You are on page 1of 1

Sub : Ventilation System of Pump Houses, MCC Rooms and Control Room for UCIL Project at Tumallapalle (Andhra

Prad

Motor Make / Motor Voltage /


SL DESCRIPTION/SPECIFICATION pole phase protection insulation Remarks
type Capacity Hz

A SUPPLY OF VENTILATION SYSTEM FOR THE PUMP HOUSES

Item Location Capacity of fan Qty of


No. ( Cu.m/hr ) Fans
(Nos.)
a) Filter water pump 3000cu.m/hr, 20mmwc 415 V / 50
house 1 IEC B3 0.55 KW 4 HZ 3 phase IP 55 Class F

b) Industrial water pump 5500cu.m/hr, 20mmwc 415 V / 50


house 1 IEC B3 0.75 KW 4 3 phase IP 55 Class F
HZ
c) Drinking water Pump 4500cu.m/hr, 20mmwc 415 V / 50
house 1 IEC B3 0.55 KW 4 3 phase IP 55 Class F
HZ
d) Sludge pump house 1000cu.m/hr, 20mmwc 415 V / 50
1 IEC B3 0.37 KW 4 3 phase IP 55 Class F
HZ
e) Monitoring pond pump 2500cu.m/hr, 20mmwc 415 V / 50
house (ETP) 1 IEC B3 0.55 KW 4 HZ 3 phase IP 55 Class F

f) Neutralization Pit pump 2000cu.m/hr, 20mmwc 415 V / 50


house (DM plant ) 1 IEC B3 0.37 KW 4 HZ 3 phase IP 55 Class F

g) Intermediate pump 5100cu.m/hr, 20mmwc 415 V / 50


house 2 IEC B3 0.75 KW 4 3 phase IP 55 Class F
HZ
SUPPLY OF VENTILATION SYSTEM FOR THE SWITCHGEAR
B.
CUM MCC ROOMS
Sl. no. Location Capacity of Exhaust system Qty of
( cu.m/hr ) Fans
(Nos)
a) MCC room (WTP) 4 Centrifugal fan for exhaust 415 V / 50
nos Panel (All LT motor system TEFC Squirrel
HZ
) Cap : 21500 cu.m/hr, Static 1 CROMPTON 7.5 KW 4 3 phase IP 55 Class F Cage induction
Heat load = 3.2 kw pressure 50 mmwc motor

Centrifugal fan for exhaust 415 V / 50 TEFC Squirrel


system 1 CROMPTON 5.5 KW 4 HZ 3 phase IP 55 Class F Cage induction
Cap : 20000 cu.m/hr, Static motor
pressure 40 mmwc
b) MCC room ( Intake Centrifugal fan for exhaust 415 V / 50
pump house ) 2 nos system TEFC Squirrel
HZ
panel (1HT & 1 LT ) Cap : 10600 cu.m/hr, Static 1 CROMPTON 3.7 KW 4 3 phase IP 55 Class F Cage induction
Heat load = 3 kw pressure 50 mmwc motor
Centrifugal fan for exhaust 415 V / 50 TEFC Squirrel
system 1 CROMPTON 2.2 KW 4 HZ 3 phase IP 55 Class F Cage induction
Cap : 9500 cu.m/hr, Static motor
pressure 40 mmwc
c) MCC room Centrifugal fan for exhaust 415 V / 50
(Intermediate pump system HZ TEFC Squirrel
house ) 3 nos panel Cap : 15600 cu.m/hr, Static 1 CROMPTON 5.5 KW 4 3 phase IP 55 Class F Cage induction
(2HT & 1 LT ) pressure 50 mmwc motor
Heat load = 4.5 kw

Centrifugal fan for exhaust 415 V / 50 TEFC Squirrel


system 1 CROMPTON 3.7 KW 4 HZ 3 phase IP 55 Class F Cage induction
Cap : 14000 cu.m/hr, Static motor
pressure 40 mmwc

You might also like