All dosage equation are based on C1Q1=C2Q2 Where C= concentration of chemical, Q= Flow rate Or, Chemical feed solution

(mg/l) X feed pump output(gallon/day) = Desired chemical dose(mg/l) X plant flow rate HP dosing calculation Steam tph=10000 kgh TDS in feed water=.1 TDS permitted in boiler= 25 ppm Percentage blow down = 100X.1/(25-0.1)=0.4% Actual blow down rate = 10000X 0.4/1000kgr=40kgr PPM PO4 dose=4ppm Loss of PO4 in BD=4X40/1000g/h=0.16 gm/hr Loss of TSP in blowdown=0.16X4=0.64g/hr TSP consumption/day=0.64X24/1000 kg/day=0.1536 LP dosing calculation Steam tph=10000 kgh O2 in feed water after deaeration @ 105 0C=0.02ppm Required oxygen level in feed water = 0.002 ppm Oxygen to be removed = 0.02 0.002 ppm =0.018 N2H4 rqrd(30times) = 30 X 0.018 ppm=0.54 ppm Residual N2H4 to be kept = 0.02 ppm Total N2H4 rqrd = 0.54 + 0.02=0.56 ppm Total N2H4 rqrd in Kg/Kg of evaporation = 0.56 X 0.000001 kg/kg = 0.00000056 kg/kg N2H4 rqrd/hr = 10000 X 0.00000056 = 0.0056 kg/hr Conc. Of N2H4 soln = 35% N2H4 to be dosed @ 35 % conc = .0056 X 100/35 kg/hr=0.016 kg /hr N2H4 Consumption/day = 0.016 X 24 Kg/day = 0.384 kg/day