You are on page 1of 4

Laboratory Testing of Aged Conductors and Groundwires

Craig J. Pon, Member, IEEE

1
Abstract – As overhead conductors and groundwires age
substantially beyond their respective design lives, there is
increasing pressure on owners of these assets to know
their present physical condition to help make decisions on
major capital expenditures. Physical assessment is the
only way of knowing the current condition of conductors
and groundwires with any degree of reliability and
accuracy. This discussion presents some laboratory tests
that have been used to assess the condition of conductors
and groundwires. It is beyond the scope of the discussion
to define end of life or remaining life.

I. INTRODUCTION

Many overhead transmission and distribution lines in North


America have far exceeded their design life. In fact, the Figure 1a: New, Unused 3/0 ACSR Conductor
oldest lines may be approaching twice their original design
life. Issues such as competition, reliability, availability,
system planning, public and worker safety among others, are
becoming increasingly important for owners of overhead
lines. Consequently, the desire to know the actual condition
of transmission and distribution line components is also
increasing. Conductors and groundwires are of primary
interest because their condition often drives the decision
whether to commit to, or possibly defer, multi-million dollar
capital refurbishment programs.

Figures 1a-b show two(2) 3/0 ACSR conductors. One is new


and has never been installed. The other was installed in 1939.
Although the surface condition of the 1939 conductor looks
as good as the new one, is it good enough to remain in-
service? Figure 1c shows a conductor installed in 1922. Figure 1b: 3/0 ACSR Conductor Installed in 1939
Although the surface condition has deteriorated, is it enough
reason to replace it?

There are some specialized devices that assess certain aspects


of conductors/groundwires in the field. Laboratory evaluation
can provide much more detailed information about the
condition of conductors/groundwires.

This discussion presents some laboratory test methods


available to assess the present condition of overhead
conductors and groundwires and to better understand their
aging processes. It is beyond the scope the discussion to
define end of life or remaining life.

Craig J. Pon is a Principal Engineer at Kinectrics, Inc, Figure 1c: 605 kcmil,54/7 ACSR Conductor Installed in 1922
Toronto, Ontario, M8Z 6C4, Canada. His email is
craig.pon@kinectrics.com.

0-7803-7519-X/02/$17.00 © 2002 IEEE


700
II. DETERIORATION OF STRENGTH i) Aeolian Vibration Endurance Test

There are two(2) main mechanisms that will cause conductors It is possible to estimate the history of aeolian vibration at
and groundwires to deteriorate due to natural aging processes. specific locations on a line by taking filed measurements
using line vibration recorders. If vibration levels are below
1) Loss of Fatigue Strength due to wind-induced vibration recognized safe levels, then loss of fatigue strength of the
2) Loss of Tensile Strength due to corrosion aluminum strands is unlikely. If vibration is detected above
safe levels, then an estimate of remaining fatigue life can be
III. LABORATORY TESTS made. Vibration dampers are normally used to reduce
vibration activity to safe levels.
Laboratory tests can provide detailed information on samples
of aged conductors/groundwires that cannot be obtained using If a laboratory assessment of the remaining fatigue strength is
in-situ or analytical techniques. The information can be used pursued, an Aeolian Vibration Endurance Test can be
to: performed to requalify aged conductor/groundwires. IEEE
Std 1138-1994 “IEEE Standard Construction of Composite
i) requalify conductors/groundwires for a specified period Fiber Optic Overhead Ground Wire (OPGW) for Use on
in the future Electric Utility Power Lines” describes a test method. They
ii) help in the estimation of the remaining physical life of are subjected to aeolian vibrations for a specified number of
conductors/groundwires cycles at a specified severity that may be experienced in a
iii) help determine if opportunities to uprate lines exist specified future period. If the conductor/groundwire survives
this test without fatigue damage, then it can be requalified for
The tests provide information on different characteristics and that specified time.
properties of the whole conductor/groundwire or of the
individual strands. The information from the tests contributes The sample used for these tests should be performed with the
directly or indirectly to an overall assessment relating to the suspension clamp or other hardware still installed and
deterioration mechanisms or other end of life criteria. undisturbed on the cable from the time of removal. Fatigue
cycles imparted during the test will be added to the fatigue
Any given test may or may not provide information that leads cycles accumulated in the field.
to definitive conclusions. However, when the data from
several tests are taken together, more reliable interpretations ii) Galloping Endurance Test
of the present condition of the conductor/groundwire can be
made. Galloping can also cause damage to the aluminum strands
through low cycle, high amplitude fatigue. However, unlike
The following tests, analyses and examinations can be aeolian vibration, quantitative field measurements are much
performed in the laboratory. Other tests not listed may also more difficult to obtain because of the randomness of the
provide useful information. event.

i) Aeolian Vibration Endurance Test A Galloping Endurance Test can be approached in a similar
ii) Galloping Endurance Test manner as for aeolian vibration. IEEE Std 1138-1994 “IEEE
iii) Sheave Passing Test Standard Construction of Composite Fiber Optic Overhead
iv) Torsional Ductility Test Ground Wire (OPGW) for Use on Electric Utility Power
v) Tension and Elongation at Failure Test Lines” describes a test method for galloping.
vi) Creep Test
vii) Remaining Zinc Test iii) Sheave Passing Test
viii) Wrap Test
ix) Visual Analysis A Sheave Passing Test can verify the ability of the aged
x) Electrical Resistance Test conductor/groundwire to withstand passing over a sheave a
xi) Metallurgical Examination number of times without undesirable damage to the
xii) Chemical Analysis conductor. Some utilities use the existing conductor or
xiii) Accelerated Corrosion Test groundwire to pull in the new cable. It is important that the
outside strands of the existing conductor/groundwire pass
The results of some tests can be referenced to either new, through the sheaves without breaking. Broken strands will
unused samples of similar construction or to industry separate from the body of the conductor and get entwined in
standards. If the assessment program has been in place for a the sheaves resulting in costly delays. Added confidence
sufficient period of time, the results can also be compared to about the good condition of the cable can be obtained by
the results of previous tests to estimate the rate of performing this test after the vibration test. In either case, the
deterioration. section of cable under the suspension clamp, other hardware
attachment points or where corrosion may be more advanced

701
should be passed over the sheave. IEEE Std 1138-1994
“IEEE Standard Construction of Composite Fiber Optic
Overhead Ground Wire (OPGW) for Use on Electric Utility
Power Lines” describes a test method for sheave passing.

iv) Torsional Ductility Test

The Torsional Ductility Test can either requalify the


conductor/groundwire for a specified period of time or
identify it as a candidate for replacement. The test method is
based on ASTM A938-1997 “Standard Test Method for
Torsion Testing of Wire” and was originally applied to
groundwires. It relates the number of turns to failure to a
subjective assessment of the degree of corrosion on steel
strands. Threshold numbers are used to make an assessment
about what future action should be taken. Use of the data
from this test is based largely on experience. The test has also
been used to assess the steel strands of ACSR conductors. Figure 2a: 5/16”, 7 Strand Galvanized Steel Groundwire
(Avg turns to Failure –31.2, Tensile Strength– 108.5% RTS)
Figures 2a-b show two(2), 5/16”, 7 strand galvanized steel
groundwires. The groundwire is shown intact at the bottom of
each photo and shown with the strands separated at the top of
the photo. The strands in Figure 2a look in much better
shape than those in Figure 2b. The centre strand, without
helix, is almost always in better shape than the six(6) outer
strands and usually fails at a higher value. For this reason, the
centre strand is tested but not included in the analysis. The
average number of turns to failure of the six(6) strands, not
including the centre strand, was 31.2 for the ground wire in
Figure 2a and 2.8 for the groundwire in Figure 2b.

v) Tension and Elongation at Failure Test

The Tension Test is used to assess the remaining tensile


strength of the whole conductor/groundwire or of the
individual strands. The test method is based on ASTM E8-01
“Standard Test Methods for Tension Testing of Metallic Figure 2b: 5/16”, 7 Strand Galvanized Steel Groundwire
Materials”. This test is quite useful because it is quite simple (Avg turns to Failure –2.8, Tensile Strength– 94.8% RTS)
yet provides the most information directly related to the
tensile strength in relation to design or actual field loads. Conductors in Overhead Lines” or IEC 61395-1998
Knowledge of the elongation of the strand at failure can help “Overhead Electrical Conductors – Creep Test Procedures
determine if the strand material has become more brittle or for Stranded Conductors”. The test can be performed at room
ductile over time. temperature, at elevated temperatures and/or at varying
tensions. This test may provide useful information if the line
The tensile strength of the groundwire calculated by adding is being considered for uprating.
the breaking strength of the individual strands including the
centre strand was 108.5% of the RTS for the groundwire in vii) Remaining Zinc Test
Figure 2a and 94.8% for the groundwire in Figure 2b.
An estimate of the remaining zinc on steel wires of ACSR
vi) Creep Test conductors and groundwires is possible in-situ using a
specially designed device.
Creep Tests can be used to determine how much creep can be
expected in future years. The test method is based on the If more detailed information from laboratory testing is
Aluminum Association-1971, “A Test Method for required, the Remaining Zinc Galvanizing Test can be
Determining the Long Term Tensile Creep of Aluminum performed using ASTM A90/A90M-01 “Standard Test
Method for Weight(Mass) of Coating on Iron and Steel
Articles with Zinc or Zinc-Alloy Coatings” on individual zinc
galvanized steel strands. The remaining zinc is removed from

702
the strand and weighed. The average thickness of zinc that Accelerated Corrosion Tests can be useful to help determine
remained on the strand can then be calculated. The quantity the remaining life of conductors/groundwires. By subjecting
of remaining zinc can be compared to the values specified by aged conductors/groundwires to a standard set of controlled
ASTM B498/B498M-98 “Standard Specification for corrosion conditions, the aging or deterioration process can be
Aluminum Steel Core Wire for Aluminum Conductors, Steel accelerated to a condition of the conductor/groundwire that is
Reinforced” or to previous measurements to estimate the rate defined as end of life. It is necessary to relate the standard
of deterioration. corrosion condition in the laboratory to actual corrosion
conditions in the field. If this can be done then it would be
viii) Wrap Test possible to relate the time to the end of life in the laboratory to
the end of life in the field. Standard test conditions specified
The Wrap Test can be performed to verify the adherence of by ASTM B117-97 “Standard Practice for Operating Salt
the zinc coating on the steel strand. The test is performed to Spray (Fog) Testing Apparatus” and EIA/TIA Std 455-16A
ASTM A475-98 “Standard Specification for Zinc-Coated “Salt Spray (Corrosion) Test for Fibre Optic Components”
Steel Wire Strand”. The zinc galvanized strand is wrapped at have been used.
least twice around a mandrel 3 times the nominal diameter of
the strand under test. Cracking or flaking of the zinc would
indicate loss of adhesion. V. LABORATORY TESTS AND REMAINING LIFE

ix) Visual Examination Laboratory testing provides information on the present


physical state of a conductor/groundwire. Input of this
A Visual Examination of the surface condition of the whole information into suitable models can provide an estimate of
conductor/groundwire and the individual strands is a good remaining physical life. However, this will probably not be
indicator of their general condition. Observations of how any the final determining factor when it is actually replaced. An
corrosion products accumulate within the conductor cross- asset management program that considers many issues such as
section and along its length can be instructive. They can also public and worker safety, competition, reliability, availability,
serve as an indicator of what to expect for other tests. system planning, availability of capital among others will
ultimately decide when to replace a conductor.
x) Electrical Resistance Test

The Electrical Resistance Test can be performed to determine VI. CONCLUDING COMMENTS
and verify the current carrying capability of the conductor.
The resistance of the conductor of the conductor can be 1. When appropriate, laboratory tests can provide much
compared to that of a new conductor and/or to ASTM more detailed, quantitative and reliable information on
B232/B232M-01e1 “Standard Specification for Concentric the condition of conductors/groundwires than
Lay Stranded Aluminum Conductors, Coated-Steel conventional inspection techniques.
Reinforced”. 2. Interpretation of laboratory test results for determining
remaining physical life is still evolving.
An excessive increase in the resistance of the conductor may 3. Laboratory inspections of conductor/groundwire are
indicate that its current carrying capacity may be reduced. location specific. Prudent selection and sampling criteria,
This may be useful information for corroded conductors. can identify line sections with the highest probability of
conductor/groundwire deterioration.
xi) Metallurgical Examination 4. As well as determining if a conductor/groundwire is in
bad condition, laboratory tests can also verify the good
The objective of Metallurgical Examinations is to compare condition of a conductor/groundwire. This can lead to
the microstructure and microhardness of aged strands to new
confidence that the conductor/groundwire can remain in-
strands.
service for longer than might be expected.
xii) Chemical Analysis
Craig J. Pon (M) received his B.A. Sc. and M. Eng. degrees in Mechanical
Chemical Analysis can be performed to constituent elements Engineering from the University of Toronto in 1979 and 1989, respectively.
in aged strands to those specified in standard specifications. He began his working career in 1979 with the Research Division of Ontario
The presence and concentrations of airborne pollutants can be Hydro. He is currently a Principal Engineer with Kinectrics, Inc., a successor
company of Ontario Hydro. He is involved with mechanical testing and
ascertained if they are part of the corrosion products. assessment of transmission and distribution line components. He also is
involved with testing fibre optic cables and accessories. He has been a
member or chairman of several IEEE WG’s including WG on Overhead
Conductors Dynamics and the WG on Fibre Optic Standards.
xiii) Accelerated Corrosion Test

703

You might also like