Professional Documents
Culture Documents
YCAV
Without the need for hot gas bypass. No slide valve is required. Low current inrush at start.
Pressure
Compressor
Temperature oC Water Temperature oC
12
Condenser Subcooling
Evaporator
Chilled Water OUT Chilled Water IN
Condenser Coil
Compressor
Oil Separator
Cooler
In
Expansion Device
(Pressure reduction)
Pressure
Compressor
Temperature oC Water Temperature oC
12
Economizer Subcooling
Condenser Subcooling
Evaporator
Chilled Water OUT Chilled Water IN
Total Subcooling
Optional High IPLV chillers have control algorithms that provide smart anticipatory control ( Fuzzy Logic ) to determine how many compressors need to be started to satisfy the current load.
1 IPLV =
0.01
0.42
0.45 10.949
0.12 9.259
6.106 8.812
Basic Electronic
Basic Electronic
How does change the frequency change the motor speed?
Basic knowledge of electrical induction motor:
1) RPM ( Rotate per minutes) = Hz . 120 / Pol What is the maximum speed of 50Hz ,2 pol, motor?
2) C = V / F = Constant What is the voltage / frequency ratio of a 3 phase , 50 Hz motor? Question :Is it possible to keep this ration by changing the voltage and frequency?
V.S.D Logic
3 Phase Power Line
Compressor 1
AC / DC Rectifier
Rectifier Controller
Compressor 3
Rectifier
Inverter
PWM Signal
Basic Electronic
How does the motor hours power change by change the frequency?
Frequency Rate is : 0 / 100 ( increase rate 10 Hz / sec ) 0 / 200 ( increase rate 30.4 Hz / sec )
The Economizer Solenoid controls a vapor feed to the economizer port on the compressor from the top of the Flash Tank. When the valve is open, refrigerant gases off in the Flash Tank providing additional subcooling to the liquid in the tank. The subcooled liquid is then fed to the evaporator resulting in additional system capacity and efficiency.
The Flash Tank Feed and Drain Valve Controller is a microprocessor driven controller that operates the Feed and Drain Valves based on commands from the Chiller Control Board. The Feed and Drain Valves control the level of liquid in the Flash Tank and the superheat to the evaporator. The Flash Tank liquid level is controlled by sequencing a stepper motor valve (Feed Valve) on the inlet of the flash tank. The controller opens and closes the feed valve to control the liquid level of the refrigerant in the Flash Tank based on commands from the Chiller Control Board. Drain Valve superheat control is controlled by a PI control algorithm based on suction pressure and suction temperature in the Chiller Control Board software. The control algorithms will attempt to control the level in the flash tank to approx 35% when the economizer is energized. If the level exceeds 87.5%, the system will fault.
YCIV Training by Gholam Reza Khajeh
Optical panel
Optical Panel allows complete control of the system from a central location. The keypad offers a multitude of command keys on the left and right side of the keypad to access displays, program set points, history, data, and initiate system commands.
The display consists of a liquid crystal 2 line by 40 characters per line display, with backlighting for outdoor viewing of operating parameters and program points.
YCIV Training by Gholam Reza Khajeh
Optical panel
Which kind of parameters should be access able from Optical Panel?
1. Entering and leaving chilled liquid, and ambient temperature. 2. Day, date and time. Daily start/stop times. Holiday and Manual Override status. 3. Compressor operating hours and starts. Automatic or manual lead/lag. Lead compressor identification. 4. Run permissive status. Compressor run status. 5. Anti-recycle timers. 6. System suction (and suction superheat), discharge (and discharge superheat), and oil pressures and temperatures. 7. Percent full load compressor motor current and average motor current. Compressor motor speed (frequency). 8. Cutout status and set points for: supply chilled liquid temperature, low suction pressure, high discharge pressure and temperature, high oil temperature, low ambient, and low leaving liquid temperature. 9. Unloading limit set points for high discharge pressure and compressor motor current. 10. Status of: evaporator heater, condenser fans, load/ unload timers, and chilled water pump. 11. Out of range message. 12. Up to 10 fault shutdown histories
Optical panel
Status Key
The displays the current chiller or system operational status. The messages displayed include: Running status Cooling demand System faults Unit faults VSD faults Unit warnings External device status Load limiting Anti-recycle timer Status of unit/system switches and a number of other messages.
The STATUS key must be pressed twice to view both system 1/2 and system 3/4 data.
YCIV Training by Gholam Reza Khajeh
The first key press displays Evaporator Leaving and Return Chilled Liquid Temps.
UNIT CHILLED LIQUID LEAVING = XXX.X F ENTERING = XXX.X F
The next key press of the UNIT DATA key or the (ARROW) key displays the ambient air temperature.
UNIT OUTSIDE AMBIENT AIR TEMP = XXX.X F
System Data
System Data as an example for R134a
Important :Also keep in mind that measuring inverter PWM current is difficult and meter error can be significant.
HOURS 1=XXXXX, 2=XXXXX, 3=XXXXX, 4=XXXXX START 1=XXXXX, 2=XXXXX, 3=XXXXX, 4=XXXXX
HISTORY Key
By press the History key, the following screen will be displayed:
FAULT HIST XX 18-JUN-20004 10:34:58 AM YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
The operator can view any of the stored 10 fault history buffers. The ALL FAULT display indicates when a fault occurred while the unit is shutting down on another fault.
FAULT HIST XX ALL FAULTS ZZ OF WW YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
The values displayed under each of the key presses may be changed by keying in new values and pressing the (ENTER) key to store the new value into memory.
SETPOINTS DEF XXXXX LO XXXXX HI XXXXX MAXIMUM REMOTE TEMP RESET = XXX.X F
SETPOINTS DEF XXXXX LO XXXXX HI XXXXX LOCAL CONTROL RANGE = +/- X.X F
Programming Key
Various operating parameters are programmable by the user. These are modified by pressing the PROGRAM key and then the (ENTER) key to enter Program Mode.
1. 2. 3. 4. 5. 6. 7. 8. 9.
Suction Pressure Cutout Low Ambient Cutout Low Leaving Liquid Temp Cutout Motor Current Limit Pulldown Current Limit Pulldown Current Limit Time Suction Superheat Setpoint Unit ID Number Sound Limit Setpoint
Programming Key
Programmable operation parameters and Limits
Option Key
The OPTIONS key provides the user with a display of unit configuration and the capability to modify the configuration 1. 2. 3. 4. 5. 6. 7. 8. 9. Display Language Selection Chilled Liquid Cooling Mode Selection Local / Remote Control Mode Selection Display Units Selection System Lead/Lag Control Mode Selection Remote Temperature Reset Selection Remote Current Limit Input Selection Remote Sound Limit Selection Low Ambient Cutout Enable/Disable
The Chilled liquid cooling mode can be selected for Water Cooling or low temperature Glycol Cooling.
YCIV Training by Gholam Reza Khajeh
Use the arrow keys with numeric to enter correct date / time and schedule for daily start /stop and holidays schedule. Confirm the entry by pressing ENTER key.
MANUAL OVERRIDE
MANUAL OVERRIDE is to only be used in emergencies or for servicing.
If the MANUAL OVERRIDE key is pressed during a schedule shutdown, the STATUS display will display the message below:
MANUAL OVERRIDE
This indicates that the Daily Schedule is being ignored and the chiller will start when chilled liquid temperature allows, Remote Contacts, UNIT switch and SYSTEM switches permitting. This is a priority message and cannot be overridden by anti-recycle messages, fault messages, etc. when in the STATUS display mode. Therefore, do not expect to see any other STATUS messages when in the MANUAL OVERRIDE mode.
Print Key
The PRINT key is used to initiate a printout of current operating data (real time data), a complete history printout of all history (fault) buffers, a printout of all normal shutdowns (compressor cycling, chiller shutdown, etc.) or history (fault) data printout of a specific fault.
PRINTOUT TYPES Operating Data
After pressing the PRINT key, the printout type is selected by pressing the (LEFT ARROW) or (RIGHT ARROW) keys until the desired printout is displayed.
History Buffer 2 History Buffer 3 History Buffer 4 History Buffer 5 History Buffer 6 History Buffer 7 History Buffer 8
Data such as circuit board output status as controlled by the Chiller Control software while operating can be viewed and compared to actual chiller operation in the event servicing is required. The Service Key allows controlling of analog and digital outputs for troubleshooting purposes when the unit is not running. The Unit Serial Number and Optimized IPLV Control mode are also entered using the Service Key.
The data sections are : 1. Software Versions 2. Analog Inputs 3. Digital Inputs 4. Digital Outputs 5. Analog Outputs 6. VSD Logic Digital Output
YCIV Training by Gholam Reza Khajeh
SYSTEM SWITCHES SYSTEM SWITCHES SYSTEM SWITCHES SYSTEM SWITCHES SYSTEM SWITCHES SYSTEM SWITCHES SYSTEM SWITCHES SYSTEM SWITCHES
SYS 11ON / /OFF / /RESET SYS ON OFF RESET =XXXXXXXXXXXXXXX =XXXXXXXXXXXXXXX SYS 22ON / /OFF / /RESET SYS ON OFF RESET =XXXXXXXXXXXXXXX =XXXXXXXXXXXXXXX SYS 33ON / /OFF / /RESET SYS ON OFF RESET =XXXXXXXXXXXXXXX =XXXXXXXXXXXXXXX SYS 44ON / /OFF / /RESET SYS ON OFF RESET =XXXXXXXXXXXXXXX =XXXXXXXXXXXXXXX
The (LEFT ARROW) or (RIGHT ARROW) keys allow scrolling through the choices and Press Enter to confirm.
TB2 allows connecting to a remote OptiView or Microgateway. Only one or the other is permitted to be connected to the chiller.
Maintenance
DAILY MAINTENANCE
1. 2. 3. 4. 5. 6. Unit Status Refrigerant Leaks Airflow Obstructions Operating Conditions Compressor Oil Level Refrigerant Charge ( FROM SIGHT GLASS) ( PRESSURE, Temp, .) (To check all errors and messages)
SCHEDULED MAINTENANCE
Each 6 month by Professional JCI - YORK service engineer
Maintenance
PROCEDURE Check oil level in oil separator sight glass Check liquid line sight glass / moisture indicator X Record system operating pressures and temperatures X Check programmable operating set points and safety cut-outs WEEKLY X X X X
QUARTERLY
SEMI-ANNUALLY
YEARLY
Check condenser coils for dirt/debris and clean if necessary X Check compressor superheat on evaporator and economizer TXVs; Check condenser and economizer subcooling1 X Check compressor and cooler heaters for operation X Sample compressor oil and replace oil if necessary1 X Leak check the chiller1 X Disconnect power source and lock out; Check tightness of power wiring connections1 X
X X X X X X
Check Glycol concentration on low Temp. X Or other applications where freezing may be a problem VSD Glycol Change Each 5 Years