You are on page 1of 2

CIRCUIT BREAKER PARAMETERS The basic technical parameters of the circuit breakers to be supplied are indicated below. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10.

11. 12. 13. 14. 15. 16. 17. Number of poles Class Nominal System Voltage Rated Voltage Rated Insulation Level Rated Frequency Rated normal current Rated Line Charging breaking current Rated Cable Charging breaking current Rated S.C. breaking current First pole to clear factor S.C. making current Rated Operating Sequence Duration of short circuit Rated out of phase breaking current Automatic rapid re closing Total break time for any current up to the rated breaking current with limiting conditions of operating coil voltage, operating &quenching media pressures. No. of auxiliary contacts for purchasers use System neutral earthing Closing time(max.) Opening time(max.) Trip & Closing coil Voltage Arcing time Creepage distance (min.) 1.2/50 micro sec. lightning impulse withstand voltage. to earth across the open circuit voltage applied to one terminal Power frequency withstand voltage to earth across terminals of open circuit breaker Type of operation 3 Out Door Type 220 kV 245 kV 1050 kV(peak) 50 Hz 3150 Amps. 125 Amps. 250 Amps 40 kA 1.3 100 kA O-0.3sec-CO-3min.-CO 1 sec. 7.9 kA 1 Ph & 3 Ph < 60 ms

18. 19. 20. 21. 22. 23. 24.

10 NO & 10 NC on each pole Effectively earthed <150 ms <30 ms 220 V+/-10% DC <=25 micro sec. 6125 mm

1050 kV(peak) 1050 kV(peak)

25.

460 kV (rms) 460 kV (rms) Spring/spring

26.

27.

28.

29. 30.

Rated values of transient recovery voltage for terminal faults Rated values of transient recovery voltage for short line faults Rated characteristics for out of phase breaking current Small inductive current interrupting capacity Rated terminal load Difference in the instants of closing/opening of contacts at rated voltage and rated operating and quenching media pressure. with in a pole between poles Insulation level of bushings 1 min. p.f. withstand voltage 1.2 X 50 micro sec lightning impulse with standing voltage Partial discharge level Controls of switching surges Noise level of equipment Auxiliary power supply

As per IEC:62271 - 100

As per IEC:62271 - 100

As per IEC:62271 - 100 Any value from 0.5-10 Amps. Without switching over voltage exceeding 2.5 p.u. 100 Kg static

31. 32.

< 5 ms < 10 ms 460 kV(rms) 1050 kV(peak) As per IEC:62271 - 100 The switching surge voltage while energising to be limited to 2.3p. u. < 140 dB 415V+/-10%,3ph,50Hz+/-5%,AC 240V+/-10%,1ph,50Hz+/-5%,AC 250V +/-10% DC

33.

34. 35. 36. 37.

You might also like