Professional Documents
Culture Documents
\
|
=
L
TP
L fc
P
P
The predictions of this equation have been compared with a large data base of measured
heat transfer coefficients during upward flow boiling within circular tubes. The data are
well correlated.
This equation has been used to determine how much heat can be added through the
internal exchanger.
The principle problem that has been identified is that under many circumstances the
liquid Reynolds Number falls in the laminar flow region. This places uncertainty on the
validity of the calculation.
However, it has also led to the identification of two potential improvements in the
exchanger design. These are the provision of a liquid recycle and the use of tube inserts
to promote heat transfer within the exchanger.
Linking Column Design, Exchanger Design and Integration
The vapor flow thru the column is set by the column duty.
The maximum cross section of the heat exchanger is dependent on the area taken up by
the down-comers. This cross section can be related to the number of tubes installed in the
heat exchanger allowing calculation of the minimum mass flux of vapor flowing through
an exchanger handling the specified column duty. Higher mass fluxes are obtained by
reducing the number of tubes in the exchanger.
The mass flux of liquid flowing through the exchanger can be set independently by
adjusting the positioning of recycle vanes installed in the liquid down-comer.
So, it is possible (using a quite simple spreadsheet) to determine the heat transfer
coefficient achieved in the heat exchanger for different combinations of vapor and liquid
mass fluxes. The homogeneous pressure drop model will then allow calculation of
minimum tube length for the heat exchanger.
Knowing the overall heat transfer coefficient for the heat exchanger the heat load
obtained for a given temperature difference between the column and the fluid with which
it is integrated.
Case Study: Methanol-Water Separation
An overview of column integration is provided in Appendix 1.
The first step in the analysis is an evaluation of exchanger performance as a function of
vapor and liquid mass flex through the unit. This is presented in Table 2.
It is found that the vapor mass flux should be at least 50 kg/m
2
she higher the liquid mass
flux the higher is the quantity of heat that can be transferred through the tubes.
The exchanger has a square face and the tube length equates with the plate spacing. The
use of a square face provides space for the provision of liquid recycle lanes.
The column diameter is assumed to be 1 metre. The vapor mass flux within the column is
assumed to be 1.8 kg/m
2
. Therefore, to obtain the vapor mass flux necessary for efficient
heat transfer in the exchanger the exchanger dimensions need to be 0.25 m x 0.25 m x 0.9
m (yielding a vapor mass flux of 57.3 kg/m
2
s).
The next step is examination of Table 2 to determine the heat duty that can be obtained as
a function of liquid mass flux.
mass flux mass flow mass flux x rho-tp vis-tp Re-L f-L Re-tp f-tp dP-tp dP-L multiplier Nu h-l htc Q/dT
vapour liquid per tube
23 0.001463 50 0.315068 3.858492905 3.25541E-05 933.9975 0.017131 20181.82 0.006628 1830.8174 11.45098 9.81095 3.7 77.7 762.3108 19.40096
50 0.003181 100 0.333333 3.648099781 3.09375E-05 1818.182 0.0088 43636.36 0.005466 6742.3417 23.52941 12.75674 3.7 77.7 991.1991 25.22621
50 0.003181 200 0.2 6.060461162 4.85294E-05 4363.636 0.00972 46363.64 0.005384 11104.194 103.9569 8.182484 42.57413 894.0568 7315.605 186.1836
50 0.003181 400 0.111111 10.83857686 7.81579E-05 9696.97 0.007961 51818.18 0.005236 19565.426 340.5779 6.189745 80.64469 1693.539 10482.57 266.7836
100 0.006362 100 0.5 2.436026801 2.12903E-05 1363.636 0.011733 84545.45 0.004633 15214.667 31.37255 16.16481 3.7 77.7 1256.006 31.9656
100 0.006362 200 0.333333 3.648099781 3.09375E-05 3636.364 0.010173 87272.73 0.004596 22678.444 108.805 11.05437 36.79602 772.7164 8541.894 217.3929
100 0.006362 400 0.2 6.060461162 4.85294E-05 8727.273 0.008173 92727.27 0.004527 37349.909 349.668 8.182484 74.12587 1556.643 12737.21 324.1645
100 0.006362 800 0.111111 10.83857686 7.81579E-05 19393.94 0.006694 103636.4 0.004403 65809.987 1145.563 6.189745 140.4106 2948.622 18251.22 464.4972
50 0.003181 200 0.2 6.060461162 4.85294E-05 4363.636 0.00972 46363.64 0.005384 11104.194 103.9569 8.182484 42.57413 894.0568 7315.605 186.1836
50 0.003181 400 0.111111 10.83857686 7.81579E-05 9696.97 0.007961 51818.18 0.005236 19565.426 340.5779 6.189745 80.64469 1693.539 10482.57 266.7836
50 0.003181 800 0.058824 20.21252866 0.000121957 20534.76 0.006599 62727.27 0.004992 35687.012 1129.31 4.730028 146.9801 3086.583 14599.62 371.5633
50 0.003181 1200 0.04 29.3510704 0.000152778 31418.18 0.005934 73636.36 0.004796 51059.915 2284.666 4.047304 206.5436 4337.416 17554.84 446.7742
Table 2. Exchanger Performance
The results of these calculations are given in Table 3.
Liq. Mass Flux dQ/dT Exchanger dx/dT
Each tube Duty MW
It is concluded that given a heat source that is 10 degrees greater than local column
temperature 0.9 MW of heat can be exchanged. 32% of recycled liquid would be
vaporised.
The final stage of the design would be the identification and validation of the integration
options (see Appendix 1).
Conclusions
The concept of an integrated internal heat exchanger that takes position previously
occupied by distillation plates has been demonstrated using a simple apparatus.
It has been found that the hydraulic behavior of such an exchanger is well modeled by a
homogeneous flow model.
There is significant scope to improve the heat transfer performance of such exchangers
by installing tube inserts.
The flexibility of such exchangers can be improved by installing vanes in the liquid
down-comers in order to provide liquid recycle and increased liquid flow through the
exchanger.
A procedure that allows the engineer to link column duty, heat exchanger design and
process integration opportunity has been developed.
REFERENCES
[1] S. Bandyopadhyay, Thermal Integration of a Distillation Column Through Side-Exchangers, Chemical
Engineering Research and Design, Vol. 85, No.1, 2007, pp. 155-166.
[2] M.Nakaiwa, K.Huang, A.Endo,T.Ohmori,T.Takamatsu, Internally heat integrated columns: A
review, ChERD, 81, 162-177, 2003
[3] G.T.Polley, Heat Exchanger Design and Process Integration, The Chemical Engineer, 8 April 1993
[4] J. C. Chen Correlations for boiling heat transfer to saturated fluids in convective flow, Ind. Eng. Chem.
Process Design Development, Vol. 5, no. 3 (1966) pp. 322-329
[5] E.E. Vzquez Ramrez, G.T Polley , J.M. Riesco Avila Engineering equations for the estimation of
heat transfer in pool boiling and flow boiling during upward flow in tubes, AMIDIQ XXX, (2009),
Mxico.
Appendix 1
Integration of Simple Columns
The scope for integrating a single simple distillation column into a process is easily
identified by superimposing the temperature/heat load lines representing the column
reboiler and condenser on the Grand Composite Curve for the background process
(example given in Figure 1).
Figure 1. Integration of Simple Column
This lines can be considered to make up a block. If the block fits well, integration is
straight forward. A column positioned above the Pinch would usually be driven by hot
utility and the heat released in the condenser used for other process heating duties. The
column could be controlled using the boil-up rate.
A column positioned below the Pinch would usually be driven by heat from the process
with the heat given up in the condenser being absorbed by cold utility. The column could
be controlled using the reflux.
On occasions, the block may fit partially (on rare occasions totally) into a pocket
(Figure 2) in the Grand Composite Curve. In the example shown, the column would be
partially driven by heat recovery and partially driven by hot utility. The heat released
through the condenser would be recovered within the process. Such an arrangement could
Ti
H
provide control and operability challenges. These would have to be examined and an
acceptable control strategy identified before the integration scheme could be accepted.
Figure 2. Integration into a Pocket
Improving Integration
It is sometimes found that a simple column does not easily fit into the Grand Composite
Curve. For instance, consider the situation illustrated in Figure 3.
Here a heat process demand positioned at a temperature level intermediate between the
column re-boiler and the condenser is restricting the ability of the process to absorb the
full condenser heat load.
In this situation the designer has a number of options. The choice may be to only re-
absorb part of the column heat duty (i.e. accept the energy penalty). Alternatively, the
designer may seek to develop a process modification (e.g. raise the column pressure and
hence the temperature at which the condenser operates, or modify the background
process in order to remove the restriction placed upon heat recovery from the column).
Another option would be to introduce an intermediate condenser such that some of the
column heat is rejected at a higher temperature level than the main overhead condenser
(Figure 4).
The scope for identifying the possibility of using an intermediate condenser (or, re-boiler)
cannot be determined through arbitrarily drawing lines to form new blocks representing
the distillation column. An examination of the thermodynamics of the distillation process
is required.
Figure 3. Process Restricts Column Integration
Ti
Figure 4. Use of Intermediate Condenser?
Distillation Column Thermodynamics
The thermodynamics of the distillation process have been appreciated for many years
(see, for example, Benedict [1947]). A good description has been given by Flower &
Jackson [1964].
An appreciation can be gained by first considering the concept of minimum reflux ratio.
Using a McCabe-Thiele plot, this can be determined from the slope of line connecting the
required overhead composition to a point at which the feed q-line cuts the equilibrium
line (or, if this point cannot be reached without cutting the equilibrium line, a line from
this point tangential to the equilibrium line). This is the limiting operating line for the
rectification section.
Figure 5. Minimum Reflux for Separation
The operating line of minimum reflux is illustrated in Figure 5. As the rectification takes
place the concentration of more volatile component in both liquid and vapour phases
H
Rectification
x
y
A
B
increase. The distillation process moves up the equilibrium line. The amount of reflux
required to complete the separation therefore changes. For the equilibrium line illustrated,
it is observed that the minimum reflux required to complete the separation falls as the
rectification process continues (moving up the curve from line A to line B. to line C etc.).
Consequently, not all of the heat that needs to be removed from the column has to
extracted through the top condenser (which otherwise provides the full reflux down the
column). Some heat can be extracted via an intermediate condenser. The quantity of heat
that can be extracted in this way can be determined (as a function of temperature) from
the differences in minimum reflux ratio.
A similar analysis can be conducted for the stripping section of the column. The
minimum boil-up required for a separation can be determined from the slope of a line
joining the required bottom concentration with the point at which the feed q-line cuts the
equilibrium line (Figure 6). It is found that some heat can be provided through the re-
boiler positioned part way up the column (using an intermediate re-boiler). Possible
intermediate load against temperature level can be determined in a manner similar to that
use for intermediate condensers.
Lecture 1 Slide 16
x
y
Boil-up required to
complete the
separation easily
determined
Heat can be added at
Intermediate temperatures
McCabe-Thiele Diagram
Required Base Condition
Figure 6. Column Boil-up Requirements
The Q-Curve
Flowers & Jackson proposed that the heat rejection profile for the rectification part of the
column and the heat absorption profile for the stripping section be brought together to
form a single curve, that they named the Q curve.
They showed that for the rectification the quantity by which the heat rejection from the
column between the feed plate and the top condenser exceeds that needed to condense
the top product is given by:
where:
For the stripping section the quantity of heat that must be added to the column between
the feed plate and a local point is given by:
The Q Curve is a plot of excess against local temperature. It can be used to identify how
heat can be added and rejected at different temperature levels. A typical example is
shown in Figure 7.
Q D
x x
x x
h
D
v
=
|
\
|
.
|
*
*
D molal fowrate of top product
x concentration of top product
x local liquid concentration
x local equilibrium concentration
h molal heat of vaporisation
D
v
=
=
=
=
=
. . . .
. . .
. .
. .
. . .
*
Q B
x x
x x
h
B
v
=
|
\
|
.
|
| *
Figure 7. Q Curve
Development of T-Q Plot from Column Simulation Results
The McCabe-Thiele construction is based on the assumption that the molal latent heat
does not vary with composition. For many systems that is not a good approximation.
For these systems the Q-curve is better developed using the Enthalpy-Concentration
Diagram for the separation. The construction (developed by Flower & Jackson) for the
rectification section is shown in Figure 8. That for the stripping section is shown in
Figure 9.
T
Stripping
Section
Rectification
Feed
Q
Figure 8. Rectification: Excess Heat Profile
For the rectification section, the following equation gives the excess heat profile:
For the stripping section the excess heat can be calculated from:
Prior to the development of distillation column simulators and physical property
packages, this more accurate approach was limited by lack of Enthalpy-Concentration
Diagrams. Now, as discussed by Dhole [1991], the information required for the solution
of these equations is to be found in the standard output from commercial process
simulators.
( )
Q D H H H
x x
x x
H h
L v L
D
c vD
= +
|
\
|
.
|
|
\
|
.
|
*
*
[ ] [ ] [ ]
Q B H H H H
x x
x x
H H
x x
x x
v vF v L vF Lf
f B
f f
B
=
(
(
+
(
(
{ }
* * *
*
*
*
*
*
Tie
Line
x
*
x x
D
H
L
H
v
*
Q
Figure 9. Heat Input Through Stripping Section
Most significantly, Dhole has further suggested that, as a first approximation, the analysis
can be extended to cover multi-component as well as binary separations. All that is
needed is a converged column simulation.
Dhole also pointed out that in addition to the Q curve, a curve relating heat requirements
to plate position can be directly derived for the converged simulation.
Interpretation of Q Curve
The Q curve (also known as the Column Grand Composite Curve, CGCC) indicates how
heat can be added and extracted from the column at intermediate points. Columns have to
operate at reflux ratios above the minimum value in order to complete the separation with
a finite number of trays. Typically economic reflux ratios fall in the range 1.05 to 1.25
times the minimum value. Consequently a heat content block for a distillation column
would consist of the heat load associated with the excess reflux plus the Q
curve profile.
In the case shown in Figure 10 a single re-boiler at the base of the column (Figure 10a)
could be used. Alternatively, re-boiler at the base and a number of intermediate re-boilers
(Figure 10b) could be used. Since, the satisfaction of overall heat requirements using the
intermediate addition of heat effects the internal reflux ratio, the use of intermediate re-
Feed Tie
x
*
x
H
L
H
v f
*
Local
Tie Line
H
L f
H
v
*
Q
x
f
x
vf
*
boilers increases the number of plates required within the column. The effect upon
column size and cost needs to be determined before a decision to use intermediate units is
taken.
The Q Curve also provides us with guidance on how the column feed can be conditioned.
If the curve shows a sharp increase in enthalpy immediately below the feed plate
(decreasing temperature), cooling of the feed could be beneficial (Figure 11). So, in an
integrated plant context, the feed to the column could be a valuable heat source.
If the curve shows a marked increase in enthalpy immediately above the feed plate
(Figure 12), partial or complete vaporization of a saturated feed would result in reduced
re-boiler load. In an integrated context the feed stream would be treated as a heat sink in
the overall process.
Vaporization of the feed changes the temperature at which it enters the column. A
different thermodynamic profile exists and a new Q Curve should be developed (Figure
13).
T
H
Reboiler
Figure 10a. The Use of a Single Reboiler
T
H
Figure 10b. The use of multiple reboilers
T
H
Feed
Location
Scope for
feed cooling
Figure 11. Profile Indicating feed cooling
The Q Curve is particularly useful in identifying where heat pumping across the feed
plate is an option (see Figure 14).
T
H
Figure 13. CGCC with feed vaporisat ion.
Saturated Feed
Vaporised Feed
T
H
Figure 12. Profile indicating that feed pre-
heating would be advantageous
Benedict M. Multi-stage Separation Processes, Trans.A.I.Chem.E. 1947, 43(2), 41-60
Flower J.R. & Jackson R. Energy requirements in the separation of mixtures by
distillation, Trans.I.Chem.E. 1964, 42,249-258
Dhole V.R. Ph.D.Thesis, UMIST, 1991
Dhole V.R. & Linnhoff B. Distillation Column Targets, Paper presented at ESCAPE-1
Conf., Denmark, May 1992
Rajah W. & Polley G.T. Synthesis of Practical Distillation Schemes, ChERD, 73A,953-
966, 1995
T
H
Intermediate
Condenser
Intermediate
Reboiler
Heat Pump
Figure 14. Application of Heat Pump