[Kumar, 2(8): August, 2013]

ISSN: 2277-9655 Impact Factor: 1.852

IJESRT
INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY

Influence of Reinforced Concrete Shear Wall on Multistorey Buildings


Venkata Sairam Kumar.N*1, Krishna Sai.M.L.N2, Satyanarayana.S.V3 *1,2,3 Department of Civil Engineering, R.V.R & J.C College of Engineering, Guntur,India sairam852@gmail.com Abstract
This work presents the behavior and change in length of shear wall in buildings varied by increasing equal heights from 3.5m to 28m i.e, ground storey (G) to G+7 keeping thickness of shear wall as constant of 250mm and observing the dimension of shear wall in length only. The study was carried by considering both wind and seismic forces for all the zones and soil types as per IS: 1893(part I):2002 and wind loads as per IS: 875(part III):1987. A total of 96 buildings were analyzed for this work using RESIST software. Buildings with symmetrical dimensions (20mx20m), varying wall length and keeping wall thickness as constant (250mm) the effect of shear wall length, wind drift, wind shear, wind moment, seismic drift, seismic shear, and seismic moment, base moment, base shear are studied and results are presented in graphs with height. Keywords: shear wall, wind drift, wind moment, wind shear, seismic shear, seismic moment, seismic drift, wall length, base moment, and base shear.

Introduction : Shear wall are a part of multi storey buildings which resist lateral forces (wind and seismic) in the resisting system of structures. These walls helps in avoiding total collapse of buildings built in regions likely to experience high winds and repeated earthquakes. In the past, shear walls are constructed in reinforced concrete buildings to resist wind forces. From the recent observations, shear walls performance is excellent under seismic forces and are now used extensively for all earthquake resistant designs. Shear walls which are meant to resist earthquake and wind forces shall be designed for ductility. The thickness of shear wall at any part of the structure preferably is not less than 150mm as per IS: 13920:1993. Hence the shear wall length was fixed to 250mm, as in India the wall thickness will be usually 230mm. standards using RESIST software. With change in storey to storey of equal heights the effect of base shear, base moment, wind drift, wind shear, wind moment, seismic drift, seismic shear, seismic moment, wall height are analyzed.

Software Information
RESIST is software developed by NPEEE (National Program on Earthquake Engineering Education) which was distributed by NICEE (National Information Center of Earthquake Engineering). The software was supplied to our college (R.V.R & J.C College of Engineering) under NPEEE an initiative of the ministry of human resource development, Govt of India. RESIST is developed for research and education purpose only.

Design Information Research Work


The present work was done to observe the dimensions of shear wall with increase in storey height and by keeping thickness of shear wall as constant (250mm). The buildings considered are of 20mx20m in area with storey height of 3.5m. Both wind and seismic forces are considered for analysis of shear wall resisting buildings. The buildings were analyzed for all the seismic zones and soil types as per Indian http: // www.ijesrt.com Dimensions and loads: No of storey: G, G+1, G+2, G+3, G+4, G+5, G+6, G+7. Length in X-direction: 20meters. Length in Y-direction: 20meters. Storey height: 3.5meters. Roof height: 1.5meters. Floor weight: Heavy (assuming 150mm slab with 50mm mortar and 25mm floor surfacing) dead load:6.5KPa.

(C) International Journal of Engineering Sciences & Research Technology [2055-2060]

[Kumar, 2(8): August, 2013]

ISSN: 2277-9655 Impact Factor: 1.852


Type of wall: Reinforced concrete shear wall. Load combinations: Wind loads: 1.2G & 1.0Qu & 1.5Wu Earthquake loads: 1.5G & 1.5Eu.

Interior walls: medium (all walls are with brick) Exterior walls: Heavy (assumes 25% glazing and 75% 230mm plastered brick). Roof weight: Heavy (assumes a 200mm deep hollow core reinforced concrete. slab plus topping and light weight screed to allow for drainage 4.8Kpa.). Seismic data input: All the considered buildings are analyzed for all the seismic zones specified as per IS: 1893 (part I): 2002 are: Zone II III IV V Intensity Low Moderate Severe Very severe Zone value 0.10 0.16 0.24 0.36

Results and Discussions


From the results with a gradual increase in height of buildings in all zones and soil types, the wall length also changed linearly. Result analysis is done in terms of percentages in RESIST software i.e. if the result is <=100% then ok, if >100% condition is failure. All the results of Base shear (Fig:1,2,3,4), wall length (Fig: 5), Base moment(Fig:6,7,8,9), wind drift(Fig: 10), wind shear(Fig:11), Wind moment(Fig:12), Seismic drift(Fig:13,14,15,16), Seismic moment(Fig:17,18,19,20), Seismic shear(Fig:21,22,23,24) are shown in graphs in terms of percentages. With increase in height the base shear of medium and soft soils have no change and varied linearly, but for rocky soils there is a slight decrease in base shear after 20mts of building height. The minimum thickness to prevent wall buckling is 204mm for G+7 building was observed. The study helps in understanding the effect of wind and seismic forces on length of shear wall and also the resulting base shear and remaining parameters covered in this paper. Increase in length of shear wall increased the stability of the structure in the considered constructed plane of shear wall of the multistory building.

Importance factor considered is 1.0 used for all the buildings as per IS: 1893 (part I): 2002. Soil type: All the buildings considered are analyzed for the three types of soils, rocky (hard), medium, soft soils as per IS: 1893 (part I): 2002. Wind and terrain information: Wind region: 5 (pink). Basic wind speed: 50m/s. Terrain category: Built up towns. Site shape: Flat. Shear wall details: Wall thickness: 250mm (Kept constant through out this work). Wall length: varied with increase in height with equal increase from storey to storey of 3.5meters. No of walls: 2 walls in X-direction and 2 walls in Y-direction.

Conclusions
This research helps in understanding shear wall consideration for wind and seismic forces and also in considering different parameters which are analyzed and can be used in research and education purposes also.

http: // www.ijesrt.com

(C) International Journal of Engineering Sciences & Research Technology [2055-2060]

[Kumar, 2(8): August, 2013]

ISSN: 2277-9655 Impact Factor: 1.852


Fig: 5 wall length (vs.) Height for all zones.
Height vs Wall Length for all zones
12 Wall length (mts)

Fig: 1 Base shear vs Height for zone V.


Height vs Base shear for Zone v
12000 B ase sh ear (K N ) 10000 8000 6000 4000 2000 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

10 8 6 4 2 0 0 5 10 15 Height (mts) 20 25 30 V IV III II

Fig: 6 Base moment vs Height for zone V


Height vs Base moment for zone V

Fig: 2 Base shear vs Height for zone IV.


Base moment (KNm)

250000 200000 150000 100000 50000 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Height vs Base shear for zone IV


7000 B ase sh ear (K N ) 6000 5000 4000 3000 2000 1000 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Fig: 7 Base moment vs Height for zone IV.


Height vs Base moment for zone IV
160000 140000 120000 100000 80000 60000 40000 20000 0 0 ROCKY MEDIUM SOFT 5 10 15 Height (mts) 20 25 30

Base moment (KNm)

Fig: 3 Base shear vs Height for zone III.


Height vs Base shear for zone III
4500 4000 3500 3000 2500 2000 1500 1000 500 0 0 5 10 15 Height (mts) 20 25 30

ROCKY MEDIUM SOFT

Base shear (KN)

Fig: 8 Base moment vs Height for zone III.


Height vs Base moment for zone III
100000 Base moment (KNm) 80000 60000 40000 20000 0 0 ROCKY MEDIUM SOFT 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Fig: 4 Base shear vs Height for zone II.


Height vs Base shear for zone II
3000 Base shear (KN) 2500 2000 1500 1000 500 0 0 5 10 15 Height (mts) 20 25 30

http: // www.ijesrt.com

(C) International Journal of Engineering Sciences & Research Technology [2055-2060]

[Kumar, 2(8): August, 2013]

ISSN: 2277-9655 Impact Factor: 1.852


Fig: 13 Seismic drift vs Height for zone V.
Height vs Seismic drift for zone v
80 70 60 50 40 30 20 10 0 0 5 10 15 Height (mts) 20 25 30

Fig: 9 Base moment vs Height for zone II.


Height vs Base moment for Zone II
70000 Base moment (KNm) 50000 40000 30000 20000 10000 0 0 5 10 15 Height (mts) 20 25 30

Seismic Drift (%)

60000 ROCKY MEDIUM SOFT

ROCKY MEDIUM SOFT

Fig: 10 Wind drift vs Height for all zones.


Height vs Wind drift for all zones
100 Wind drift (%) 80 V 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 IV III II

Fig: 14 Seismic drift vs Height for zone IV.


Height vs Seismic Drift for zone IV
90 80 70 60 50 40 30 20 10 0 0 5 10 15 Height (mts) 20 25 30

Seismic Drift (%)

ROCKY MEDIUM SOFT

Fig: 11 Wind shear vs Height for all zones.


Height vs Wind shear for all zones
40 35 30 25 20 15 10 5 0 0 5 10 15 Height (mts) 20 25 30

Fig: 15 Seismic drift vs Height for zone III.


Height vs Seismic Drift for zone III
100 Seismic Drift (%) 80 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT V IV III II

Wind Shear (%)

Fig: 12 Wind moment vs Height for all zones.


Height vs Wind moment for all zones
35 Wind Moment (%) 25 20 15 10 5 0 0 5 10 15 Height (mts) 20 25 30 V IV III II Seismic Drift (%) 30

Fig: 16 Seismic drift vs Height for zone II.


Height vs Seismic Drift for zone II
120 100 80 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

http: // www.ijesrt.com

(C) International Journal of Engineering Sciences & Research Technology [2055-2060]

[Kumar, 2(8): August, 2013]

ISSN: 2277-9655 Impact Factor: 1.852


Fig: 21 Seismic shear vs Height for zone V.
Height vs Seismic shear for zone V
120 Seismic Shear (%) 100 80 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Fig: 17 Seismic moment vs Height for zone V.


Height vs Seismic moment for zone V
120 Seismic Moment (%) 100 80 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Fig: 18 Seismic moment vs Height for zone IV.


Height vs Seismic moment for zone IV
120 Seismic moment (%) 100 80 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT Sesismic shear (%)

Fig: 22 Seismic shear vs Height for zone IV.


Height vs Seismic shear for zone IV
90 80 70 60 50 40 30 20 10 0 0 5 10 15 Height (mts) 20 25 30

ROCKY MEDIUM SOFT

Fig: 19 Seismic moment vs Height for zone III.


Height vs Seismic Moment for zone III
100 Seismic moment (%) 80 60 40 20 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT Seismic Shear (%)

Fig: 23 Seismic shear vs Height for zone III.


Height vs Seismic shear for zone III
70 60 50 40 30 20 10 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Fig: 20 Seismic moment vs Height for zone II.


Height vs Seismic Moment for zone II
90 80 70 60 50 40 30 20 10 0 0 5 10 15 Height (mts) 20 25 30

Fig: 24 Seismic shear vs Height for zone II.


Height vs Seismic shear for zone II
50 Seismic Shear (%) 40 30 20 10 0 0 5 10 15 Height (mts) 20 25 30 ROCKY MEDIUM SOFT

Seismic Moment (%)

ROCKY MEDIUM SOFT

Acknowledgement
We thank R.V.R & J.C College of Engineering for providing us RESIST software and also to NPEEE and NICEE for developing this software. http: // www.ijesrt.com (C) International Journal of Engineering Sciences & Research Technology [2055-2060]

[Kumar, 2(8): August, 2013]

ISSN: 2277-9655 Impact Factor: 1.852

References
[1] IS: 1893 (Part 1): 2002, Criteria for earthquake resistant design of structures. BIS, Fifth revision. [2] IS: 13920: 1993, Ductile detailing of reinforced concrete structures subjected to seismic forces-code of practice. [3] Dr.Sudir K Jain, Explanatory examples on Indian seismic code IS 1893 (Part I). [4] Dr.R.K.Ingle, Dr.Sudhir K Jain, Explanatory examples for ductile detailing of RC Buildings. [5] Pankaj Agarwal, Manish Shrikhande, Earthquake resistant design of structures. [6] P.C.Varghese, Advanced reinforced concrete design. [7] Bryan Stafford Smith, Alex Coull, Tall Building Structures Analysis and Design. [8] Victor Gloncu and Federico M.Mazzolani Ductility of seismic resistant steel structures. [9] NPEEE, NICEE, RESIST (INDIA) Users Guide. [10] Khaled M.Heiza, Madgy A. Tayel comparative study on effects of wind and earthquake loads on high rise buildings. Concrete research letters. [11] Abdur Rahman, Saiada Fuadi Fancy, Shamim Ara Bobby Analysis of drift due to wind loads and earthquake loads on tall structures by programming language C. international journal of scientific and engineering research, vol:3, Issue 6, june-2012. [12] Misam Abidi, Mangulkar Madhuri.N. Review on shear wall on soft storey high rise buildings.IJEAT Vol.1, Issue:6, August:2012. [13] Alfa Rasikan, M.G.Rajendran Wind behavior of buildings with and without shear wall. IJERA vol:3, Issue:2, March-April 2013, PP:480-485.