You are on page 1of 5

Site Layout-GBT

Guard Room Main Gate

DG Tower

Shelter

Verified by WTTIL Dated- 28.04.2009

Lighting Arrestor

SLD FOR CELL SITE EARTHING

EB METER

SFU

SERVO

DG CANOPY

AMF INSIDE CANOPY

25 X 6 MM GI STRIP To SHELTER ISB 2 OPPOSITE PLACES OPPOSITE PLACES

TO TOWER 2 DIAGONALLY

25 X 6 MM GI STRIP

To DG NEUTRAL

25 X 6 MM GI STRIP

400X100x10mm GI PLATE with 20 holes,8 mm dia.

TO PIU OR ACDB

To AC

E1 GI / 2
Verified by WTTIL Dated- 28.04.2009

E1 GI / 3 25 X 6 MM GI STRIP

E1 Cu

INTERNAL CABLE EARTHED 2 DIAGONALLY OPPOSITE PLACES IGB SHELTER

EGB
EGB & IGB ARE INTERCONNECTED

25 X 3 MM COPPER STRIP

Earthing Diagram GI Strip(25X6) Shelter


GI Strip shown in thick dark line

IGB

CU EP-1
TOWER GI EP-2
2X(1CX16) Sq mm CU Green cable

GI EP-3
All body earthing should be done through Bus Bar(25X6, 2nos GI strip).

DG
2X(1CX16) Sq mm CU

Bus Bar
Verified by WTTIL Dated- 28.04.2009

Green cable for

DG

Neutral

Shelter Internal Layout

3 Model Box 16MPower point

BTS

BTS

BTS

2 M Box For Bulkhead

Cu Busbar Rf Earth 6 Model Box For Switch Board

Bulkhead fitting

Door

1X40 w Tube light

1X40 w Tube light

AC

Do not show distance

MDS Box 2 No with 20A MCB

PIU
150mm Distance to sheltar wall

PP BB

DCDB

Tx Rack

BTS

Verified by WTTIL Dated- 28.04.2009

DG Without AMF
DCDB

Tx rack

2cX16 Sq mm Cu multistrands 4 core alarm cable

20 pair alarm cable

Alarm Box

20 pair alarm cable

D D F

2x1cX50 Sq mm Cu multistrands B/Charger

BB 600 AH

DC Power Plant

4 sq mmx2 core cu flexible

2.5 sq mmx2 core cu flexible


1.5 sq mmx10/12 core cu flexible/Armored

6 sq mmx3 core cu flexible 10sq mmx2 core cu flexible For dg to battery Charger

Relay Box

10 Sq mm x 3 Cu Flexible

PIU

DG Set
20KVA

AC

M C B

35 sq mmx4 core AL armored 35 sq mmx4 core AL armored

EB

Cable laying by Electrical vendor Cable laying by Electrical Vendor Cable laying by Air conditioner vendor
Verified by WTTIL Dated- 28.04.2009

Cable termination by Electrical vendor Cable termination by Electrical Vendor

Cable termination by AC Vendor


Cable termination by BSS