Professional Documents
Culture Documents
ENTER DATA IN YELLOW CELL ONLY. Note: These calcualtions are at fundamental frequency of 50Hz. In the presence of harmonics Xeff value at that harmonic has to be considered. Ex for 5th harmonic, Xeff5 = (Xc/5-XL*5), similarly for all other harmonics. In general, Xeffn = (Xc/n -XL*n ) Current drawn by each harmonic to be calculated, then the RMS value can be calculated.
Xc (capacitor impedance) XL (reactor impedance) Tuning factor Capacitance micro farad Resonance frequency Harmonic order
11.0250 ohms 0.7286 ohms 6.6 % 288.7 MFD 194 Hz 3.89 order 10.2964 ohms 23.27 amps 27.49 amps
Series reactor rating X eff (effective reactance) milli Henry 2.3192 mH Current drawn by the filter (REFER THE TABLES BELOW) Rated current of capacitor