Professional Documents
Culture Documents
Project Information
Project #: Name: Location: 7 Podno grijanje Notes:
Area 8.7 8.9 15.6 12.7 60.7 13.4 5.3 20.3 21.4 2.6 14.4
Temperature = C BB = Baseboard
RH Circuits 1 1 1 1 5 1 1 2 2 1 1
Flowrate 0.01 0.01 0.02 0.01 0.10 0.02 0.01 0.04 0.03 0.02 0.03
Head Loss = kPa N = Not Heated
Head Loss 9 4 4 9 10 5 4 5 5 9 7
Rooms Room 5, WC vanjski Garderoba Spavaca soba 1 Kuhinja Dnevni boravak Spavaca soba 2 Hodnik Kupatilo Kotlovnica WC Radna soba 2
Created using LoopCAD 2011 Viega Add-On Version:2.5.0598 (Trial)
Page 1 of 10
Name:Podno grijanje Project #:7 112 113 Total 16.7 9.8 210.5 RH,OTH RH NH,RH,OTH 1 1 19 0.07 0.01 0.38 18 9 18 Radna soba 1 Ulazni hodnik
Temperature = C BB = Baseboard
Page 2 of 10
C C W
279 W 0 W 2416 W
Garderoba
Total Area: Heated by: Room Temperature: 8.9 m RH 15 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 6.7 55 1 150 18 28 367 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 266 W 300 0 0 0 W W W W
C C W
34 W 0 W 300 W
Temperature = C BB = Baseboard
Page 3 of 10
Hodnik
Total Area: Heated by: Room Temperature: 5.3 m RH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 4.1 9 1 229 22 30 156 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 89 W 104 0 0 0 W W W W
C C W
15 W 0 W 104 W
Kotlovnica
Total Area: Heated by: Room Temperature: 21.4 m RH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 17.6 79 2 229 23 34 667 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 663 W 772 0 0 0 W W W W
C C W
109 W 0 W 772 W
Kuhinja
Total Area: Heated by: Room Temperature: 12.7 m RH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 10.8 92 1 150 22 30 333 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 298 W 344 0 0 0 W W W W
C C W
46 W 0 W 344 W
Temperature = C BB = Baseboard
Page 4 of 10
Kupatilo
Total Area: Heated by: Room Temperature: 20.3 m RH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 16.1 110 2 150 24 34 683 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 683 W 768 0 0 0 W W W W
C C W
86 W 0 W 768 W
Radna soba 1
Total Area: Heated by: Room Temperature: 16.7 m RH,OTH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 13.6 94 1 150 25 38 655 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 655 W 770 0 0 191 W W W W
C C W
115 W 0 W 961 W
Radna soba 2
Total Area: Heated by: Room Temperature: 14.4 m RH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 11.7 81 1 150 24 34 521 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 521 W 603 0 0 0 W W W W
C C W
82 W 0 W 603 W
Temperature = C BB = Baseboard
Page 5 of 10
Room 5
Total Area: Heated by: Room Temperature: 1.9 m NH -9 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 1.2 0 0 229 -9 33 0 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 0 W 0 0 0 0 W W W W
C C W
0 W 0 W 0 W
Spavaca soba 1
Total Area: Heated by: Room Temperature: 15.6 m RH,OTH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 13.2 85 1 150 23 32 449 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 449 W 518 0 0 3 W W W W
C C W
69 W 0 W 521 W
Spavaca soba 2
Total Area: Heated by: Room Temperature: 13.4 m RH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 11.2 80 1 150 24 33 460 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 460 W 520 0 0 0 W W W W
C C W
60 W 0 W 520 W
Temperature = C BB = Baseboard
Page 6 of 10
Ulazni hodnik
Total Area: Heated by: Room Temperature: 9.8 m RH 15 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 7.5 18 1 229 20 33 447 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 392 W 426 0 0 0 W W W W
C C W
34 W 0 W 426 W
WC
Total Area: Heated by: Room Temperature: 2.6 m RH,OTH 20 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 1.9 18 1 229 24 36 79 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 79 W 87 0 0 7 W W W W
C C W
8 W 0 W 94 W
Temperature = C BB = Baseboard
Page 7 of 10
WC vanjski
Total Area: Heated by: Room Temperature: 6.8 m RH 10 C Radiant Heating: Heated Area: Tubing in Floor: Circuits in Room: Tube Spacing: Required Surface Temp: Required Water Temp: Est. Peak Output: 4.7 46 1 229 15 27 344 m m Load/Loss Summary: Room Design Load: Radiant Load: Baseboard Load: Forced Air Load Other Load: Radiant Back Loss: Recovered Back Loss: Total Heat Loss: 259 W 279 0 0 0 W W W W
C C W
20 W 0 W 279 W
Manifold 2
0.11
34
31
10 (5)
Circuit
Manifold 3
10
0.21
18
38
31
10
Circuit
Total
13
19
0.38
18
38
18
Temperature = C BB = Baseboard
Page 8 of 10
Manifold 2
Circuit A-10 A-11 A-12 A-13 A-14 Total Rooms Served Kotlovnica Kotlovnica Kupatilo Kupatilo Radna soba 2 Total Length 40 39 62 48 81 270 Tube Spacing 229 229 150 150 150 Area Covered 9.0 8.3 9.9 6.6 11.7 45.5 Tubing ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) Flowrate 0.02 0.02 0.02 0.01 0.03 0.11 Head Loss 0 0 1 0 2 2 Temp Drop 10 (5) 10 (5) 10 (5) 10 (5) 10 (4) Load 393 364 470 313 603 2143 Actuator Yes Yes Yes Yes Yes 5
Manifold 3
Circuit A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-18 A-19 Total Rooms Served Dnevni boravak Radna soba 1 Dnevni boravak Dnevni boravak Dnevni boravak Dnevni boravak WC Ulazni hodnik Kuhinja WC vanjski Total Length 68 94 72 71 76 74 18 18 92 46 630 Tube Spacing 150 150/152 150 150 150 150 229 229 150 229 Area Covered 10.0 14.0 9.5 10.5 11.1 11.8 3.6 4.5 10.8 6.1 92.0 Tubing ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) ViegaPEX Barrier 3/4" (Coil) Flowrate 0.02 0.07 0.02 0.02 0.02 0.02 0.02 0.01 0.01 0.01 0.21 Head Loss 1 9 1 1 1 1 0 0 0 0 9 Temp Drop 10 (6) 10 (3) 10 (6) 10 (6) 10 (6) 10 (6) 10 (3) 10 (7) 10 (10) 10 (10) Load 455 796 431 476 504 535 185 256 348 329 4314 Actuator Yes No Yes Yes Yes Yes Yes Yes Yes Yes 9
Temperature = C BB = Baseboard
Page 9 of 10
Disclaimers
With the permission of ASHRAE, portions of the 2009 ASHRAE Handbook Fundamentals are reproduced in this software, including the Climatic Design Conditions data. The program and data are provided "as is" without warranty of any kind either expressed or implied. The entire risk as the quality and performance of the program and data is with you. In no event will ASHRAE be liable to you for any damages, including without limitation any lost profits, lost savings, or other incidental or consequential damages arising out of the use or inability to use this program or the data . 2009 ASHRAE, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. The calculated values shown in this report are based on the data input by the user of the software. Inaccurate or erroneous data input will result in inaccurate or erroneous results. You are strongly advised to review all input data carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application.
IN NO EVENT WILL AVENIR SOFTWARE INC. (AVENIR) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AVENIRS CUMULATIVE LIABILITY FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT.
Temperature = C BB = Baseboard
Page 10 of 10