713MN
713MN
M713GB/9911
Index:
Page
Flow Converter 713
Technical section
Triangular Weir
Parshall Flumes
Venturi flumes
Mounting of Sensor
Electrical Connection
Control
Function keys
Flow key
Summation key
Alarm key
Sample key
10
10
10
11
12
Menu key
12
Configuring
13
Specifications
16
Order numbers
16
Dimensions
16
Functional indications
17
18
19
CE - CERTIFICATE OF CONFORMITY
This product complies with the requirements concerning
electromagnetic compatibility (EMC) stipulated in Council directive no.
89/336/EEC of 3rd May 1989, altered at directive no. 92/31/EEC, on
the approximation of the laws of the Member States relating to
electromagnetic compatibility.
MJK Automation A/S declare that the product complies to the values
stipulated in EN 50081-1 and EN 50082-1.
where:Q =
b =
be =
be =
ha =
he =
he =
hb =
B =
L =
ha
hb
For determination of Ce
b/B = 1,0
Ce = 0,602+0,075 ha/hb
b/B = 0,9
Ce = 0,598+0,064 ha/hb
b/B = 0,8
Ce = 0,596+0,045 ha/hb
b/B = 0,7
Ce = 0,594+0,030 ha/hb
b/B = 0,6
Ce = 0,593+0,018 ha/hb
b/B = 0,4
Ce = 0,591+0,0058 ha/hb
b/B = 0,2
Ce = 0,588-0,0018 ha/hb
b/B = 0
Ce = 0,587-0,0023 ha/hb
Edge
= minimum 45
d ~ 1-2 mm
3
0,8
Ce
1,0
0,78
0,76
0,9
0,74
0,72
0,8
0,7
0,68
0,7
0,66
0,6
0,64
0,62
0,4
0,6
0,2
0,58
0,0
ha/hb
0,56
1
11 13 15 17 19 21 23 25
Triangular weir
according to ISO 1438
ha
hb
=
d =
ha =
hb =
B =
L =
minimum 45
1-2 mm
height in [m]
depth below edge in [m]
flumewidth in [m]
distance to sensor,
4 to 5 ha max.
ha
hb
Formula: (Kindsvater-Shen).
where:Q =
ha =
he =
he =
g =
=
height
depth below edge in [m]
flume width in [m]
distance to sensor,
4 til 5 ha max.
4
flow in m3/h
height in [m]
the effective height in [m]
ha + kh, kh = 0,001
acc. due to gravity = 9,81 m/s2
aperture angle
Q = k han
hvor:
Q = flow in m3/h
b = width in the measuring flume in[ m]
h a = water level before the narrowing in [m]
h b = water level in the narrowing in [m]
L = distance to the sensor (use table below)
0,005
0,004
0,003
0,002
0,001
b
1"
2"
3"
6"
9"
12"
24"
36"
k
217
425
630
1310
1851
2407
5142
7863
n
1,548
1,548
1,548
1,574
1,528
1,519
1,55
1,566
L
0,24
0,27
0,30
0,41
0,58
0,89
0,99
1,09
h [m] 1
3"
12"
36"
6" 9"
24"
1" 2"
Parshall flume
The most common type of flume is the Parshall flume.
The Parshall flume is a standardized Venturi flume.
0,1
b
0,01
1
10
100
1000
10000
Q [m/h]
ha
hb
At free flow, only the level ha is measured. The location
of the sensor is important and must be carried out as
illustrated in the drawing and the table in the next
column. It is important to have a laminar flow
(horizontal streaming calm water with no whirls) at the
out- and inlet from the flume. Upstream the measuring
flume, must extend at least ten times the width of the
inlet section of the flume. On the outlet side the only
demand is that the water should run freely. This is the
case when hb 0,7 ha.
where:
ha = water level before the narrowing
L = DN (the nominal diameter of the flume),
measured from the beginning of the meas. section.
Size D
6'' (DN 150)
8'' (DN 200)
10'' (DN 250)
12'' (DN 315)
15'' (DN 400)
18'' (DN 450)
24'' (DN 600)
30'' (DN 800)
A12 x A22
A12 - A22
where:
A1 and h1= cross section and height in the inlet of the
flume
Max Flow
35 m3/h
70 m3/h
110 m3/h
200 m3/h
325 m3/h
545 m3/h
1100 m3/h
1750 m3/h
Table showing the size of D, and the max. flow for the
Palmer & Bowlus flumes.
Q/h diagram for the MJK Palmer & Bowlus flumes, the
height ha is shown as a function of the flow Q.
ha [m]
0,35
24"
0,3
30"
15"
0,25
0,2
12"
10"
0,15
8"
0,1
0,05
Q [m3/h]
0
0
50
100
150
200
250
300
350
400
450
500
ha
ha
H
=
=
=
=
flow in [m3/h]
width in the flume in [m]
water level before the narrowing
distance to the sensor = 3 - 4 x ha max
=
=
=
=
=
flow in [m3/h]
width in the flume in [m]
level
distance to sensor = 3 - 4 x ha max
height of the flume
h a[m] 1
200mm
160mm
120mm
ha[m] 1
200mm
0,1
160mm
120mm
0,1
0,01
0,1
10
100
1000
3
Q [m /h]
0,01
1
10
100
1000
Q [m 3/h]
Q/h diagram for the long throated Venturi flumes,
the height ha is shown as a function of the flow Q.
Size b
5" (DN
5'' (DN
6'' (DN
8'' (DN
8'' (DN
120)
120)
160)
200)
200)
H
150
300
300
320
520
mm
mm
mm
mm
mm
Max Flow
35 m 3/h
120 m3/h
150 m3/h
200 m3/h
450 m3/h
Mounting of sensor
Ultrasonic measuring system
0-30 cm
40 cm
10 cm
30 cm
70 cm
0-1 m
40 cm
10 cm
1 m
140 cm
Blockingdistance
0-3 m
75 cm
30 cm
3 m
3,75 m
Blockingdistance
Sensor height
Measuring
range
Opt. reflection
plate
0-level
suppression
Mleomrde
Min. mleomrde
Max. mleomrde
Sensor height
Measuringrange
0-1 m
30 cm
100 cm
Measuring range
0-3 m
1 m
3 m
Measuring range
0-level suppression
Electrical connection
Electrical connection of the flow converter 713, for hydrostatical, and ultrasonic measurement systems respectively.
Flow Converter 713
Hydrostatic measuring
system
Supply
Supply
Analog
output
Puls output
Supply
Control
On the front of the Flow Converter, you will find 4
function keys: the flow key, the summation key, the
alarm key and the sample key.
When one of these keys are pressed once or more the
different function menues appear. The avaliable menus
depend on how the Flow Converter is configured.
MAIN
MENU
FUNCTION
INDICATION
MAIN
MENU
SUM MENU
WITH
SELECTION
OR
SUM MENU
WITH VALUE
CONFIRM WITH
Display
The ESCape-key
MENU
ENTER
Q(t)
ALARM
Q(t)
or:
- Number of stormflows
- Time of stormflow
- Total stormflow
- Amount of most recent stormflow
- Start/finish time for last stormflow
- 99 stormflow log
9
Registration of:
- Total number of samples
- Number of samples today
- Number of samples within
24 hours
Function keys
The summation key:
Flow key:
Q(t)
Q(t)
F1
Flow
Measuring of volume:
13:34:12
3196 m3/h
F2
volume
F5
21/06/95
VOLUME:
13:34:12
223196 m3
Average flow 1 HR
The total volume is indicated, from when the value was
last reset or since start-up.
F6
1 HR
3120 m3/h
volume 1 HR
F3
1 HR
VOLUME :
TODAY
3120 m3/h
F7
TODAY
VOLUME:
Average flow 24 HR
00:00 - 13:51
776 m3
volume today
F4
11:00 - 12:00
77376 m3
24 HR
3120 m3/h
F8
The average flow for the last 24 hours is indicated
(00:00:00 til 23:59:59).
volume 24 HR
21/05/95
77376 m3
Stormflow measuring:
F9
Alarmkey:
No. of stormflows
ALARM
21/06/95
13:34:12
NO. OF STORMFLOWS
19621
The digital outputs can be configured as alarms of one
of the following alarm types: high flow, low flow, 24 hour
volume, one hour volume and sensor error. Press the
alarm key to see the previous nine alarms. A new
alarm is registered as alarm no 1, the other alarms are
moved one place, and the alarm which was previously
registered as alarm no 9 is erased.
F10
Stormflow time
F15
F11
ALARM 1:
13/03 23:33
F12
ALARM 2:
13/03 23:33
Stormflow start/stop
00:29
F14
99 days log
HIGH FLOW D#
13/03 23:54
ALARM 3:
VOLTAGE FAILURE
21/06 00:22
21/06 11:23
1084 m3
F13
HIGH FLOW D#
STORMFLOW
LAST STORMFLOW :
Alarm display
138 m3
18/6 14:21
Sample key:
Menu key:
MENU
SAMPLE
F16
Number of samples
0.1
Level
F17
LEVEL= 543.2
I= 12.3 mA
D1=0 D2=0 D3=1 D4=1 D5=0
Here the measured level (LEVEL), the value for the
analog output (I) is indicated. The digital outputs are
indicated as D1-D5. 0 indicates non activated output,
where as 1 indicates activated outputs. Outputs chosen
to "not in use" are not shown.
0.2
Language
LANGUAGE
F18
Number of samples 24 HR
0.3
0000
ENGLISH
DANSK
NO: Menu
0.4
Access denied
2.1
Configuring:
1.0
1.1
2.2A
1.2
2.2B
2.3
Measurement Stormflow /
Continuous
1.6
2.4
Here the level for 0-point can be keyed in over the flow
calculation for starts of the flow measurement. This
function is used for instance when a weir has to be
measured. The flow calculation is not done before the
level is above the minimum level, while the actual calculation is made from the 0-point for flow measurements.
2.5
2.0
1.5
Sensor level
1.4
1.3
2.6
3.0
Here the type and size of flume/weir used for the flow
measuring is chosen.
3.1
3.2
3.3
Venturi flumes
3.4
Parshall flumes
3.5
Palmer/Bowlus flumes
14
4.4
The limit for flow low is keyed in with the arrow keys.
The area is 0.0 to (maximum flow+10%).
4.6
4.0
4.1
4.5
4.7
4.8
Flow>0%:
4.3
4.9
Sampler:
Alarm 1 HR volume
Counter output:
Alarm 24 HR volume
4.2
4.10
5.0
5.1
The limit for flow high is keyed in with the arrow keys.
Double arrow runs the value fast with 10cm steps,
single arrow runs the value slowly with 0,1 cm steps.
The area is 0.0 to (maximum flow+10%).
15
Specifications
Dimensions
Order numbers
Part no:
201450
201455
201460
202600
202650
202655
202660
Specifications:
713U-1111 Ultrasonic measuring system, range 0-30 cm
713U-1121 Ultrasonic measuring system, range 0-1 m
713U-1131 Ultrasonic measuring system, range 0-3 m
713-1104 Flow Converter without sensor, 4-20 mA input
713P-1114 Hydrostatic measuring system, range 0-30 cm
713P-1124 Hydrostatic measuring system, range 0-1 m
713P-1134 Hydrostatic measuring system, range 0-3 m
Universal bracket
Bracket for ultrasonic sensor 7005
16
Functional Indications
6 Q(t)
Q(t)
MENU
CONTINOUS
F1
0.1
LEVEL = 0.00
i = 4.00 mA
D1=0 D2=0 D3=0 D4=0 D5=0
24/12/96
FLOW:
LANGUAGE ENGLISH
DANISH
AVERAGE FLOW
1 HR
6VOLUME:
17
TODAY
6 VOLUME:
F4
AVERAGE FLOW:
FLOW:
24 HR
24 HR
6 VOLUME:
ALARM:
24/12 13:01
F16
24/12/96
21:05:00
NUMBER OF SAMPLES: 937
Alarm type
24/12 13:55
F10
F17
20:00 - 21:00
176 m3
24/12/96
21:05:00
STORMFLOW TIME:
9:51
TODAY:
00:00 - 21:05
NUMBER OF SAMPLES: 45
F11
F18
00:00 - 21:05
3717 m3
STORMFLOW VOLUME:
TOTAL:
1084 m3/h
24 HR
23/12/96
NUMBER OF SAMPLES: 56
F8
170 m3/h
F15
24/12/96
21:05:00
NO. OF STORMFLOWS: 15
F7
TODAY
177 m3/h
FLOW:
0.4
ACCESS NOT ALLOWED
:1HR
F3
AVERAGE FLOW:
F9
21:05:00
223196 m3
F6
3120 m3/h
FLOW:
0.3
ENTER ACCESS CODE
USE ARROW KEYS 0000
24/12/96
6 VOLUME:
SAMPLER
STORMFLOW
F5
21:05:00
3196 m3/h
F2
0.2
ALARM
F12
23/12/96
1080 m3
STORMFLOW VOLUME:
LAST:
54 m3/h
F13
START 24/12 13:05
STOP 24/12 13:55 00:50
F14
LOG 22
m3
18/6 12:56
14:21
138
18/6
ENTER
F19
RESET
YES: Enter
ENTER
NO : Menu
PRINCIPLES OF MEASUREMENT
HYDROSTATIC
ULTRASONIC
1.0
2.0A
PROGRAMMING OF
MAIN FUNCTIONS
1.2
OPTIONAL
RANGE
ENABLED
DISABLED
3.0
ULTRASONIC SENSOR
DATA FOR MOUNTING
2.1A
1.1
SET DATE AND TIME
24/12/96
12:30:55
ACCESS CODE
2.0B
HYDROSTATIC SENSOR
DATA FOR MOUNTING
4.0
PROGRAMMING OF
FLOW CALCULATION
2.1B
3.1
2.2B
3.2
SENSOR HEIGHT
5.1
4.1
ENTER DIGITAL OUTPUT
(1.5)
ANALOG output
4-20mA
0-20mA
DO 1-4
2.2A
4.2
1.3
PROGRAMMING OF
ANALOG OUTPUT
XXX.X cm
ENABLED
5.0
PROGRAMMING OF
DIGITAL OUTPUT
DO 5
COUNTER
SAMPLER
SENSOR
ERROR
2.3
18
FLOW MEASUREMENT 0 -
PUNKT
LEVEL
1.4
XXX.X cm
MEASUREMENT STORMFLOW
CONTINOUS
COUNTER
OUTPUT
2.4
FLOW > 0
STORMFLOW
LEVEL FOR
MAX. FLOW
24 HR VOLUME
4.3
4.4
4.5
XXX.X cm
4.9
2.6
1.6
FLOW
LOW
4.8
2.5
1.5
STORMFLOW COUNTER
DELAYED hh:mm
FLOW
HIGH
4.7
DIGITAL OUTPUT #
ON-TIME
XX.X sec
AVERAGING OF LEVEL
OVER
XX seK
ENTER DELAY ON
SIGNAL mm:ss
XX:XX
XX:XX
4.10
VENTURI
FLUME
3.3
VENTURI FLUME
dimension
PARSHALL
FLUME
3.4
PARSHALL FLUME
dimension
PALMER/BOWLUS
FLUME
3.5
PALMER/BOWLUS FLUME
dimension
V-NOTCH WEIR
RECTANGULAR WEIR
3.6.1
V-NOTCH WEIR
type
3.6.2
V-NOTCH WEIR
ANGLE
XXX
3.6.3
90 V-NOTCH WEIR
FLUME WIDTH
XXX.X
m3
3.6.4
90 V-NOTCH WEIR
DEPTH BELOW EDGE XXX.X cm
Q(h) LINEARIZATION
OPTIONAL
FORMULA
3.7.1
3.8.1
3.9.1
RECTANGULAR WEIR
FLUME WIDTH
XXX.X cm
NUMBER OF Q(h)-POINTS
(1-10)
X
OPTIONAL FORMULA
ENTER EXPONENT
X.XXX
3.7.2
3.8.2
3.9.2
RECTANGULAR WEIR
EDGE WIDTH
XXX.X cm
OPTIONAL FORMULA
ENTER FACTOR
XX.XXX
3.7.3
RECTANGULAR WEIR
DEPTH BELOW EDGE XXX.X cm
3.8.3
ENTER FLOW POINT ##
XXX.X m3/h
DIGITAL OUTPUT #
NO
NC
1 HR VOLUME
4.6
ENTER MAX 1 HR
VOLUME ALARM
XXX.X m3
Series No.:
Date:
Measuring station:
Wanted /
Measuring
Continiuosly
HYDROSTATIC SENSOR
Un wanted
/
Access key:
Storm flow
min
sec
min
ULTRASONIC SENSOR
Sensor type:
Sensor range:
Ultra sonic sensor height
cm
cm
cm
cm
sec
m3/h
/
/
Weir width:
cm
Flume width:
cm
High point:
cm
Flow point:
Optional formular
l/sec
m3/h
Range:
Rectangular weir
Exponent:
Factor:
Function:
Setting:
Delay on
signal
m3 between
pulses
On-time:
NO / NC
DO2
Function:
Setting:
Delay on
signal
m3 between
pulses
On-time:
NO / NC
DO3
Function:
Setting:
Delay on
signal
m3 between
pulses
On-time:
NO / NC
DO4
Function:
Setting:
Delay on
signal
m3 between
pulses
On-time:
NO / NC
DO5
Counter output
m3 between
pulses
On-time
NO / NC
4-20mA
0-20mA
19
20