TRANSMISSION LINE DESIGN

Given: Power = 150 MW, Length = 200 km 1. Circuit Configuration Here, Power Factor (pf) = 0.96 mf limit for 200km line = 2.0

mf limit
3 2.5 mf limit value 2 1.5 1 0.5 0 0 200 400 Line Length (km) 600 800 mf limit

Economic Voltage, Veco =[ Lt - Length of Transmission Line, P - Power to be transmitted, Cos - Power factor, Nc - Number of circuits: 1 - Single Circuit 2- Double Circuit For single circuit configuration i.e. Nc = 1; Veco =[

] ,

] = 187.861 220kV

For double circuit configuration i.e. Nc = 2; Veco =[ ] = 139.772 132kV

Surge Impedance Loading (SIL) =

, V - Economic voltage level

Zc - Line impedance: 400 for single ckt and 200 for double ckt SIL for single ckt =

= 121 = 87.12

SIL for double ckt = mf calculated =

mf calculated for single ckt = mf calculated for double ckt =

= 1.239
= 1.722