Auditor:
1
Electrical Audit Report for Archive Base
Date of Audit
Date of Report
7th December
2009
2
Electrical Audit Report for Archive Base
Contents
Table of Contents
Electrical System block diagram.................................................................................5
Generator Set..............................................................................................................13
Comments.................................................................................................................13
3
Electrical Audit Report for Archive Base
Earthing System.........................................................................................................16
Comments.................................................................................................................16
Lightning Arrestor.....................................................................................................16
Comments.................................................................................................................16
NO Load Reading.......................................................................................................18
ON Load Reading.....................................................................................................18
4
Electrical Audit Report for Archive Base
GEN NEPA
37KVA SUPPLY
4c x 25mm2 PVC/SWA/PVC
4c x 25mm2 PVC/SWA/PVC
250 A 250 A
MCCB MCCB
CHANGE OVER
BREAKER PANEL
MEM- 200A
BUS BAR PANEL TO EXTERNAL
STREET LIGHT
CHANGING
100A ROOM 100A 100A
FEDERAL FEDERAL FEDERAL
ELECTRIC ELECTRIC ELECTRIC
DB DB DB
5
Electrical Audit Report for Archive Base
CONSUMERS
COMMENTS
ELCB is not installed in DB. In case any consumer gets earthed, there is no
protection.
There is only a two phase supply on DB instead of three phases.
There is very poor illumination in the hall as only three light fittings are
working. The total number of installed fittings are 16.
o As no voltage drop was noticed, the reason for not working of these
fittings is either
Defective wiring and/or
Fittings are defective (Ballast, starter tube)
o This needs to be checked urgently.
urgently.
6
Electrical Audit Report for Archive Base
CONSUMERS
COMMENTS
7
Electrical Audit Report for Archive Base
CONSUMERS
AC Split Units - 6 (1.5HP,PANASONIC)
Louver fittings - 16 (4X16W)
COMMENTS
8
Electrical Audit Report for Archive Base
CONSUMERS
Refrigerator - 1
Micro wave oven - 1
Water Dispenser - 1
Electric kettle - 2
COMMENTS
The ring wired circuit of single 13Amps socket outlet supplies power to
o Refrigerator
o Microwave oven
o Water dispenser
o Electric Kettle.
The power cable between 13A SSO to consumer is sagging.
All bulbs were found to be fused.
No earth leakage protection equipment is mounted in the incoming DB.
There is only two phase incoming supply at DB Isolator, tapped from first floor
main hall DB isolator, instead of a three phase supply from bus bar panel.
No legend of DB wiring.
Size of DB and Isolator is high.
9
Electrical Audit Report for Archive Base
CONSUMERS
COMMENT
Three phase power is tapped from Isolator incoming for another DB.
Also three phase power is tapped for supplying power to Air conditioning units
No earth leakage current protection system is installed.
Only one split AC is working while second one’s compressor is not functional.
Light illumination level is low as most of fittings are non-functional. It needs
wiring and fitting to be checked and fixed.
There is no emergency light installed.
10
Electrical Audit Report for Archive Base
COMMENTS
DB incoming supply is tapped from second floor main hall DB Isolator’s
incoming.
No ELCB is installed in DB to protect the system from earth leakage current.
Isolators and MCB are oversized.
In general illumination level is low.
low.
11
Electrical Audit Report for Archive Base
EXTERNAL ELECTRICALS
STATISTICS
No of fittings - 15 (400w)
Broken glass - 1
Broken fitting - 1
COMMENTS
The perimeter lights are all in one circuit (radial), terminated to a 32Amps
gear switch.MEM Gear Switch is mounted on the fence behind the main
building.
The fittings are looped with a 2.5 mm2 PVC/SWA/PVC cable and they are
terminated with 3c x 1.5mm2 industrial flexible cords.
The poles are not earthed.
earthed.
Termination at the JB is not neatly done.
done.
Some of the 6” x 6” boxes used to conceal the connections between loops
and fitting rid connectors are not earthed, not covered and are not made in
screw.
Some of the fittings are dirty and have debris inside.
Some of the fittings mounted on the security posts are unearthed and cables
are flying around the post, not concealed.
33KV NEPA lines are passing through the base yard. The overhead line is
recommended to be replaced with underground XLPE cable.
One perimeter fitting is broken in pieces and is hanging behind the diesel
tank.
Junction boxes appear to be IP55 but water was seen inside.
There is no terminal strip inside the junction boxes. Wires are directly joined
using pliers.
No PVC gland is used; therefore, the possibility of water, dust and insects
entering the region is high.
Galvanized 20mm conduit is recommended in place of existing plastic PVC
conduit pipe.
External wall mounted bulkhead fittings (2) are hanging. It is IP41, while it
should be IP55.
12
Electrical Audit Report for Archive Base
GENERATOR SET
[37KVA, DUEZ MAKE, AIR COOLED]
COMMENTS
13
Electrical Audit Report for Archive Base
COMMENTS
There are two 250 Amps 3pole breakers installed inside the 100Amps BILL
changeover panel. One is connected to the Genset while the second breaker
is connected to PHCN 16 mm2 1C AL cables. There is NO interlock
(Mechanical or Electrical).In
Electrical).In case both the breakers are ON at the same
time, it might cause serious problems.
14
Electrical Audit Report for Archive Base
COMMENTS
Top cover is open and cables from gear switch to bus bar panel are not well
connected.
Cable wire color code is not correct. Black wire is used for Y phase and the
same color is used for Neutral also.
COMMENTS
15
Electrical Audit Report for Archive Base
EARTHING SYSTEM
COMMENTS
Earthing pit and earthing chamber could not be located therefore earth
resistance could not be measured.
None of the electrical panels like DBs, Gear Switches, Bus bar panel, Genset
body are properly earthed.
LIGHTENING ARRESTOR
COMMENTS
16
Electrical Audit Report for Archive Base
COMMENTS
It has been observed that there is frequent power failure as PHCN power is
disconnected for the last two months and the Genset remains under
breakdown very frequently. Last month there was no power for more than two
weeks. Under such a situation the fire alarm system will be nonfunctional as
its UPS could last only half an hour. In case of a fire, the system will fail and
there would be serious consequences.
17
Electrical Audit Report for Archive Base
NO LOAD READING
ON LOAD READING
18
Electrical Audit Report for Archive Base
Status
Yes No
Has portable electrical equipment including extension leads and power boards
been tested and tagged in accordance with the Guideline for Testing of Portable N/A
Electrical Equipment?
Have ELCB’s been checked to ensure they are working correctly? N/A
Have all people been trained in the use of all equipment? N/A
19
Electrical Audit Report for Archive Base
Are training records kept for the safe use of all equipment? N/A
Has earth resistance of all earth chambers measured and maintained below the
limit? N/A
Are out of service tags for faulty equipment available and used? N
20
Electrical Audit Report for Archive Base
Completion Complete
Location Issue/ Hazard Proposed Action Responsibility
Date d Y/N
GF - Main hall Illumination is very low as 13 out Electrical wiring and/or fittings must be
of 16 fittings are not working checked and fixed ASAP SLB - -
21
Electrical Audit Report for Archive Base
GF and FF Only two phase power is Connect three phase supply SLB - -
DBs connected
GF and FF Incoming supply is tapped from Connect power from Bus Bar Panel SLB - -
front DBs Main hall’s respective DBs
200Amps Panel top is open and one live Fix the problem by covering top and use
Gear Switch cable and N-cables are black red cable for live line SLB - -
color
22
Electrical Audit Report for Archive Base
23
Electrical Audit Report for Archive Base
24