Professional Documents
Culture Documents
Chapter 42
Water and Steam Chemistry,
Deposits and Corrosion
Chemistry-boiler interactions
To understand how water impurities, treatment
chemicals and boiler components interact, one must
first understand boiler circuitry, and steam generation
and separation processes.
Boiler feed pumps provide feedwater pressure and
flow for the boiler. From the pumps, feedwater often
passes through external heaters and then through an
economizer where it is further heated before entering
the boiler. In a natural circulation drum-type unit,
boiling occurs within steel tubes through which a
water-steam mixture rises to a steam drum. Devices
in the drum separate steam from water, and steam
leaves through connections at the top of the drum.
This steam is replaced by feedwater which is supplied
42-1
42-2
42-3
Boiler feedwater
To maintain boiler integrity and performance and
to provide steam of suitable turbine or process purity,
boiler feedwater must be purified and chemically conditioned. The amount and nature of feedwater impurities that can be accommodated depend on boiler operating pressure, boiler design, steam purity requirements, type of boiler water internal treatment,
blowdown rate, and whether the feedwater is used for
steam attemperation. Feedwater chemistry parameters to be controlled include dissolved solids, pH, dissolved oxygen, hardness, suspended solids, total organic carbon (TOC), oil, chlorides, sulfides, alkalinity,
and acid or base forming tendencies.
At a minimum, boiler feedwater must be softened
water for low pressure boilers and demineralized water for high pressure boilers. It must be free of oxygen and essentially free of hardness constituents and
suspended solids. Recommended feedwater limits are
shown in Table 1. Use of high-purity feedwater minimizes blowdown requirements and minimizes the potential for carryover, deposition, and corrosion problems throughout the steam-water cycle.
Operation within these guidelines does not by itself
ensure trouble-free operation. Some feedwater contaminants such as calcium, magnesium, organics, and carbonates can be problematic at concentrations below the
detection limits of analytical methods commonly used
Table 1
Recommended Feedwater Limits
Once-Through
Boilers
Drum Boilers
Oxygen
Pressure,
psig (MPa)
with AVT*
AVT
Treatment
15 to 300
(0.10 to 2.07)
301 to 600
(2.08 to 4.14)
601 to 900
(4.14 to 6.21)
901 to 1000
(6.21 to 6.90)
1001 to 1500
(6.90 to 10.34)
>1500
(>10.34)
All
All
All
9.3 to 10.0
9.3 to 10.0
9.3 to 10.0
9.3 to 9.6
9.3 to 9.6
9.3 to 9.6
9.3 to 9.6
9.3 to 9.6
8.0 to 8.5
8.8 to 9.2
8.8 to 9.2
8.8 to 9.2
8.8 to 9.2
8.8 to 9.2
8.8 to 9.2
Total hardness,
as ppm CaCO3,
maximum
0.3
0.2
0.1
0.05
0.003
0.003
0.003
0.003
0.001
0.007
0.007
0.007
0.007
0.007
0.007
0.007
0.007
0.030 to 0.150
Iron, ppm
maximum
0.1
0.04
0.02
0.02
0.01
0.01
0.01
0.010
0.005
Copper, ppm
maximum
0.05
0.02
0.01
0.01
0.005
0.002
0.005
0.002
0.001
Organic, ppm
TOC max.
1.0
1.0
0.5
0.2
0.2
0.2
0.2
0.200
0.200
Cation conductivity,
S/cm max.
0.5
0.2
0.2
0.15
0.15
Oxygen, ppm
maximum***
N/A
42-4
Makeup water
Boiler feedwater is generally a mix of returned
steam condensate and fresh makeup water. For utility boilers, most of the steam is usually returned as
condensate, and only 1 to 2% makeup is necessary.
However, for some industrial cycles, there is little or
no returned condensate, so as much as 100% makeup
may be necessary.
Chemistry requirements for makeup water depend
on the amount and quality of returned steam condensate. Where a large portion of the feedwater is uncontaminated condensate, makeup water can generally
be of lesser purity so long as the mixture of condensate and makeup meet boiler feedwater requirements.
The feedwater concentration for each chemical species is the weighted average of the feedwater and
makeup water concentrations:
Feedwater concentration = (condensate concentration flow
(1)
+ makeup concentration makeup flow) / total feedwater flow
Attemperation water
Water spray attemperation is used to control steam
temperature. Attemperation for utility boilers is discussed in the Steam temperature adjustment and control section of Chapter 19, Boilers, Superheaters and
Reheaters. The spray water is feedwater, polished feedwater, or steam condensate. As the spray water evaporates, all chemicals and contaminants in the water
remain in the steam. This addition must not be excessive. It must not form deposits in the attemperator
piping, and it must not excessively contaminate the
steam. If a superheated steam purity limit is imposed,
the steam purity after attemperation must not exceed
this limit. To meet this requirement, the weighted
average of the spray water total solids concentration
and the saturated steam total solids concentration
must not exceed the final steam total solids limit. Additionally, spray water attemperation must not increase the steam total solids concentration by more
than 0.040 ppm. Independent of other considerations,
the spray water solids concentration must never exceed 2.5 ppm. Ideally, the purity of attemperation
water should equal the desired purity of the steam.
Blowdown
The dissolved solids concentration of boiler water
is intermittently or continuously reduced by blowing
down some of the boiler water and replacing it with
feedwater. Blowdown rate is generally expressed as a
percent relative to the steam flow rate from the drum.
42-7
Phosphate, ppm
10
10
100
1000
10000
10.5
pH
10
Phosphate, ppm
100
boiler water pH because measured sodium concentrations include non-phosphate sodium salts. While dissolved sodium chloride and sulfate do not alter boiler
water pH, ammonia does alter the pH. Hence, the
presence of ammonia must be taken into account
where ammonia concentrations are significant compared to phosphate concentrations.
Historically, the initial goal of coordinated pH-phosphate control was to keep the effective molar sodiumto-phosphate ratio just below 3, to prevent caustic stress
corrosion cracking, acid corrosion, and hydrogen damage. This proved to be an effective method for control
of deposition and corrosion in many boilers. However,
caustic gouging of furnace wall tubes occurred in some
boilers using coordinated pH-phosphate control, and
laboratory tests indicated that solutions with molar
sodium-to-phosphate ratios greater than about 2.85 can
become caustic when highly concentrated. Subsequently, many boilers were operated under congruent
control with a target effective sodium-to-phosphate
ratio of less than 2.85, generally about 2.6, and often
less than 2.6. Again, this proved to be an effective
method of control for many boilers, but some of the
boilers operating with low molar sodium-to-phosphate
ratios experienced acid phosphate corrosion. Instances
of boiler tube corrosion generally occurred in boilers that
experienced substantial phosphate hideout and hideout-return when the boiler load changed.
Phosphate hideout, hideout-return, and associated
corrosion problems are now addressed by equilibrium
phosphate treatment.13 The concentration of phosphate
in the boiler water is kept low enough to avoid hideout and hideout return associated with load changes,
thus it is always in equilibrium with the boiler. The
effective molar sodium-to-phosphate ratio is kept
above 2.8. The free hydroxide, as depicted in Fig. 6,
is not to exceed the equivalent of 1 ppm sodium hydroxide. Concern about caustic gouging at the higher
ratios is largely reduced by experience with this treat-
Table 2
Boiler Water Limits
Pressure
Range,
psig (MPa)
Maximum
TDS, ppm
Maximum
Suspended
Solids, ppm
Maximum
Silica, ppm
15 to 50*
(0.10 to 0.35)
1250
15
30
15 to 50**
(0.10 to 0.35)
3500
15
150
51 to 325
(0.35 to 2.24)
3500
10
150
326 to 450
(2.25 to 3.10)
3000
90
451 to 600
(3.11 to 4.14)
2500
40
601 to 750
(4.14 to 5.17)
2000
30
751 to 900
(5.18 to 6.21)
1500
20
901 to 1000
(6.21 to 6.90)
1250
42-9
Table 3
Boiler Water Limits for Coordinated Phosphate Boiler Water Treatment
Pressure, psig (MPa)
15 to 1000
(0.10 to 6.90)
Maximum
TDS, ppm
Maximum
sodium, ppm
Maximum
silica, ppm
Defined by Table 2 or as
necessary to attain required
steam purity, whichever is less
1001 to 1500
(6.90 to 10.34)
1501 to 2600
(10.35 to 17.93)
2601 to 2800
(17.93 to 19.31)
15 ppm or as necessary to
attain required steam
purity, whichever is less
Maximum sodium concentration (if any) as necessary to attain required steam purity
Defined by Table 2 or as
necessary to attain required
steam purity, whichever is less
2 ppm or as necessary to
attain required steam
purity, whichever is less
Phosphate as
PO4, ppm
See Fig. 5
"Effective"
Na/PO4
molar ratio
2.6 to 3.0
pH
Maximum
specific conductivity, S/cm
Twice the maximum TDS (ppm).
Note:
ppm = mg/kg
Phosphate treatment chemicals may hide out during periods of high-load operation, then return to the
boiler water when the load and pressure are reduced.
This type of hideout makes control of boiler water
chemistry difficult and can cause corrosion of furnace
wall tubes. This hideout and return phenomena is
caused by concentration of phosphate at the tube/
water interface in high heat flux areas. In these areas, phosphates accumulate in the concentrated liquid. The concentrated phosphates then precipitate, or
they adsorb on or react with surface deposits and
scale.13,14,15 Where excessive deposits are not present,
this hideout and hideout return associated with load
and pressure changes can be eliminated by decreasing the phosphate concentration in the boiler water
or possibly by increasing the sodium-to-phosphate
ratio. Where hideout and hideout-return are caused
by excessive deposits, the boiler must be chemically
cleaned. The amount of phosphate hideout or return
accompanying load changes must not be more than 5
ppm. Corrective action is necessary if the amount of
phosphate hideout or return accompanying load
changes is more than 5 ppm and/or the boiler water
pH change is more than 0.2 pH units, or where there
are changes in the hideout/hideout-return behavior.
This phenomenon must be distinguished from loss of
phosphate to passive film formation. As the passive oxide film reforms following a chemical cleaning of the
boiler, some phosphate is irreversibly lost from the boiler
water. This is minimized if chemical cleaning is followed
by a phosphate boilout repassivation of the boiler.
Operators should not over-correct for deviations of
42-10
pH
9.6
Na/PO4 = 2.8
Na/PO4 = 2.6
9.4
9.2
8.8
Phosphate, ppm
hydroxide may be excessive for some units, for example oil-fired boilers with especially high heat fluxes
in some areas of the furnace.
When mixing boiler water treatment chemicals,
operators should verify the identity and purity of the
chemicals and take into account water of hydration
in the weight of the chemicals. Neither phosphoric acid
nor monosodium phosphate should be used for routine boiler water treatment. If monosodium phosphate
is used to counter an isolated incident of alkali contamination of the boiler water, it must be used with
caution, and at reduced load.
Phosphate, ppm
10
50
Maximum
40
Optimum
30
Minimum
20
10
0
(0)
200
(1379)
400
(2758)
600
(4137)
800
(5516)
1000
(6895)
42-11
42-12
Otherwise, over a period of years the accumulative effects will be significant. Potential effects include increased deposition, pitting, pressure drop, and fatigue
cracking. Particular care is required to minimize the
extent and duration of chemistry deviations for cycling
units where operational transients are frequent.
Steam purity
Purity or chemistry requirements for steam can be
as simple as a specified maximum moisture content,
or they can include maximum concentrations for a
variety of chemical species. Often, for low-pressure
building or process heater steam, only a maximum
moisture content is specified. This may be as high as
0.5% or as low as 0.1%. Conversely, some turbine
manufacturers specify steam condensate maximum
cation conductivity, pH, and maximum concentrations
for total dissolved solids, sodium and potassium, silica,
iron, and copper. Turbine steam must generally have
total dissolved solids less than 0.050 ppm, and in some
cases less than 0.030 ppm. Individual species limits
may be still lower. If steam is to be superheated, a
maximum steam dissolved solids limit must be imposed
to avoid excessive deposition and corrosion of the superheater. This limit is generally 0.100 ppm or less.
Even where steam purity requirements are not imposed by the application, steam dissolved solids concentrations less than 1.0 ppm are recommended at
pressures up to 600 psig (4.1 MPa), dissolved solids
concentrations less than 0.5 ppm are recommended at
600 to 1000 psig (4.1 to 6.9 MPa), and dissolved solids concentrations less than 0.1 ppm are recommended
above 1000 psig (6.9 MPa).
Up to 2000 psig (13.8 MPa), most non-volatile chemicals and impurities in the steam are carried by small
water droplets entrained in the separated steam. Because these droplets contain dissolved solids in the same
concentration as the boiler water, the amount of impurities in steam contributed by this mechanical carryover
is the sum of the boiler water impurities concentration
multiplied by the steam moisture content. Mechanical
carryover is limited by moisture separation devices placed
in the steam path, as described in Chapter 5.
High water levels in the drum and boiler water
chemistries that cause foaming can cause excessive
moisture carryover and therefore excessive steam
impurity concentrations. Foaming is the formation of
foam or excessive spray above the water line in the
drum. Common causes of foaming are excessive solids or alkalinity, and the presence of organic matter
such as oil. To keep dissolved solids below the concentration that causes foaming requires continuous or
periodic blowdown of the boiler. High boiler water alkalinity increases the potential for foaming, particularly in the presence of suspended matter.
Where a chemical species is sufficiently volatile, it
also carries over as a vapor in the steam. Total carryover is the sum of the mechanical and vaporous carryover. Vaporous carryover depends on solubility in
steam and is different for each chemical species. For
most dissolved solids found in boiler water, it is negligible by comparison to mechanical carryover at pres-
42-13
Table 4
Guidelines for Measurements on Grab Samples
Measurement
10
pH
Electrometric
ASTM D 1293
Method A
Conductivity
ASTM D 1125
Methods A or B
Dissolved
oxygen
Colorimetric or
titrimetric
ASTM D 888
Methods A, B, C
Suspended
iron oxides
Membrane comparison
charts
ASME PTC 31
Ion exchange
equipment
Iron
Photometric
(bathophenanthroline)
or atomic absorption
(graphite furnace)
ASTM D 1068
Method C, D
Copper
Atomic absorption
(graphite furnace)
ASTM D 1688
Method C
Sodium
Atomic absorption or
flame photometry
ASTM D 4191 or
ASTM D 1428
Silica
Colorimetric or
atomic absorption
ASTM D 859 or
ASTM D 4517
Phosphate
Ion chromatography or
photometric
ASTM D 4327 or
ASTM D 515
Method A
Ammonia
Colorimetric
(nesslerization) or
ion-selective electrode
ASTM D 1426
Method A or B
Hydrazine
Colorimetric
ASTM D 1385
Chloride
Colorimetric,
ion-selective electrode
or ion chromatography
ASTM D 512 or
ASTM D 4327
Sulfate
Turbidimetric or ion
chromatography
ASTM D 516 or
ASTM D 4327
Calcium and
magnesium
Atomic absorption;
gravimetric or
titrimetric
ASTM D 511 or
ASTM D 1126
Fluoride
Ion-selective electrode
or ion chromatography
ASTM D 1179 or
ASTM D 4327
Morpholine
Colorimetric
ASTM D 1942
Alkalinity
Color-change titration
ASTM D 1067
Method B
Hydroxide ion
in water
Titrimetric
ASTM D 514
Total organic
carbon
Instrumental (oxidation
and infrared detection)
ASTM D 4779
0.1
0.01
0
(0)
500
(3447)
1000
(6895)
1500
(10,342)
2000
(13,790)
2500
(17,237)
3000
(20,684)
Technique(s)
Reference/
Comment
(Notes 1 and 2)
Notes:
1. ASME PTC refers to Performance Test Codes of the American
Society of Mechanical Engineers, New York, New York.
2. ASTM refers to testing procedures of the American Society for
Testing and Materials, Philadelphia, Pennsylvania.
Technique(s)
Reference
pH
Electrometric
ASTM D 5128
Conductivities
(general, cation
and degassed)
Electrical conductivity
ASTM D 4519
measurement before and
after hydrogen cation
exchanges and at atmospheric boiling water
after acidic gas removal
Sodium
ASTM D 2791
Total organic
carbon
Instrumental (oxidation
and measurement
of carbon dioxide)
ASTM D 5173
the corrosion, appearance of the corrosion, and chemistry of localized deposits and corrosion products often
suggest the cause. Common causes are flow accelerated
corrosion, oxygen pitting, chelant corrosion, caustic
corrosion, acid corrosion, organic corrosion, acid phosphate corrosion, hydrogen damage, and corrosion assisted cracking. Figs. 12 and 13 show typical locations
of common fluid-side corrosion problems. Further dis-
42-15
42-16
42-17
Pre-operational cleaning
Fig. 19 Caustic gouging initiated along weld backing ring.
42-18
In general, all new boiler systems receive an alkaline boilout, i.e. hot circulation of an alkaline mixture
with intermittent blowdown and final draining of the
unit. Many systems also receive a pre-operational
chemical cleaning. The superheater and reheater
should receive a conventional steam blow (a period of
high velocity steam flow which carries debris from the
system). Chemical cleaning of superheater and reheat
surfaces is effective in reducing the number of steam
blows to obtain clean surfaces, but is not required to
obtain a clean superheater and reheater.
Alkaline boilout
All new boilers should be flushed and given an alkaline boilout to remove debris, oil, grease and paint.
This can be accomplished with a combination of trisodium phosphate (Na3PO4) and disodium phosphate
(Na2HPO4), with a small amount of surfactant added
as a wetting agent. The use of caustic NaOH and/or
soda ash (Na2CO3) is not recommended. If either is
used, special precautions are required to protect boiler
components.
Chemical cleaning
After boilout and flushing are completed, corrosion
products may remain in the feedwater system and
boiler in the form of iron oxide and mill scale. Chemical cleaning should be delayed until full load operation has carried the loose scale and oxides from the
feedwater system to the boiler. Some exceptions are
units that incorporate a full flow condensate polishing system and boilers whose pre-boiler system has
been chemically cleaned. In general, these units can
be chemically cleaned immediately following pre-operational boilout.
Different solvents and cleaning processes are used
for pre-operational chemical cleaning, usually determined by boiler type, metallic makeup of boiler components, and environmental concerns or restrictions. The
four most frequently used are: 1) inhibited 5% hydrochloric acid with 0.25% ammonium bifluoride, 2) 2%
Steam 41 / Water and Steam Chemistry, Deposits and Corrosion
Chordal thermocouples
The chordal thermocouple (see Chapter 40) can be
an effective diagnostic tool for evaluating deposits on
operating boilers. Properly located thermocouples can
indicate a tube metal temperature increase caused by
excess internal deposits, and can alert the operator to
conditions that may cause tube failures. Thermocouples are often located in furnace wall tubes adjacent to the combustion zone where the heat input is
highest and the external tube temperatures are also
high. (See Fig. 22.)
Deposition inside tubes can be detected by instrumenting key furnace tubes with chordal thermocouples. These thermocouples compare the surface
temperature of the tube exposed to the combustion
process with the temperature of saturated water. As
deposits grow, they insulate the tube from the cooling
water and cause tube metal temperature increases.
Beginning with a clean, deposit-free boiler, the instrumented tubes are monitored to establish the temperature differential at two or three boiler ratings; this
establishes a base curve. At maximum load, with clean
tubes, the surface thermocouple typically indicates
metal temperatures 25 to 40F (14 to 22C) above saturation in low duty units and 80 to 100F (44 to 56C) in
high duty units as shown in Fig. 23. The temperature
variation for a typical clean instrumented tube is dependent upon the tubes location in the furnace, tube
thickness, inside fluid pressure, and the depth of the
Table 6
Guidelines for Chemical Cleaning
Unit Operating
Pressure, psig (MPa)
Water-side
Deposit Weight*
(g/ft2 )
20 to 40
12 to 20
10 to 12
42-19
Clean Tube
500F
(260C)
Chemical Recovery Boiler
583F
(306C)
Saturation Temp
500F (260C) at
665 psi (4.6 MPa)
Heat Input
120,000 Btu/h ft2
(378,550 W/m2)
510F
(266C)
Furnace
Side
Scaled Tube
80 g/ft2
877F
(469C)
785F
(418C)
500F
(260C)
500F
(260C)
42-20
Soaking method
The soaking (static) cleaning method (Fig. 25) involves preheating the unit to a specified temperature,
filling the unit with the hot solvent, then allowing the
unit to soak for a period of time, depending on deposit
conditions. To assure complete deposit removal, the
acid strength of the solvent must be somewhat greater
than that required by the actual conditions; unlike the
circulation method, control testing during the course
of the cleaning is not conclusive, and samples of solvent drawn from convenient locations may not truly
represent conditions in all parts of the unit.
The soaking method is preferable for cleaning units
where definite liquid distribution to all circuits (by the
circulation method) is not possible without the use of
many chemical inlet connections. The soaking method
is also preferred when deposits are extremely heavy,
or if circulation through all circuits at an appreciable
rate can not be assured without an impractically-sized
circulating pump. These conditions may exist in large
natural circulation units that have complex furnace
wall cooling systems.
Advantages of this method are simplicity of piping
connections and assurance that all parts are reached
by a solvent of adequate acid strength.
Solvents
Many acids and alkaline compounds have been
evaluated for removing boiler deposits. Hydrochloric
acid (HCl) is the most practical cleaning solvent when
using the soaking method on natural circulation boilers. Chelates and other acids have also been used.
An organic acid mixture such as hydroxyacetic-formic (HAF) is the safest chemical solvent when applying the circulation cleaning method to once-through
boilers. These acids decompose into gases in the event
of incomplete flushing.
For certain deposits, the solvent may require additional reagents, such as ammonium bifluoride, to promote deposit penetration. Alloy steel pressure parts,
particularly those high in chromium, should generally
not be cleaned with certain acid solvents. A general
guideline for solvent selection can be found in Table 7.
Prior to chemically cleaning, it is strongly recommended that a representative tube section be removed
and subjected to a laboratory cleaning test to determine and verify the proper solvent chemical, and concentrations of that solvent.
Steam 41 / Water and Steam Chemistry, Deposits and Corrosion
200
With Internal
Deposits
After Operation
T, F
150
Base Curve
Clean Condition
100
50
50
100
Firing Rate, %
Low Duty Units
200
With Internal
Deposits
After Operation
150
T, F
100
50
Base Curve
Clean Condition
0
50
100
Firing Rate, %
High Duty Units
Deposits
Scale deposits formed on the internal heating surfaces of a boiler generally come from the water. Most
of the constituents belong to one or more of the following groups: iron oxides, metallic copper, carbonates, phosphates, calcium and magnesium sulfates,
silica, and silicates. The deposits may also contain
various amounts of oil.
Pre-cleaning procedures include analysis of the
deposit and tests to determine solvent strength and
contact time and temperature. The deposit analyses
should include a deposit weight in grams per square
foot (or milligrams per square centimeter) and a spectrographic analysis to detect the individual elements.
X-ray diffraction identifying the major crystalline constituents is also used.
If the deposit analysis indicates the presence of copper (usually from corrosion of pre-boiler equipment,
such as feedwater heaters and condensers), one of
three procedures is commonly used: 1) a copper
complexing agent is added directly to the acid solvent,
2) a separate cleaning step, featuring a copper solvent,
is used followed by an acid solvent, and 3) a chelantbased solvent at high temperature is used to remove
iron, followed by addition of an oxidizing agent at re42-21
Inhibitors
The following equations represent the reactions of
hydrochloric acid with constituents of boiler deposits:
Fe3 O4 + 8HCl 2FeCl3 + FeCl 2 + 4H2O
(2)
(3)
42-22
(4)
unless means are provided to slow this reaction without affecting the deposit removal. A number of excellent commercial inhibitors are available to perform this
function. The aggressiveness of acids toward boiler
deposits and steel increases rapidly with temperature.
However, the inhibitor effectiveness decreases as the
temperature rises and, at a certain temperature, the
inhibitor may decompose. Additionally, all inhibitors
are not effective with all acids.
Table 7
Comparative Cleaning Effectiveness
Makeup of Deposit
Type of
Cleaning
HCl
HAF
EDTA
Citric
Bromate
Iron
Copper
Silica
Hardness
(Ca/Mg)
Good
Good
Good
Good
N/A
Medium
Poor
Medium
Medium
Good
Medium
Medium
Poor
Poor
N/A
Good
Medium/poor
Medium/poor
Poor
N/A
Cleaning procedures
The chemical cleaning of steam generating equipment consists of a series of distinct steps which may
include the following:
1.
2.
3.
4.
Fig. 26 Solvent conditions during cleaning by the circulation method.
Precautions
Cleaning must not be considered a substitute for
proper water treatment. Intervals between cleanings
should be extended or reduced as conditions dictate.
Every effort should be used to extend the time between chemical cleanings. Hazards related to chemical cleaning of power plant equipment are fairly well
recognized and understood, and appropriate personnel safety steps must be instituted.27
42-24
Solvent disposal
General considerations A boiler chemical cleaning
is not complete until the resultant process waste water stream is disposed of. Selection of handling and
disposal methods depends on whether the wastes are
classified as hazardous or non-hazardous. Boiler
chemical cleaning wastes (BCCW) are different in
volume and frequency of generation and have different discharge regulations from other power plant waste
streams. Of all power plant discharges, BCCWs are
most likely to be classified as hazardous. Depending
upon the cleaning process, the resultant BCCW may
become one of the driving forces in solvent selection.
Under National Pollutant Discharge Elimination
System (NPDES) requirements, boiler cleaning wastes
are considered chemical metal cleaning wastes. The
primary parameters of concern are iron, copper, chromium and pH. In all cases, waste management must
be performed in accordance with current regulatory
requirements.
Waste management options Table 8 lists the handling practices for BCCW. In co-ponding, the BCCW
is mixed in an ash pond with other waste streams from
the power plant. Acid wastes are neutralized by the
alkaline ash, and the metals are precipitated as insoluble metal oxides and hydroxides, or absorbed on
ash particles. Co-ponding is the least expensive and
the easiest disposal option.
Incineration of organic-based cleaning wastes by
direct injection into the firebox of the utility boiler is
another common disposal practice. Potential emissions
from the boiler must be carefully monitored to ensure
regulatory compliance.
Large quantities of BCCW are often disposed of in a
secure landfill. Evaporation can reduce waste volume
and, thereby, reduce overall landfill disposal costs.
HCl cleaning wastes can be treated to NPDES standards using lime or caustic precipitation. It is more
Layup
Table 8
Boiler Chemical Cleaning Wastes
Practices/Options
Source Reduction
Optimize cleaning frequency
Reduce volume of cleaning solution
Improve boiler water chemistry
Alternate Solutions
Change the cleaning solvent
Disposal
Evaporation
Incineration
Co-ponding
Secured landfill
Treatment
Neutralization
Physical waste treatment
Chemical waste treatment
Recycle and Reuse
Recycle for metal recovery
Reuse acid in alternate applications
During periods when boiler operation is interrupted, substantial pitting and general corrosion can
occur within unprotected water-steam circuitry. When
boilers return to operation, corrosion products migrate
to high heat flux areas of the boiler or carryover to
the turbine. Out-of-service corrosion can therefore impede boiler startup and lead to operational problems
such as deposition, under-deposit corrosion, corrosion
fatigue, and cycle efficiency loss.
Preservation methods inhibit out-of-service corrosion by eliminating or controlling moisture, oxygen,
and chemical contaminants that cause corrosion. Table
9 provides a brief summary and comparison of common preservation methods.
These methods are designed to limit corrosion
caused by the normal range of boiler and atmospheric
contaminants. Gross contamination must be avoided
and, if it occurs, the contaminants must be immediately neutralized and removed. Respective vendors
should be contacted for specific recommendations for
balance-of-plant equipment (turbine, condensate,
feedwater, and atmospheric pollution control systems).
Vendor procedures should also be followed for boiler
auxiliary equipment such as pulverizer gearboxes,
sootblowers, fans, and motors.
42-25
Table 9
Summary and Comparison of Boiler Lay-up Methods
Lay-up Method
Effectiveness
Costs
Safety and
Environmental Concerns
Strengths
Weaknesses
Poor
Minimal
Minimal
Not effective
Vaporous
corrosion
inhibitors
Variable,
generally
fair
Chemicals
Chemical application
Chemical removal
and disposal
Minimal maintenance
requirements
Remaining inhibitive
capacity is difficult
to monitor
Chemicals must be
replaced periodically
Difficult to distribute
through components
Nitrogen
blanketing
Excellent
Nitrogen distribution
system
Nitrogen
Nitrogen suffocation
Consistently effective
Easy to monitor
Safety concerns
Nitrogen leakage
Hot standby
Good
Heat
Residual temperature
and pressure
Fast restart
Cold standby
Poor
Minimal
Minimal
Fast restart
Wet, water-filled
Variable,
generally
good
Demineralized water
Chemical treatment
Disposal of treated
water
Handling of
chemicals
Disposal of treated
water
Easily applicable to
non-drainable
components
Facilitates rapid
return to service
Freeze damage
Valve seepage and
associated corrosion
damage
Difficult to monitor
and inspect
May corrode copper
alloys beyond boiler
Dry, dehumidified
air
Excellent
Dehumidifier and
blower unit
Air recirculation
piping
Minimal
Consistently effective
Safe
No disposal problems
Easy to monitor
Boiler must be
totally drained
Initial plumbing
and equipment
requirements
Nitrogen blanketing
Even where water is present, corrosion can be prevented by eliminating oxygen from the environment.
Oxygen can be eliminated by sealing and pressurizing the entire boiler, or the space above water level,
with nitrogen to prevent air in-leakage. In the absence
of acids and other oxidants, eliminating air stops corrosion. Nitrogen blanketing is a highly effective
method for preventing corrosion. It is easy to monitor
and alarm, so effective preservation can be assured.
However, the boiler must be well sealed to prevent
excessive leakage.
It is absolutely imperative that working spaces
around nitrogen blanketed equipment be well ventilated. Venting of nitrogen during purging or water
filling operations can release large amounts of nitrogen into surrounding areas. Also, before entry, areas
that have been nitrogen blanketed must be well ventilated and the air tested to confirm that all parts have
adequate oxygen concentrations.
Wet (water-filled) layup
Wet layup in combination with nitrogen blanketing is often the most practical method of protection,
especially for boilers that are not fully or easily
drainable. However, for longer storage periods, advantages of wet layup are offset by accumulative corrosion in areas of valve seepage and by accumulative
cost of replacement water, chemicals, treated water
disposal, nitrogen cover gas, and heat in cold climates.
Consequently, dry layup is generally recommended for
storage periods longer than six months.
Before a boiler is flooded with layup water, provision
must be made to support the additional weight when
drum (if present), superheater, and steam piping are
filled. If the boiler is to be completely filled with layup
water, an expansion tank or surge tank above the highest vent is necessary to accommodate volume changes
that are caused by normal temperature fluctuations.
The expansion space at the top of the boiler (whether
in a drum or in a surge tank) should be nitrogen blanketed to assure that there is no air ingress. Where freezing conditions are expected or possible, provision must
be made for heating water-filled components.
Wet layup generally requires demineralized water
having a specific conductivity less than 1.0 S/cm before treatment chemicals are added. Use of demineralized water and all volatile treatment chemicals is
essential where boilers include non-drainable or stainless steel components. Use ammonium hydroxide to
raise water pH into the range of 10.0 to 10.4. Use an
oxygen scavenger/inhibitor to further retard corrosion.
Dry (dehumidified) layup
Dry layup requires the removal of all water and the
dehumidification of air to maintain a relative humidity less than 50%, and preferably less than 40%. This
prevents corrosion by hygroscopic salts. Dry-air (dehumidified) storage is highly effective, and its continued effectiveness is easy to monitor. Dry layup allows
easy and safe access for maintenance, with no potential for suffocation and no exposure to toxic chemicals.
42-27
References
1. Klein, H.A., and Rice, J.K., A research study on internal corrosion in high pressure boilers, Journal of Engineering for Power, Vol. 88, No. 3, pp. 232-242, July, 1966.
2. Cohen, P., Ed., The ASME Handbook on Water Technology in Thermal Power Systems, The American Society of Mechanical Engineers, New York, New York, 1989.
3. Consensus on Operating Practices for the Control of
Feedwater and Boiler Water Quality in Modern Industrial
Boilers, The American Society of Mechanical Engineers,
New York, New York, 1994.
4. Interim consensus guidelines on fossil plant cycle
chemistry, Report CS-4629, Electric Power Research Institute, Palo Alto, California, June, 1986.
5. Guideline for Boiler Feedwater, Boiler Water, and
Steam of Steam Generators with a Permissible Operating Pressure > 68 bar, VGB PowerTech e.V., Essen, Germany, VGB-R 450 Le, (in German), 1988.
6. Betz Handbook of Industrial Water Conditioning,
Ninth Ed., Betz Laboratories, Trevose, Pennsylvania, September, 1991.
7. Drew Principles of Industrial Water Treatment, 11th
Ed., Drew Industrial Division, Ashland Chemical Co.,
Boonton, New Jersey, 1994.
8. Kemmer, F.N., Ed., The Nalco Water Handbook, Second Ed., McGraw-Hill, New York, New York, 1988.
9. Macbeth, R.V., et al., UKAEA Report No. AAEW-R711,
Winfrith, Dorchester, United Kingdom, 1971.
10. Goldstein, P., and Burton, C.L., A research study on
internal corrosion of high-pressure boilers final report,
Journal of Engineering for Power, Vol. 91, pp. 75-101,
April, 1969.
42-28
11. Freier, R.K., Cover layer formation on steel by oxygen in neutral salt free water, VGB Speiserwassertagung
1969 Sunderheft, pp. 11-17 (in German), 1969.
12. Whirl, S.F., and Purcell, T.E., Protection against
caustic embrittlement by coordinated pH control, Third
Annual Meeting of the Water Conference of the Engineers
Society of Western Pennsylvania, Pittsburgh, Pennsylvania, 1942.
13. Stodola, J., Review of boiler water alkalinity control,
Proceedings of the 47th Annual Meeting of The International Water Conference, Pittsburgh, Pennsylvania, pp.
235-242, October 27-29, 1986.
14. Economy, G., et al., Sodium phosphate solutions at
boiler conditions: solubility, phase equilibrium and interactions with magnetite, Proceedings of the International
Water Technology Conference, Pittsburgh, Pennsylvania,
pp. 161-173, 1975.
15. Tremaine, P., et al., Interactions of sodium phosphate
salts with transitional metal oxides at 360C, Proceedings
of the International Conference on Interaction of Iron
Based Materials with Water and Steam, Heidelberg, Germany, June 3-5, 1992.
16. Martynova, O.I., Transport and concentration processes of steam and water impurities in steam generating
systems, Water and Steam: Their Properties and Current Industrial Applications, J. Staub and K. Scheffler,
Eds., Pergamon Press, Oxford, United Kingdom, pp. 547562, 1980.
17. Nagda, N.L. and Harper, J.P., Monitoring Water in
the 1990s: Meeting New Challenges, STPl102, American
Society for Testing and Materials, Philadelphia, Pennsylvania, 1991.
24. Port, R.D., and Herro, H.M., The Nalco Guide to Boiler
Failure Analysis, McGraw-Hill Company, New York, New
York, 1991.
25. Dooley, R.B., and McNaughton, W.P., Boiler Tube
Failures: Theory and Practice, Electric Power Research
Institute, Palo Alto, California, 1996. LICENSED MATERIAL available to EPRI members.
26. Annual Book of ASTM Standards, Section 11, Water
and Environmental Technology, Vols. 11.01 and 11.02,
American Society for Testing and Materials, Philadelphia,
Pennsylvania, 2003.
27. Wackenhuth, E.C., et al., Manual on chemical cleaning of fossil-fuel steam generating equipment, Report CS3289, Electric Power Research Institute, Palo Alto, California, 1984.
28. Samuelson, M.L., McConnell, S.B., and Hoy, E.F., An
on-site chemical treatment for removing iron and copper
from chelant cleaning wastes, Proceedings of the 49th International Water Conference, Pittsburgh, Pennsylvania,
p. 380,1988.
29. Nalmet heavy metal removal program, Nalco Chemical Company, Naperville, Illinois, February, 1989.
42-29
42-30