You are on page 1of 6

GX20 Flow Calculation Software GX3.

03a
UL: EX5045 FM: PI 3022566
Project: Hotel
File Name: Qtel Room.FLC

Consolidated Report
Customer Information
Company Name: Zukhrof Trading & Contracting.
Address:

Phone:
Contact:
Title:

Project Data
Project Name:
Designer:
Number:
Account:
Location:
Description:

Hotel
Aleem

Qtel Room
Rev - 0

Page:
1 of 6
Calculation Date/Time: Monday, March 02, 2015, 11:12:37 AM
Copyright (c) Hughes Associates, Inc. Licensed to: Kidde-Fenwal

Consolidated Report
Enclosure Information
Elevation:
Atmospheric Correction Factor:
Enclosure Number:
Name:
Enclosure Temperature...
Minimum:
Maximum:
Maximum Concentration:
Design Concentration...
Adjusted:
Minimum:
Minimum Agent Required:
Width:
Length:
Height:

0 m (relative to sea level)


1
1
Room
21.0 C
21.0 C
7.278 %
7.277 %
7.000 %
9.2 kg
3.03 m
1.77 m
3.10 m

Volume:
Non-permeable:

16.63 cubic m
0.00 cubic m

Total Volume:

16.63 cubic m

Adjusted Agent Required:


Number of Nozzles:

9.5 kg
1

Page:
2 of 6
Calculation Date/Time: Monday, March 02, 2015, 11:12:37 AM
Copyright (c) Hughes Associates, Inc. Licensed to: Kidde-Fenwal

Consolidated Report
Agent Information

Agent: FM-200 / Propellant N2


(FM-200 is a Trademark of Great Lakes Chemical Corp.)
Adjusted Agent Required:
Container Name:
Container Part Number:
Number of Main Containers:
Number of Reserve Containers:
Manifold:

9.5 kg
8 L Cylinder
E7763-102-01-EU
1
0
No Manifold

Pipe Take Off Direction:


Agent Per Container:
Fill Density:
Container Empty Weight:
Weight, All Containers + Agent:
Floor Area Per Container:
Floor Loading Per Container:

Horizontal
9.5 kg
1.007 kg / l
14.0 kg
23.5 kg
0.03 square m
783 kg /square m

Pipe Network
Part 1 - Pipe
Diameter

Pipe
Length

Elevation

40 mm

0.51 m

0.51 m

40 mm

0.07 m

0.00 m

Pipe

40T

20 mm

0.20 m

0.00 m

Pipe

40T

20 mm

2.46 m

2.46 m

Pipe

40T

20 mm

0.80 m

0.00 m

Pipe

40T

20 mm

0.45 m

0.00 m

Pipe/E1-N1

40T

20 mm

0.10 m

-0.10 m

Description

Start

End

Main Cyl. X 1

Adapter

Type

Part 2 - Equivalent Length


Start

End

Side Union Other

90

45

Thru

Added

Total

0.00 m

15.24 m

0 40mm VOA

0.00 m

3.60 m

0.00 m

0.21 m

0.00 m

3.14 m

Page:
3 of 6
Calculation Date/Time: Monday, March 02, 2015, 11:12:37 AM
Copyright (c) Hughes Associates, Inc. Licensed to: Kidde-Fenwal

Consolidated Report
Part 2 - Equivalent Length
Start

End

Side Union Other

90

45

Thru

Added

Total

0.00 m

1.46 m

0.00 m

1.13 m

0.00 m

0.76 m

Part 3 - Nozzles
Start
0

End
1

Flow
9.5 kg

9.5 kg

9.5 kg

9.5 kg

9.5 kg

9.5 kg

9.5 kg

Name

Size

Type

Nozzle Area

E1-N1

20 mm

180

123.16 square mm

Parts Information

Total Agent Required: 9.5 kg


Container Name: 8 L Cylinder (Part: E7763-102-01-EU)
Number Of Containers: 1
Nozzle

Type

Nozzle Area

Part Number

E1-N1

180

123.16 square mm

1-C3333-302-27

Pipe:

Type

Diameter

Length

40T

20 mm

4.01 m

'Other' Items:
1 - 40 mm Valve Outlet Adapter (Part: 1-K63497-02)
List of 90 degree elbows:
4 - 20 mm

System Acceptance
System Discharge Time: 8.0 seconds
Percent Agent In Pipe: 28.6%
Percent Agent Before First Tee: 0.0%
Enclosure Number:

Page:
4 of 6
Calculation Date/Time: Monday, March 02, 2015, 11:12:37 AM
Copyright (c) Hughes Associates, Inc. Licensed to: Kidde-Fenwal

Consolidated Report
Enclosure Name: Room
Minimum Design Concentration:
Adjusted Design Concentration:
Predicted Concentration:
Maximum Expected Agent Concentration:

Nozzle
E1-N1

Minimum
Agent
Required
9.2 kg

7.000%
7.277%
7.278%
7.278% (At 21.0 C)

Adjusted
Agent
Required

Predicted
Agent
Delivered

9.5 kg

9.5 kg

Nozzle
Pressure
(Average)
8.405 bar

Standard Isometric View

Page:
5 of 6
Calculation Date/Time: Monday, March 02, 2015, 11:12:37 AM
Copyright (c) Hughes Associates, Inc. Licensed to: Kidde-Fenwal

Consolidated Report
Standard Plan View

Standard Elevation View

Page:
6 of 6
Calculation Date/Time: Monday, March 02, 2015, 11:12:37 AM
Copyright (c) Hughes Associates, Inc. Licensed to: Kidde-Fenwal

You might also like