You are on page 1of 1

1.

Uniform depth of various types of panels in one PCC, depending upon the rating is
not possible to maintain.

2.Lighting trafo only tape wound type.

3.All ACB shall have only release and release shall be microprocessor based
communicable type with O/L, S/C & E/F protection with display. Communication
protocol shall be Modbus type

4.All O/G ACB shall be MDO type however I/C & B/C ACB shall be EDO type 3 Pole
configurations .

5.All MFM shall be digital non communicable type.

6.The Degree of Protection of PCC will be IP42 and for MCCs & DBs will be IP-54

7.Component rating selection of Motor feeder shall be as per GE type 2


coordination charts .

8.Motor protection relay used in 200KW feeder shall be ER make numerical


communicable type.

9.We have considered Motor Protection Circuit Breaker (MPCB) for motor
feeders rated up to 15KW.

10.All MCCB used in power supply feeder shall have electronic type release with
O/L, S/C & E/F protection and all MCCB used in motor feeder shall have electronic
type release with O/L & S/C protection only.

11.We have considered Electronic O/L relay with LED indication for motor feeders
rated 15KW and above. And bellow 15KW bimetal type thermal O/L relay.