Line-to-Neutral Volts (Vn) 230 Volts

Line 1 Calculated Load (A1) 50 Amp


Line 2 Calculated Load (A2) 60 Amp
Line 3 Calculated Load (A3) 60 Amp
Service Neutral Impedance Z1 0.1
Ground Resistance (3-point method) R 100
Neutral/Ground Parallel Resistance 0.10
Line 1 Resistance 4.600
Line 2 Resistance 3.83
Line 3 Resistance 3.83
Line 1 - Actual Load 49.58 Amp
Line 1 Watts 11307.72 Watts
Line 1 - Loads Operates at Volts 228.07 Volts
Line 2 - Actual Load 59.74 Amp
Line 2 Watts 13678.53 Watts
Line 2 - Loads Operates at Volts 228.99 Volts
Line 3 - Actual Load 59.74 Amp
Line 3 Watts 13678.53 Watts
Line 3 - Loads Operates at Volts 228.99 Volts
Parallel Neutral/Ground Path 69.89 Amp
Neutral Watts 487.98 Watt
Neutral Current 69.82 Amp
Ground Current 0.07 Amp
Touch Voltage from Metal Parts to Earth 6.98 Volts
RESULTS
Single Phase System Three Phase System
TOUCH VOLTAGE & GROUND CURRENT CALCULATION
DOW RESTRICTED - For internal use only
Circuit Voltage 230 Volts
Circuit Ampere 16 Amp
Load Resistance 14.38
Ground Resistance 1
Electrode Resistance 25
Body Resistance 1000
Total Resistance 38.77
Total Current 5.93 Amp
Load Voltage Drop 85.29 Volts
Ground/Body Voltage Drop 144.71 Volts
Body Resistance 1000.00
Body Current 144.71 mA
Circuit Current 14.96 Amp
RESULTS
Single Phase System
Jignesh.Parmar
www.electricalnotes.wordpress.com
jiguparmar@yahoo.com
DOW RESTRICTED - For internal use only
DOW RESTRICTED - For internal use only
DOW RESTRICTED - For internal use only