Professional Documents
Culture Documents
PRESENTATION
Dims:
W x H. 96 x 96mm (front)
W x H. 89.5 x 89.5mm (main body)
L. 100mm
FUNCTION OVERVIEW
Programming mode.
START
IO 0.00A
TOROID RATIO
Set ratio of externally
connected toroid
NETWORK
FREQUENCY
Set for 50 or 60Hz
connected toroids
1. LCD (Liquid Crystal Display) for user information
2. RESET button
3. TEST button
4. Power supply green LED indication
RELAY 1 SETTING
Set reset mode
method
5. MODE button*
6. Parameter increment button*
7. Parameter decrement button*
8. Trip status red LED indication
* accessible only when the front cover is open
RELAY 2 SETTING
Assign relay activation and
reset mode methods
EARTH FAULT
CURRENT SETTING
Set Low-set and High-set
tripping parameters
A clear backlit LCD provides all the key information that the user requires for both operation
and the setting up. Setting is achieved in a few simple steps and requires no previous
knowledge of product operation.
SUMMARY1
List all parameter and
function settings
Normal operation provides the user with the actual live earth fault current on one screen. The
actual current represents that of the current passing through the primary side of the externally
connected CT. This is achieved by the setting of the ratio for the CT.
Programming mode allows the user to assign the operation of both internal relays for either
Auto or Manual resetting. Relay 2 has the added option of being allowed to energise at the
start or end of a time out period. If assigned to energise at the start, the Relay can be used to
operate a buzzer or lamp giving early warning before a system actually shuts down.
Programmable parameters
User settings summary mode
START
Display live
earth fault
current
Low-set and High-set thresholds can be programmed for the Earth fault detection. The time
current characteristic of the low-set units are selectable between Normal Inverse curve 3/10,
Normal Inverse curve 1.3/10, Long Time Inverse curve, Very Inverse curve, Extremely
Inverse curve, Extremely Inverse 0.65 curve and Definite Time. High-set units are the
Definitive Time type. Instantaneous tripping is possible by setting the time to minimum.
A simple Summary screen is displayed once the programming is complete. The same screen
can also be displayed by subsequent presses of the RESET button. This allows the user to
access key information with the tamperproof transparent cover closed and sealed.
A Test mode is provided (also accessible with the tamperproof transparent cover closed) to
confirm the correct operation of the internal relays. The relays will energise when the TEST
button is pressed and de-energise when the button is released (AUTO Reset) or when the
RESET button is pressed (MAN reset).
SUMMARY1
List all parameter and
function settings
1
Displaying of the Summary screen during normal operation is achieved via subsequent
presses of the RESET button. See Section 7. QUICK VIEW OF USER SETTINGS for further
information.
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the users own risk.
P9660-1-A 1
012378
INSTALLATION
Installation work must be carried
out by qualified personnel.
The front window of the P9660 is supplied with a clear protective film which
can be removed as and when necessary.
^ When carrying out future maintenance on the product or application and it
becomes necessary to disconnect the connectors from the product, ensure for
the Current Transformer connector, they do not remain open circuit.
circuit This can
lead to high voltages being present on this connector.
PROGRAMMING
The
button selects the required parameter to be changed. The
buttons either increment or decrement a value accordingly.
Any adjustments made are stored by the pressing and holding of the
button
until the LCD shows the word Saved!
Saved!
Saved! See Section 6. SAVING OF SETTINGS.
Please read the Notes during programming before commencing with the
following.
1A. TOROID RATIO
Setting the Toroid Ratio will allow the actual Earth fault current (Io) to be
displayed on the LCD which represents that of the current flowing through the
parallel connected, external CTs. If no CTs are used, the parameter should be
set to 5/5 (i.e. 1:1). Use this if the fault current is likely to be <5A.
Default setting is 5/5
TOROID RATIO
5/5
NORMAL OPERATION
Apply power to the unit and the green Power supply LED will illuminate.
The LCD will momentarily display a welcome screen as shown
Model No.
Version
TYPE: P9660
Ver: X.X
Press either
or
Whilst in the same screen as that for the Toroid Ratio (see 1A.), press
the
Actual Earth
fault current
IO 0.00A
NETWORK FREQUENCY
50Hz
60Hz
Press either
or
to select between 50Hz or 60Hz. This should be
set to suit the frequency of the network being monitored.
TEST MODE
2. RELAY 1 SETTING
TEST
TYPE: P9660
Ver: X.X
Release the
button and the relay(s) will remain energised if set to Manual
reset or de-energise if set to Auto reset.
Press the
to de-energise relay(s) which are set to Manual reset. The
LCD will revert back to Normal operation. The LCD backlight and red
Trip LED will stop flashing.
RELAY 1 CONFIGURATION
AUTO
MAN
Testing should be carried out on a regular basis to check the integrity of the
P9660.
Press either
or
to select between AUTO resetting or MANUAL
MAN
resetting (after a fault has occurred).
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the users own risk.
P9660-1-A 2
012378
PROGRAMMING (continued)
3. RELAY 2 SETTING
Default setting for Relay 2 is to energise at the end of the time out period.
Resetting mode is Auto.
Press the same button again to display the Last Tripped Information screen
(refer to the next section for further information on this feature).
Press again to display the Earth Fault Summary screen.
Press again to display the contact details for Broyce Control.
Press again to revert back to Normal operation.
IO 5.90A Io>
R1 R2
Default settings for Earth Fault are shown in the LCD screen example in this
section.
Settings for Earth fault are displayed in turn following subsequent presses of
the
E/F SETTING
Low Set:
1: Io> 2.00A
holding the
Press either
Press the
or
and
button briefly.
TRIPPING MODE
Relays that
were
activated at
trip
or
for >1sec. will increment or
decrement the new value at a quicker rate.
Stepping through each User Setting screen is performed by pressing and
Level which
was triggered
(i.e. Low-set)
When an Earth fault condition occurs, the current displayed on the LCD
increased accordingly. When the level of current exceeds the Low-set setting,
the reading will be highlighted by the digits flashing.
The LCD backlight will flash.
Relay 2 will energise immediately if set to energise at the start of the time out
period (See Section 3. RELAY 2 SETTING).
The characters Io> will display to indicate the Low-set has been triggered.
If the Curve in selection 2: is set to Definite Time, then selection 3: will
display 3: t> and the required delay can then be set.
If High-set is set to Disable in selection 4:, then Io>> or to>> cannot be
adjusted.
IO 3.60A Io>
Low-set
triggered
E/F SUMMARY
Io> 2.00A
NI 3/10
ko> 0.1
Io>>10.0A
to>>0.05s
R1 = MAN R2 = AUTO (E)
CT=5:5, FREQ=50Hz
6. SAVING OF SETTINGS
If after viewing the Summary screen the settings are correct, press and hold
the
button until the word Saved.
Saved. appears. Any new settings are now
stored.
The screen will revert back to Normal operation.
It is not possible to edit settings when these screens are displayed.
This feature can also be activated with the front window closed!
Following the setting of Earth Fault, the LCD displays the Earth Fault
screen showing a summary of the settings made during programming. All
settings are displayed. The selected CT ratio, Network Frequency and Relay
operation (following a Reset) information is also displayed.
If the current continues to increase above the High-set setting, the characters
Io> will change and display Io>> to indicate the High-set has been
triggered.
IO 13.00A Io>>
R1
High-set
triggered
Relay(s) which
energised on
tripping
When the unit finally trips, the digits will stop flashing and remain highlighted.
This allows the user to see what current caused the unit to trip.
The red Tripped LED will also flash.
The relays which energised are also displayed on the screen after tripping.
Press
to reset and return the unit back to normal operation (assuming
the fault has been cleared). The LCD reverts back to displaying the normal
system currents and the red Tripped LED stops flashing.
If either relay is set for Auto resetting, then they would have de-energised after
the fault had cleared. The corresponding relay ident (i.e. R1 and/or R2) on the
display would also disappear. Pressing the RESET button will only clear the
LCD. If either relay is set for Manual resetting, then pressing the RESET button
will de-energise the relay(s) and clear the LCD.
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the users own risk.
P9660-1-A 3
012378
t (s)
t t(s)
(s)
10
k
1.0
0.9
0.8
0.7
0.6
0.5
k0.4
1.0
0.9
0.8
0.7
0.6
0.5
1.0
0.3
0.9
0.4
0.4
0.1
0.3
0.8
0.7
0.2
0.6
0.5
0.1
0.3
0.2
t (s)
200
100
10
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.05
0.2
1
0.1
0.1
0.1
0.05
0.05
0.05
0.01
0.1
1
10
20
10
0.1.
1
20
t (s)
t (s)
20
I/I>
10
I/I>
I/I>
1000
100
100
10
10
10
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
1.0 k
0.1
0.1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.1
1.0
0.1
0.05
0.6
0.5
0.05
0.1
0.9
0.8
0.7
0.4
0.3
0.2
0.2
0.1
0.01
10
0.01
20
0.01
1
10
I/I>
20
10
20
I/I>
I/I>
I/I>
* Abbreviations used in the LCD screen for the selected IDMT characteristic curve.
The sequence of curves that are presented to the user when programming is shown below
NI 3/10
NI 1.3/10
LTI
VI
EI
EI 0.65
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the users own risk.
P9660-1-A 4
012378
TECHNICAL SPECIFICATION
Supply voltage Un (1, 2):
85 265VAC/85 - 370VDC
18 57VAC/18 75VDC
Electrical life:
Dielectric voltage:
Rated impulse
withstand voltage:
5A (directly connected)
50/60Hz
<0.4VA @ In
4 x In (continuous)
External CT (15,16):
Maximum CT primary
current rating:
5%
5% (with a minimum of 50mS)
5% (with a minimum of 50mS and I > 1.2 x
set-trip)
1% of rated current In
<1 sec.
0.5% @ constant conditions
Ambient temperature:
Relative humidity:
-10 to +60C
+95%
Electrical Endurance
Housing:
Protection:
Weight:
Mounting:
Max. panel thickness:
Terminal type:
4.4in lb (0.5Nm)
0.24 0.30in (6 7.5mm)
Conforms to IEC. CE and
and RoHS Compliant.
EMC: Immunity: EN/IEC 61000-6-2
Emissions: EN/IEC 61000-6-4
Generic: IEC 60255-26 (EMC), IEC 255-3, IEC
60255-151
( ) Bold digits in brackets refer to terminal numbers on the rear of the unit.
Options:
Output:
(RL1 - 3, 4, 5):
(RL2 - 6, 7, 8):
Output rating:
1 x SPDT relay
1 x SPDT relay
AC1 250V 8A (2000VA)
AC15 250V 5A (1250VA)
DC1 25V 8A (200W)
The P9600 range also includes combined Overcurrent or Earth fault relays
available with either IDMT or DT characteristics. Additionally, a voltage, power
and frequency monitoring only product is also available. Please refer to separate
data sheets.
DIMENSIONS
CONNECTION DIAGRAM
Aux.
A1
A2
10
96
1 2
3 4 5 6 7 8
RL1
RL2
IN
9 10 11 12 13 14 15 16
L1
L2
L3
N
100
96
Front view
96
MADE IN U.K.
89.5
Side view
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the users own risk.
P9660-1-A 5
012378