Professional Documents
Culture Documents
Load data:
Calculation
model:
Optimization:
Valuation initial
network:
Selection, if the load flow results are shown only for the
normal network operation or also for the (N-1)-security check
are shown. If at least 1 (N-1)-optimization is selected, the
(N-1)-security check results are shown.
Results:
The user defined voltage limits appear and can be changed if the menu option
"Calculation - Load Flow - Reference Voltages..." is selected. In this calculation
module only the limits of node voltages of the considered voltage level (medium
voltage level) are used. The procedure chooses for the calculation and the
7-1
graphical results from the user defined limits and from the predetermined norm
the stricter rules. The user defined limits have the default values 95% and 105%.
Graphical Results
The graphical results window appears after having selected "Calculation -Optimal
Distribution Network - Chart...". The value to be shown can be selected with the
menu option "Results". Only results of the considered voltage level are shown.
Chart Parameters
The parameter window appears after having selected "Chart - Parameters...".
Select nodes /
elements:
Title:
Default title:
Grid:
Black/white:
Ymin:
Ymax:
Show names:
Show node
names:
7-2
Chart Representation
Node Voltages
The fat bars show the value ranges of node voltages for the normal network
operation. The overlying thin bars show the value ranges of the (N-1)-security
check. The results of the (N-1)-security check are only shown if the calculation
parameter "N-1 calculation" in "Valuation initial network" is selected or if at least
one (N-1)-calculation was performed.
Line Currents, Element Loadings
The results of the normal operation case and of the (N-1)-security check
(maximum line currents/ maximum element loadings) are represented as parallel
bars. The results of the (N-1)-security check are only shown if the calculation
parameter "N-1 calculation" in "Valuation initial network" is selected or if at least
one (N-1)-calculation was performed.
Voltage Limits
The voltage limits in the normal operation case are shown as dashed lines. The
voltage limits in the exceptional case (N-1-security check) are shown as plain
lines.
Text Results
Text File
The calculated optimal values are listed in a text file if the load flow parameter
"Text file" is selected ("Calculation - Load Flow - Parameters..."). The text file is
shown after having selected the menu option "Results - List - Last Calculation...".
It can also be opened by an external text editor.
Result File
The extreme values of the node voltages and the element loadings are listed in a
result file if the load flow parameter "Result file" is selected ("Calculation - Load
Flow - Parameters..."). The result file can be used by external programs (e.g. MSExcel).
7-3
Error File
Comments and error messages are listed in the error file. It is always shown if the
load flow parameter "Iteration caracteristics" is selected ("Calculation - Load Flow
- Parameters... - Iteration Data...")
Theory
The module Optimal Distribution Network optimizes the operation of distribution
networks regarding different objective functions. Distribution networks have
usually meshes but they are radially operated. In the normal operation case
network losses can be minimized selecting optimal separation points. In case of
element failures some portion of the system may be out of service and can be
resupplied by changing the separation points. Dispersed generators may feed
energy into the distribution system. The HV/MV-transformers usually have voltage
control with possibly active compounding. The MV/LV-transformers have no
voltage control, but their taps can be changed by hand mostly.
7-4
Optimization
The four optimization procedures are performed in the predetermined order and
independently of each other. The calculated optimal values of the preceding
optimization procedure are taken on.
Optimal Separation Points
Network losses of the high load case are minimized applying the optimal
separation points procedure in accordance with chapter "Optimal Separation
Points".
Compounding
The goal is to aligne the value ranges of the MV-nodes reducing the big ones and
increasing the small ones. The procedure changes iteratively the compounding
data of the HV/MV-transformers if their voltage control and their compounding are
active. The predetermined values Umin and Umax remain constant and the
values Imin and Imax are changed. The smaller the range between Umin and
Umax is, the lower is the influence of the compounding on the node voltages.
Cosphi-Values of Cosphi-Controlled Generators
The control input "Cosphi oper" of cosphi-controlled generators with type "Cosphi
constant" is changed. The goal is to find feasible values as close as possible to 1
in order to minimize network losses. If the voltage range of the corresponding
node amounts more than 80% of the range between the upper an lower voltage
limit, the cosphi-value is changed so that the generator consumes inductive
reactive power. "Cosphi oper" must not leave the feasible domain defined by
"Cosphi lim1" and "Cosphi lim2".
Transformer Nominal Voltages
The goal is to set the nominal voltages of the voltage controlled HV/MVtransformers as high as possible, in order to minimize network losses. The node
voltage limits are considered. If the calculation parameter "opt. MV/LV-trans. tap"
is active, the taps of the MV/LV-transformers are changed too. The procedure
proceeds iteratively. It is only successful if the HV/MV-transformers have a
sufficiently big number of tap steps and a sufficiently big magnitude of the
additional voltage per tap step.
Voltage Limits
On the low voltage level voltages must be within the limits +6% and -10% in the
case of normal operation and +6% and -15% in the exceptional case. These limits
are converted to the medium voltage level under consideration of the voltage drop
in the low voltage network (5%) and over the MV/LV-transformer. This yields the
NEPLAN User's Guide V5
7-5
allowed voltage range of each MV-node. The procedure chooses for the
calculation and the graphical results from the user defined limits and from the
predetermined norm the stricter rules. The user defined limits have the default
values 95% and 105%.
The voltage limits are always shown in the graphical result window. However, they
are only considered by the last optimization procedure (transformer nominal
voltages).
7-6