmic.

and rectifier modules

Separate cable duct for output load cables


Inter cabinet DC bus for live cabinet expansion
Top or bottom cable entry
Matching DC distribution cabinets

PPS 25 Cabinet

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 25 Power System

PPS 25 Power System


Cabinet System

Cabinet System
Input
Model

PPS 25 System

Input

230/400V 3-phase (site configurable)

Inputs

Single input for each 6 rectifier positions


(4 inputs for 24 rectifier cabinets)

(max.)

Description

Output
Rectifier Modules

(max.)

24 (bulk output feed to battery and load)

Battery Outputs

Several battery breaker modules are available and are based on:
MCCBs: 1x1500A, 2x600A, 4x384A
MCBs: 12x100A
Knife fuses: 5xNH1-3

Load Outs - MCB

Several battery breaker modules are available and are based on:
MCCBs: 1x1500A, 2x600A, 2x384A, 4x384A
MCBs: 24x2-63A, 16x80-100A, 24x2-16A high ohmic
Knife fuses: 5xNH1-3, 9xNH00

(2-63A)

24V DC Version

Yes (max. 1200A per cabinet)

48V DC Version

Yes

PPS 25 modular DC power cabinet systems are


designed to meet rigid telecom applications with
very high reliability and flexibility for future
expansion. These cabinet power solutions
provide rectification, system management and
power distribution while allowing configurable
solutions within the same cabinet or through the
use of external distribution cabinets. The PPS 25
systems are based on hot-swappable fan-cooled
PMP 25 rectifier modules with constant output
power available at 24V/110A or 48V/50A per
module.

Features
Supervision

PCS

Expansion

System management is accomplished through


messages and alarms displayed on the system
controllers (PCS) LCD screen and can also be
displayed remotely via the PC-based PowCom
software package.

TM

Expansion Rack

Up to six subracks per cabinet, each with four rectifier modules

Expansion Cabinet

Expansion cabinet can be be placed to the left or right of existing


cabinets, allowing up to 128 rectifier modules

Features

Battery
Battery Symmetry Inputs

4 (expandable to 12 by adding the optional interface circuit board)

Low Voltage Battery


Disconnection (LVBD)

Yes (through a trip coil in each MCCB or contactor)

Mechanical
Dimensions (WxHxD)

600x2150x600mm

Cable Entry

Top and/or bottom for cables <50sq/mm (using cable duct)


Top or bottom entry for cables >50sq/mm

Plug-in for multiple racks,


subracks, and PDUs

A total of 35U is available for rectifier subracks, distribution, and battery


breaker modules (29U at bottom cable entry)

Yes

Partial Load Disconnect

Yes

Hinged Door Access

Yes

Ethernet Network
Interface

Yes

Modem Interface

Yes

Options
Temp. Comp. Charge

High reliability
Simple installation and operation
LCD display for self-guided controller operation
Interfaces standards include RS232, and Form
C dry alarm contacts with grouped alarms
Up to 1200A per cabinet
Live expansion up to 6400A
Plug-in ready for various DC distributions and
subracks
Inter-cabinet DC paralleling bus
Site programmable supervision unit
Intelligent battery management
Optional Ethernet (SNMP compatible) interface
module
International standards compliance

Note: All specifications are subject to change without notification.

11V0005-039 PPS25 SY V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

www.power-one.com

PPS 7 Power System (Shelf Systems)


Legacy Products- For Reference Only

Description

Features

PPS 7 modular DC power shelf systems


provide large power system features in
cost-effective, rack-mounted form factors.
These shelf-power solutions provide
rectification, system management, and
power distribution while maintaining high
reliability and offering flexibility for future
expansion. The PPS 7 systems are based
on hot-swappable rectifier modules output
power available at 560 or 670 watts per
module.

System management is accomplished


through messages and alarms displayed
on the system controllers (PCU) LCD
screen and can also be displayed remotely
via the PC-based PowCom software.
package.

AUG 29, 2006

Page 1 of 4

High reliability
Simple installation and operation
LCD display for self-guided controller
operation
RS232 interface for remote operation
Intelligent battery management:
Temperature compensation (requires
optional cables)
Programmable battery load testing
with data logging
Symmetry (requires optional cables)
Programmable low voltage
disconnect
Optional Ethernet (SNMP compatible)
interface module
Natural convection cooling - no fans
International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems)


Legacy Products- For Reference Only

System Configurations

PPS 7-2100 System


An all-in-one 3U high shelf system that can
be installed in both 19 and ETSI telecom
cabinet solutions. The system subrack can
accommodate up to three rectifier modules,
a supervision module (PCU), and DC
distribution with a single battery breaker and
six load breakers.

PPS 7-2800 System


An all-in-one 3U high shelf system that can
be installed in both 19 and ETSI telecom
cabinet solutions. The system subrack can
accommodate up to four rectifier modules, a
supervision module (PCU), and DC
distribution with a single battery breaker and
a single load breaker.

PPS 7-3500 System


An all-in-one 6U high shelf system that can
be installed in 19 and ETSI telecom
cabinet solutions. The system subrack can
accommodate up to five rectifier modules, a
supervision module (PCU), and DC
distribution with up to two battery breakers
and twenty load breakers.

AUG 29, 2006

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems)


Legacy Products- For Reference Only

System Components

Rectifier Modules
The PPS 7 system utilizes plug-in rectifier modules that
are based on a soft-switching approach. Features
include 3 LEDs for rectifier status indication, thermal
shutdown, and input overvoltage disconnection with an
automatic reset (only on PMP 7 modules).
Rectifier Features
Model

Voltage

Power (Max)

Current (Max)

PMP 7.24 SIC

24 VDC

560 W

20 A

PMP 7.48 SIC

48 VDC

672 W

12 A

Supervision Module (PCU)


Advanced system supervision is accomplished using a
microprocessor-based control module that allows both local
and remote system monitoring.

AUG 29, 2006

Menu-guided operation
RS232 interface for remote operation
Battery management and testing
Low voltage battery disconnect (LVBD)
Temperature compensation
Battery symmetry measurement
Optional Ethernet interface through SNMP and/or TCP/IP
Partial load disconnection (PLD)

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems)


Legacy Products- For Reference Only
Input
Model

PPS 7-2100

PPS 7-2800

PPS 7-3500

Input

230/400V 3-phase
208-240V 1-phase
Site configurable

230/400V 3-phase
208-240V 1-phase
Site configurable

230/400V 3-phase
208-240V 1-phase
Site configurable

Inputs (max.)

Single input

Single input

Single input

Rectifier Modules (max.)

Battery Outputs

Load Outputs

20

24 VDC Version

Yes

N/A

N/A

48 VDC Version

Yes

Yes

Yes

PCU

PCU

PCU

Battery Symmetry Inputs

Low Voltage Battery


Disconnection (LVBD)

Yes

Yes

Yes

Output

Features
Supervision

Battery

Mechanical
Dimensions (WxHxD)

485x133x305 mm

Mounting

19, ETSI, or flush


ETSI mount
(site configurable)

19, ETSI, or flush


ETSI mount
(site configurable)

19, ETSI, or flush


ETSI mount
(site configurable)

Cable Entry

Top

Top

Top

485x133x305 mm

485x266x305 mm

Options
Temp. Comp. Charge

Yes

Ethernet Network
Interface

Yes

Modem Interface

Yes

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use
as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without
the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change
depending on the date manufactured. Specifications are subject to change without notice.

AUG 29, 2006

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

XCS

Controller

Description
The Power-One Xscend Controller System (XCS) provides comprehensive monitoring
and control for Power-Ones Xscend DC power systems. This digital controller monitors
total system conditions including DC voltage, rectifier current, rectifier temperature,
system capacity, battery parameters and circuit breaker status.
The XCS enables data storage of system configuration information such as battery type,
installation date and system commission date. Visual notification of alarm and warning
conditions are indicated by front panel LEDs, while descriptions of the alarms are provided
through an LCD, or as an option, may be accessed remotely through a modem or a
Network Interface (PNI) module.
To meet individual site requirements, the XCS contains a logic operator that can be
programmed to monitor and control specified requirements. This allows actions to be set,
alarms to be triggered, and outputs to be activated based on internal and external signal
monitoring, comparing and processing.

Features
User controls and interfaces:

Intelligent battery management:

Simple menu-guided operation using front

Temperature compensation with

User-selectable alarm parameters

Automatic and manual load testing

40 event data logging

Battery voltage and symmetry monitoring

Password controlled environment

Capacity testing

Multiple language options

Low voltage disconnect

panel mounted pushbuttons and an LCD

RS232 Interface and Form C dry


alarm contacts

programmable compensation factor

Monthly data logging

www.power-one.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

XCS

Controller
Input

Other Technical Data

Voltage

18-72V DC

Current

<200 mA at 48V, <400 mA at 24V

Interface

Dimensions
(WxHxD)

483/584 x 44 x 274mm
(19/23 x 1.75 x 10.8in.)

Weight

4.94kg (11lbs.)

Operating
Temperature

-40 to +65C

Display

2x20 character LCD with backlight

Internal
Communication

RS485 Data Bus for communication


with a maximum of 128 rectifiers and
128 sub-controllers

Storage
Temperature

-50 to +85C

Internal
Communication

RS232 Serial interface for


remote control from a PC with
PowCom software

Environment

Storage:
Transport:
Operation:

Indications

Green LED Yellow LED Red LED -

Power ON
System warning message
System failure message

Controls

Four pushbutton controls

Signal
Collection

Wide range of interface units with


analog and digital input/outputs

Software

Site upgradeable by EEPROM flash

Language

Multiple language options

Battery
Battery
Disconnection

An optional feature that allows


voltage controlled disconnection
of batteries.

Boost Charging

Manual time controlled or


automatic boost charging with
adjustable time and voltage levels.

Battery Test

Automatic or manual testing of


batteries up to four times per year
with a 10 test memory. Variables
include: test duration, end voltage,
and amount of Ahs to be
discharged during test.

Symmetry
Measurement

Optional tool that measures


batteries for early detection of
thermal runaway. Allows for
separate measurements of up to
12 parallel battery branches, each
divided into four blocks.

Temperature
Compensation
Charging

Allows continuous adjustment of


output voltage according to
battery temperature. Features
include adjustable compensation
factor and separate thresholds for
high temperature alarms.

PLD

Optional feature that allows


voltage or time controlled
disconnection of non-essential
load.

Enhanced
Battery
Monitoring

Monthly logging of essential


battery parameters, including
temperature, temp. hours, current,
charging voltage, and symmetry
voltage. Parameters are stored
for 5 years.

Alarms
Alarm History

The last 40 events are saved and


include a time and date stamp.

Alarm
Contacts

6 potential free change-over alarm


contacts. Two open collector outputs
for LVD operation.

Alarms

High System Voltage


Low System Voltage
Load/ Battery Disc.
Mains Error
Distribution Fuse Failure
Battery Failure
Module Failure
Battery Temp. Alarm
Symmetry Fault
Battery Fuse Failure
High Load
Battery Fuse Disc.
Urgent Module Failure
Communication Failure
Partial Load Disc.

1*
2*
4*
3*
4*
6*
5*
6*
6*
4*
5*
5*
4*
5*
4*

* All alarms are indicated using an LED and displayed in


the LCD. The numbers represent an example of alarm
routing. Sixteen additional alarms are available and are
configurable by changing the PCS EEPROM.

11V0005-061 XCS V3.0

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3

Note: All specifications are subject to change without notification.

www.power-one.com