Professional Documents
Culture Documents
Output Ratings
Generating Set Model Prime* 480V, 60 Hz 675.0 kVA 540.0 kW * Refer to ratings definitions on page 4. Ratings at 0.8 Ratingsat .8 power factor. power factor Standby* 750.0 kVA 600.0 kW
Technical Data
Engine Make & Model: Alternator Model: Base Frame Type: Circuit Breaker Type: Frequency: Engine Speed: RPM Fuel Tank Capacity: litres (US gal) Fuel Consumption, Prime: l/hr (US gal/hr) Fuel Consumption, Standby : l/hr (US gal/hr) Perkins 2806A-E18TAG3 LL7024J Heavy Duty Fabricated Steel 3 Pole ACB/MCCB 50 Hz 1000 (264.2) 138.4 (36.6) 155.6 (41.1) 60 Hz 1800
Lubrication system
Oil Filter Type: Total Oil Capacity l (US gal): Oil Pan l (US gal): Oil Type: Cooling Method: Eco, Full Flow 55.5 (14.7) 53.5 (14.1) API CH4 / CI4 Water
Performance
Engine Speed: RPM Gross Engine Power: kW (hp) -Standby: -Prime:
50 Hz
-
60 Hz
1800 678.2 (909.0) 617.5 (828.0)
Fuel System
Fuel Filter Type: Eco Replaceable Element Recommended Fuel: 110% Load
Air System
Air Filter Type: Combustion Air Flow: m/min (cfm) -Standby: -Prime: Max. Combustion Air Intake Restriction: kPa (in H2O) Radiator Cooling Air Flow: m/min (cfm) External Restriction to Cooling Air Flow: Pa (in H2O)
50 Hz
Replaceable Element -
60 Hz
Class A2 Diesel Fuel Consumption: l/hr (US gal/hr) 100% Load 75% Load 50% Load
47.6 (1681) 44.3 (1564) 6.3 (25.3) 804.0 (28393) 125 (0.5)
Prime 50 Hz 60 Hz Standby 50 Hz 60 Hz 155.6 (41.1) 114.7 (30.3) 79.2 (20.9) 155.3 (41.0) 138.4 (36.6) 103.3 (27.3) 72.6 (19.2)
(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)
Cooling System
Cooling System Capacity: l (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil: kW (Btu/min) -Standby: -Prime: Heat Radiation to Room: kW (Btu/min) -Standby: -Prime: Radiator Fan Load: kW (hp)
50 Hz
-
60 Hz
61.0 (16.1)
Exhaust System
Silencer Type: Silencer Noise Reduction Pressure Drop Across Silencer System: kPa (in Hg) Silencer Noise Reduction
50 Hz
Level 1
60 Hz
SD200 (1) 0.47 (0.139) 10 6.8 (2.0) 143.0 (5050) 130.0 (4591) 542 (1008) 513 (955)
Centrifugal
170.9 (9719) 163.9 (9321) 45.6 (2593) 41.6 (2366) 14.0 (18.8)
Level: dB Max. Allowable Back Pressure: kPa (in. Hg) Exhaust Gas Flow: m/min (cfm) -Standby: -Prime: Exhaust Gas Temperature: C (F) m/min (cfm) -Standby: -Prime:
Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local Olympian dealer for power ratings at specific site conditions.
60 Hz
440/254V 220/127V
1993
1283
1694
300
300
300
300
300
300
300
300
300
Xd X'd X''d
Reactances shown are applicable to standby ratings. * Based on 30% voltage dip. ** With optional Permanent Magnet generator or AREP excitation.
Operating Data
Overspeed: RPM Voltage Regulation (steady state) (% ): Wave Form NEMA = TIF: Wave Form IEC = THF: Total Harmonic Content LL/LN: Radio Interference: 2250 +/- 0.5 50 2.0% 4.0%
Technical Data
3 Phase Ratings and Performance at 50 Hz, RPM 3 Phase Ratings and Performance at 60 Hz, 1800 RPM
Voltage
kVA
Prime
kW
Standby
kVA kW
Voltage
kVA
480/277V 220/127V 380/220V 675.0 675.0 675.0
Prime
kW
540.0 540.0 540.0
Standby
kVA
750.0 750.0 750.0
kW
600.0 600.0 600.0
440/254V
Dimensions: mm (in)
Length Width Height 4111 (161.9) 1536 (60.5) 2246 (88.4)
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Definitions
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
General Data
Documents
A full set of operation and maintenance manuals and circuit wiring diagrams.
Warranty
All equipment carries full manufacturer's warranty.
LEHF8849-02 (09-10)
Discretion isis recommended when distributing. Discretion recommended when distributing. Materials and specifications are subject to change without notice. Materials and specifications are subject to change without notice. CAT,CAT, CATERPILLAR, their respective logos, OLYMPIAN, Caterpillar Yellow, the Power Edge trade dress as well as as CATERPILLAR, their respective logos OLYMPIAN, "Caterpillar Yellow", and the "Power Edge" trade dress, as well corporate andand product identity used herein,are trademarks of Caterpillar and may not bebe used without permission. Caterpillar and may not used without permission. corporate product identity used herein, are trademarks
Information contained in this publicationmay be considered confidential. may be considered confidential. Information contained in this publication