Structural
Robinson
Meier
Juilly & Associates
Principals
Peter Robinson, S.E.
Jayson E. Haines, S.E.
Netshelter SX,
AR3100
Structural Calculations
For Seismic Anchorage
Prepared for:
APC Corp.
January 27, 2006
RMJ Job No. 05240
Page 1
Netshelter SX
AR3100
Table of Contents
Description
Page
Project Description................................................1
Zone 4 (California) Summary Flowchart........... 2-3
Zone 0-3 (Non-CA) Summary Flowchart......... 4-5
Installation Details ...................................................
Single Unit Installation Plan ................................6
Ganged Unit Installation Plan ............................7
Concrete Slab Installation Detail ........................8
Conc. Fill Over Mtl. Deck Installation Detail ...............9
Raised Computer Floor Installation Detail ..................... 10
Calculations Zone 4 .............................................
Single Unit,Ground Floor............................. 11-12
Ganged Unit, Ground Floor ........................ 13-15
Single Unit, <50% of building ..................... 16-17
Ganged Unit, <50% of building.................. 18-20
Ganged Unit, <90% of building.................. 21-24
Worst Case Bracket .............................................25
Calculations Zone 0-3..........................................
Single Unit,Ground Floor............................. 26-27
Ganged Unit, Ground Floor ........................ 28-30
Single Unit, <50% of building ..................... 31-32
Ganged Unit, <50% of building.................. 33-35
Single Unit, <90% of building ..................... 36-37
Ganged Unit, <90% of building.................. 38-41
Worst Case Bracket .............................................42
1/27/2006
2
Single Netshelter SX
AR3100 Unit
Ground Floor
>0%, <50% of
building height
Concrete Slab
(4" min)
no computer
floor
(2000# LOAD)
no computer
floor
(2000# LOAD)
USE
(4)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 2.5"
>50% of
building height
USE
SITE SPECIFIC
ENGINEERING
REQUIRED
USE
(8)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 1-5/8",
NOTE: (1) APC 870-11101A pallette bracket may be used in lieu of (2) APC7701 brackets
: RAISED FLOORS >18"REQUIRE SITE SPECIFIC ENGINEERING
1/27/2006
3
Ground Floor
>0%,< 50% of
building height
Concrete Slab
(4" min)
18" raised
computer floor
(4000# LOAD)
no computer
floor
(4000# LOAD)
USE
(4)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 2.5"
18" raised
computer floor
(4000# LOAD)
>50% of
building height
no computer
floor
(4000# LOAD)
USE
(8)AR7701 Brackets w/
3/8" diameter Kwik Bolt
3, Embed. 1-5/8"
18" raised
computer floor
USE
SITE SPECIFIC
ENGINEERING
REQUIRED
no computer floor
(4000# LOAD)
USE
(8)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 1-5/8",
NOTE: (1) APC 870-11101A pallette bracket may be used in lieu of (2) APC7701 brackets
: RAISED FLOORS >18"REQUIRE SITE SPECIFIC ENGINEERING
1/27/2006
4
Single Netshelter SX
AR3100 Unit
Ground Floor
>0%, <50% of
building height
>50% of
building height
Concrete Slab
(4" min)
no computer
floor
(2000# LOAD)
no computer
floor
(2000# LOAD)
no computer
floor
(2000# LOAD)
USE
(4)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 2.5"
USE
USE
(4)AR7701 Brackets w/
(4)AR7701 Brackets w/
NOTE: (1) APC 870-11101A pallette bracket may be used in lieu of (2) APC7701 brackets
: RAISED FLOORS >18"REQUIRE SITE SPECIFIC ENGINEERING
1/27/2006
5
Ground Floor
>0%,< 50% of
building height
Concrete Slab
(4" min)
18" raised
computer floor
(4000# LOAD)
no computer
floor
(4000# LOAD)
USE
(4)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 2.5"
18" raised
computer floor
(4000# LOAD)
no computer
floor
(4000# LOAD)
USE
(4)AR7701 Brackets w/
3/8" diameter Kwik Bolt
3, Embed. 1-5/8"
>50% of
building height
18" raised
computer floor
no computer floor
(4000# LOAD)
USE
(8)AR7701 Brackets w/
3/8" diameter Hilti Kwik
Bolt 3, Embed. 1-5/8",
NOTE: (1) APC 870-11101A pallette bracket may be used in lieu of (2) APC7701 brackets
: RAISED FLOORS >18"REQUIRE SITE SPECIFIC ENGINEERING
Date:
Page:
1/27/2006
11
23.6
42.1
77
Seismic Force
(Zone 4, N a=1.5,
Ca =
0.66
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
Ip =
1.0
(Importance)
AR3100
Frame
275.2
11.8
21.05
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.0
(Floor)
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
2000
9.65
30.6
38.5
Fp =
0.157
Fp,min =
0.33
Fp,max =
1.89
Use Fp =
0.33
(internal brackets)
Longitudinal Overturning
Overturning
Moment =
28906
lb-in
0.9xResisting
Moment =
24163
lb-in
Anchorage Force =
Shear Force =
491.6
750.8
lbs
lbs.
Netshelter SX Unit
Plan
23.6 in.
Design Bolts for 491.6 lbs tension, 750.8 lbs. shear, longitudinal direction, fully loaded
Netshelter SX Unit
Plan
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
28906
lb-in
43104
lb-in
Anchorage Force =
Shear Force =
0
750.8
lbs
lbs.
Seismic
Force (Fp)
42.1 in.
23.6 in.
Design Bolts for 0 lbs tension, 750.8 lbs. shear, transverse direction, fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
1/27/2006
12
Load Cases:
AR3100 Single Fully Loaded Unit (Ground Floor)
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
491.6
SHEAR FORCE
(LBS.)
750.8
ANCHORAGE DESIGN
4
0.375
2.5
6.67
shallow anchor, increase load per UBC 1632.2
3.75 in. slab, min.
712
1255
983.2/1898.6 =
Shear
1501.6/3346.6 =
0.52
0.45
SUMMARY
CONCRETE:
3.75 in. slab, min. Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385), embed. 2.5 in.
Use 4 brackets total, one anchor/bracket
11:31 AM
1/27/2006
Date:
1/27/2006
Page:
13
Seismic Force
(Zone 4, N a=1.5,
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
38.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.66
Ip =
1.0
(Importance)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.0
(Floor)
Fp =
0.157
(2000lbs.x 2units)
Fp,min =
0.33
33
30.6
Fp,max =
1.89
Use Fp =
0.33
4000
38.5
(internal brackets)
Longitudinal Overturning
Overturning
Moment =
57813
lb-in
0.9xResisting
Moment =
96650
lb-in
Netshelter SX
plan
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1501.6 lbs.
Design Bolts for 0 lbs tension, 1501.6 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
57813
lb-in
0.9xResisting
Moment =
86207
lb-in
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1501.6 lbs.
Netshelter SX
plan
Design Bolts for 0 lbs tension, 1501.6 lbs. shear, transverse direction, ganged fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
Date:
1/27/2006
Page:
Load Case: Ganged Fully Loaded Unit (On 18" raised computer floor, Ground Floor)
14
Seismic Force
(Zone 4, N a=1.5,
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
56.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.66
Ip =
1.0
(Importance)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.0
(Floor)
Fp =
0.157
(2000lbs.x 2units)
Fp,min =
0.33
33
30.6
Fp,max =
1.89
Use Fp =
0.33
4000
56.5
Longitudinal Overturning
Overturning
Moment =
84842
lb-in
0.9xResisting
Moment =
96650
lb-in
Netshelter SX
plan
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1501.6 lbs.
Design Bolts for 0 lbs tension, 1501.6 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
84842
lb-in
0.9xResisting
Moment =
86207
lb-in
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1501.6 lbs.
Netshelter SX
plan
Design Bolts for 0 lbs tension, 1501.6 lbs. shear, transverse direction, ganged fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
1/27/2006
15
ANCHORAGE
FORCE (LBS.)
SHEAR FORCE
(LBS.)
GANGED UNIT
1501.6
ANCHORAGE DESIGN
4
0.375
2.5
6.67
shallow anchor, increase load per UBC 1632.2
3.75 in. slab, min.
712
1255
0.0/1898.6 =
Shear
3003.3/6693.2 =
0.00
0.45
SUMMARY
CONCRETE:
3.75 in. slab, min. Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385), embed. 2.5 in.
Use 4 brackets total, one anchor/bracket
11:31 AM
1/27/2006
Date:
1/27/2006
Page:
16
AR3100
Frame
275.2
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
11.8
21.05
2000
9.65
30.6
38.5
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.5
Fp =
0.393
Fp,min =
0.33
Fp,max =
1.89
Use Fp =
0.39
Longitudinal Overturning
Overturning
Moment =
34412
lb-in
0.9xResisting
Moment =
24163
lb-in
Netshelter SX Unit
Plan
Anchorage Force =
Shear Force =
42.1 in.
1062.2 lbs
750.8 lbs.
23.6 in.
Design Bolts for 1062.2 lbs tension, 750.8 lbs. shear, longitudinal direction, fully loaded
Netshelter SX Unit
Plan
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
34412
lb-in
43104
lb-in
Anchorage Force =
Shear Force =
0
750.8
lbs
lbs.
Seismic
Force (Fp)
42.1 in.
23.6 in.
Design Bolts for 0 lbs tension, 750.8 lbs. shear, transverse direction, fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
1/27/2006
Page:
17
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
1062.2
SHEAR FORCE
(LBS.)
750.8
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 8
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.750
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.67
Min. Conc Slab Thickness (1.5x embed. Length) 2.625 in. slab, min.
423
1062
2124.4/2256.0 =
Shear
1501.6/5664.0 =
0.94
0.27
564.0
1416.0
11:31 AM
1/27/2006
Date:
1/27/2006
Page:
18
Seismic Force
(Zone 4, N a=1.5,
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
46.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.66
Ip =
1.0
(Importance)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.5
(Floor)
Fp =
0.393
(2000lbs.x 2units)
Fp,min =
0.33
32.95
30.6
Fp,max =
1.89
Use Fp =
0.39
4000
46.5
Longitudinal Overturning
Overturning
Moment =
83126
lb-in
0.9xResisting
Moment =
96650
lb-in
Netshelter SX
plan
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1787.7 lbs.
Design Bolts for 0 lbs tension, 1787.7 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
83126
lb-in
0.9xResisting
Moment =
86207
lb-in
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1787.7 lbs.
Netshelter SX
plan
Design Bolts for 0 lbs tension, 1787.7 lbs. shear, transverse direction, ganged fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
Date:
1/27/2006
Page:
19
Seismic Force
(Zone 4, N a=1.5,
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
56.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.66
Ip =
1.0
(Importance)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.5
(Floor)
Fp =
0.393
(2000lbs.x 2units)
Fp,min =
0.33
32.95
30.6
Fp,max =
1.89
Use Fp =
0.39
4000
56.5
Longitudinal Overturning
Overturning
Moment =
0.9xResisting
Moment =
101003 lb-in
Netshelter SX
plan
Seismic Force
96650
lb-in
2 ganged units
Anchorage Force =
Shear Force =
132.1 lbs
1787.7 lbs.
Design Bolts for 132.1 lbs tension, 1787.7 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
Seismic Force
101003 lb-in
86207
lb-in
2 ganged units
Anchorage Force =
Shear Force =
483.5 lbs
1787.7 lbs.
Netshelter SX
plan
Design Bolts for 483.5 lbs tension, 1787.7 lbs. shear, transverse direction, ganged fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
1/27/2006
20
Load Cases:
Ganged Fully Loaded Unit (<=50% OF BUILDING HEIGHT)
Ganged Fully Loaded Unit (On 18" RAISED COMPUTER FLOOR SYSTEM, <=50% OF BUILDING HEIGHT)
ANCHORAGE FORCES
CONDITION
ANCHORAGE
FORCE (LBS.)
SHEAR FORCE
(LBS.)
GANGED UNIT
483.5
1787.7
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 8
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.750
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.67
Min. Conc Slab Thickness (1.5x embed. Length) 2.6 in. conc. cover, min.
423
1062
967.0/2256.0 =
Shear
3575.3/5664.0 =
0.43
0.63
SUMMARY:
CONC. FILL OVER METAL DECK:
2.6 in. conc. cover, min. Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385), embed. 1.75 in.
Use 8 brackets total, one anchor/bracket
11:31 AM
1/27/2006
Date:
1/27/2006
Page:
21
Seismic Force
(Zone 4, N a=1.5,
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
38.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.66
Ip =
1.0
(Importance)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.9
Fp =
0.581
(2000lbs.x 2units)
Fp,min =
0.33
23.6
30.6
Fp,max =
1.89
Use Fp =
0.58
4000
38.5
Longitudinal Overturning
Overturning
Moment =
0.9xResisting
Moment =
101861 lb-in
Netshelter SX
plan
Seismic Force
96650
lb-in
2 ganged units
Anchorage Force =
Shear Force =
220.8 lbs
2645.7 lbs.
Design Bolts for 220.8 lbs tension, 2645.7 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
Seismic Force
101861 lb-in
86207
lb-in
2 ganged units
Anchorage Force =
Shear Force =
511.5 lbs
2645.7 lbs.
Netshelter SX
plan
Design Bolts for 511.5 lbs tension, 2645.7 lbs. shear, transverse direction, ganged fully loaded
11:43 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
1/27/2006
22
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
511.5
SHEAR FORCE
(LBS.)
2645.7
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 8
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.625
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.33
Min. Conc Slab Thickness (1.5x embed. Length) 2.4 in. conc. cover, min.
423
1062
1023.0/2256.0 =
Shear
5291.5/5664.0 =
0.45
0.93
564.0
1416.0
11:31 AM
1/27/2006
Date:
1/27/2006
Page:
23
Seismic Force
(Zone 4, N a=1.5,
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
56.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.66
Ip =
1.0
(Importance)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.9
Fp =
0.581
(2000lbs.x 2units)
Fp,min =
0.33
23.6
30.6
Fp,max =
1.89
Use Fp =
0.58
4000
56.5
Longitudinal Overturning
Overturning
Moment =
0.9xResisting
Moment =
149484 lb-in
Netshelter SX
plan
Seismic Force
96650
lb-in
2 ganged units
Anchorage Force =
Shear Force =
2238.7 lbs
2645.7 lbs.
Design Bolts for 2238.7 lbs tension, 2645.7 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
Seismic Force
149484 lb-in
86207
lb-in
2 ganged units
Anchorage Force =
Shear Force =
2067.9 lbs
2645.7 lbs.
Netshelter SX
plan
Design Bolts for 2067.9 lbs tension, 2645.7 lbs. shear, transverse direction, ganged fully loaded
11:51 AM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 4 (California).xls
1/27/2006
24
Load Cases:
Ganged Fully Loaded Unit
(On 18" RAISED COMPUTER FLOOR SYSTEM, <=90% OF BUILDING HEIGHT)
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
2238.7
SHEAR FORCE
(LBS.)
2645.7
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 8
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.625
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.33
Min. Conc Slab Thickness (1.5x embed. Length) 2.4 in. conc. cover, min.
826
1062
4477.4/4405.2 =
Shear
5291.5/5664.0 =
1.02
0.93
1101.3
1416.0
11:31 AM
1/27/2006
2239
4
560
1.05
294
Sx (in3) =
0.0066
44.52
50
1/27/2006
25
Tension Force
1.05 in
NOTE: (1) APC 870-11101A pallette bracket may be used in lieu of (2) APC7701 brackets
11:31 AM
1/27/2006
Date:
Page:
1/27/2006
26
23.6
42.1
77
Seismic Force
Center of Gravity Location
Ca =
0.28
(Zone 0-3)
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
Ip =
1.0
(Importance)
AR3100
Frame
275.2
11.8
21.05
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.0
(Floor)
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
2000
9.65
30.6
38.5
Fp =
0.067
Fp,min =
0.14
Fp,max =
0.80
Use Fp =
0.14
(internal brackets)
Longitudinal Overturning
Overturning
Moment =
12263
lb-in
0.9xResisting
Moment =
24163
lb-in
Anchorage Force =
Shear Force =
0
318.5
lbs
lbs.
Netshelter SX Unit
Plan
23.6 in.
Design Bolts for 0 lbs tension, 318.5 lbs. shear, longitudinal direction, fully loaded
Netshelter SX Unit
Plan
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
12263
lb-in
43104
lb-in
Anchorage Force =
Shear Force =
0
318.5
lbs
lbs.
Seismic
Force (Fp)
42.1 in.
23.6 in.
Design Bolts for 0 lbs tension, 318.5 lbs. shear, transverse direction, fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
27
Load Cases:
AR3100 Single Fully Loaded Unit (Ground Floor)
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
0
SHEAR FORCE
(LBS.)
318.5
ANCHORAGE DESIGN
4
0.375
2.5
6.67
shallow anchor, increase load per UBC 1632.2
3.75 in. slab, min.
712
1255
0.0/1898.6 =
Shear
637.1/3346.6 =
0.00
0.19
SUMMARY
CONCRETE:
3.75 in. slab, min. Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385), embed. 2.5 in.
Use 4 brackets total, one anchor/bracket
1:46 PM
1/27/2006
Date:
Page:
1/27/2006
28
2 - AR3100
Part
Seismic Force
Weight (lbs)
Frame
X (in)
550.4
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.28
Z (in)
Ip =
1.0
(Importance)
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.0
(Floor)
Y (in)
21.05
(Zone 0-3)
Fp =
0.067
(2000lbs.x 2units)
Fp,min =
0.14
33
30.6
Fp,max =
0.80
Use Fp =
0.14
4000
38.5
(internal brackets)
Longitudinal Overturning
Overturning
Moment =
24527
lb-in
0.9xResisting
Moment =
96650
lb-in
Anchorage Force =
Shear Force =
0
637.1
lbs
lbs.
Netshelter SX
plan
Seismic Force
2 ganged units
Design Bolts for 0 lbs tension, 637.1 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
24527
lb-in
0.9xResisting
Moment =
86207
lb-in
Anchorage Force =
Shear Force =
0
637.1
lbs
lbs.
Seismic Force
2 ganged units
Netshelter SX
plan
Design Bolts for 0 lbs tension, 637.1 lbs. shear, transverse direction, ganged fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
Date:
Page:
1/27/2006
29
Load Case: Ganged Fully Loaded Unit (On 18" raised computer floor, Ground Floor)
# of Units ganged (max)= 2
Single Unit Dimension
Length (in) =
23.6
Width (in) =
42.1
Frame Height (in) =
77
Frame Weight (lb.) =
275.2
Unit
2 - AR3100
Part
Seismic Force
Weight (lbs)
Frame
550.4
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.28
Z (in)
Ip =
1.0
(Importance)
56.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.0
(Floor)
Y (in)
21.05
(Zone 0-3)
Fp =
0.067
(2000lbs.x 2units)
Fp,min =
0.14
33
30.6
Fp,max =
0.80
Use Fp =
0.14
4000
56.5
Longitudinal Overturning
Overturning
Moment =
35994
lb-in
0.9xResisting
Moment =
96650
lb-in
Anchorage Force =
Shear Force =
0
637.1
lbs
lbs.
Netshelter SX
plan
Seismic Force
2 ganged units
Design Bolts for 0 lbs tension, 637.1 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
35994
lb-in
0.9xResisting
Moment =
86207
lb-in
Anchorage Force =
Shear Force =
0
637.1
lbs
lbs.
Seismic Force
2 ganged units
Netshelter SX
plan
Design Bolts for 0 lbs tension, 637.1 lbs. shear, transverse direction, ganged fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
30
Load Cases:
Ganged Fully Loaded Unit (Ground Floor)
Ganged Fully Loaded Unit (On 18" raised computer floor, Ground Floor)
ANCHORAGE FORCES
CONDITION
ANCHORAGE
FORCE (LBS.)
SHEAR FORCE
(LBS.)
GANGED UNIT
637.1
ANCHORAGE DESIGN
4
0.375
2.5
6.67
shallow anchor, increase load per UBC 1632.2
3.75 in. slab, min.
712
1255
0.0/1898.6 =
Shear
1274.1/6693.2 =
0.00
0.19
SUMMARY
CONCRETE:
3.75 in. slab, min. Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385), embed. 2.5 in.
Use 4 brackets total, one anchor/bracket
1:46 PM
1/27/2006
Date:
Page:
1/27/2006
31
AR3100
Frame
275.2
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
11.8
21.05
2000
9.65
30.6
38.5
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.5
Fp =
0.167
Fp,min =
0.14
Fp,max =
0.80
Use Fp =
0.17
Longitudinal Overturning
Overturning
Moment =
14599
lb-in
0.9xResisting
Moment =
24163
lb-in
Anchorage Force =
Shear Force =
0
318.5
lbs
lbs.
Netshelter SX Unit
Plan
23.6 in.
Design Bolts for 0 lbs tension, 318.5 lbs. shear, longitudinal direction, fully loaded
Netshelter SX Unit
Plan
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
14599
lb-in
43104
lb-in
Anchorage Force =
Shear Force =
0
318.5
lbs
lbs.
Seismic
Force (Fp)
42.1 in.
23.6 in.
Design Bolts for 0 lbs tension, 318.5 lbs. shear, transverse direction, fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
32
Load Cases:
Single Fully Loaded Unit (<=50% OF BUILDING HEIGHT)
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
0
SHEAR FORCE
(LBS.)
318.5
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 4
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.750
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.67
Min. Conc Slab Thickness (1.5x embed. Length) 2.625 in. slab, min.
423
1062
0.0/1128.0 =
Shear
637.1/2832.0 =
0.00
0.22
564.0
1416.0
1:46 PM
1/27/2006
Date:
Page:
1/27/2006
33
2 - AR3100
Part
Seismic Force
Weight (lbs)
Frame
550.4
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.28
Z (in)
Ip =
1.0
(Importance)
46.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.5
(Floor)
Y (in)
21.05
(Zone 0-3)
Fp =
0.167
(2000lbs.x 2units)
Fp,min =
0.14
32.95
30.6
Fp,max =
0.80
Use Fp =
0.17
4000
46.5
Longitudinal Overturning
Overturning
Moment =
35266
lb-in
0.9xResisting
Moment =
96650
lb-in
Anchorage Force =
Shear Force =
0
758.4
lbs
lbs.
Netshelter SX
plan
Seismic Force
2 ganged units
Design Bolts for 0 lbs tension, 758.4 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
35266
lb-in
0.9xResisting
Moment =
86207
lb-in
Anchorage Force =
Shear Force =
0
758.4
lbs
lbs.
Seismic Force
2 ganged units
Netshelter SX
plan
Design Bolts for 0 lbs tension, 758.4 lbs. shear, transverse direction, ganged fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
Date:
Page:
1/27/2006
34
Seismic Force
Center of Gravity Location
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
2 - AR3100
Frame
550.4
23.6
21.05
56.5
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.28
Ip =
1.0
(Importance)
(Zone 0-3)
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.5
(Floor)
Fp =
0.167
(2000lbs.x 2units)
Fp,min =
0.14
32.95
30.6
Fp,max =
0.80
Use Fp =
0.17
4000
56.5
Longitudinal Overturning
Overturning
Moment =
42850
lb-in
0.9xResisting
Moment =
96650
lb-in
Anchorage Force =
Shear Force =
0
758.4
lbs
lbs.
Netshelter SX
plan
Seismic Force
2 ganged units
Design Bolts for 0 lbs tension, 758.4 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
42850
lb-in
0.9xResisting
Moment =
86207
lb-in
Anchorage Force =
Shear Force =
0
758.4
lbs
lbs.
Seismic Force
2 ganged units
Netshelter SX
plan
Design Bolts for 0 lbs tension, 758.4 lbs. shear, transverse direction, ganged fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
35
Load Cases:
Ganged Fully Loaded Unit (<=50% OF BUILDING HEIGHT)
Ganged Fully Loaded Unit (On 18" RAISED COMPUTER FLOOR SYSTEM, <=50% OF BUILDING HEIGHT)
ANCHORAGE FORCES
CONDITION
ANCHORAGE
FORCE (LBS.)
SHEAR FORCE
(LBS.)
GANGED UNIT
758.4
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 4
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.750
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.67
Min. Conc Slab Thickness (1.5x embed. Length) 2.6 in. conc. cover, min.
423
1062
0.0/1128.0 =
Shear
1516.8/2832.0 =
0.00
0.54
SUMMARY:
CONC. FILL OVER METAL DECK:
2.6 in. conc. cover, min. Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385), embed. 1.75 in.
Use 4 brackets total, one anchor/bracket
1:46 PM
1/27/2006
Date:
Page:
1/27/2006
36
23.6
42.1
77
Seismic Force
Ca =
0.28
Z (in)
Ip =
1.0
(Importance)
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.9
Part
AR3100
Weight (lbs)
Frame
275.2
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
X (in)
11.8
Y (in)
21.05
2000
9.65
30.6
38.5
(Zone 0-3)
Fp =
0.247
Fp,min =
0.14
Fp,max =
0.80
Use Fp =
0.25
Longitudinal Overturning
Overturning
Moment =
21607
lb-in
0.9xResisting
Moment =
24163
lb-in
Anchorage Force =
Shear Force =
0
318.5
lbs
lbs.
Netshelter SX Unit
Plan
23.6 in.
Design Bolts for 0 lbs tension, 318.5 lbs. shear, longitudinal direction, fully loaded
Netshelter SX Unit
Plan
Transverse Overturning
Overturning
Moment =
0.9xResisting
Moment =
21607
lb-in
43104
lb-in
Anchorage Force =
Shear Force =
0
318.5
lbs
lbs.
Seismic
Force (Fp)
42.1 in.
23.6 in.
Design Bolts for 0 lbs tension, 318.5 lbs. shear, transverse direction, fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
37
Load Cases:
Single Fully Loaded Unit (<=90% OF BUILDING HEIGHT)
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
0
SHEAR FORCE
(LBS.)
318.5
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 4
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.625
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.33
Min. Conc Slab Thickness (1.5x embed. Length) 2.4 in. conc. cover, min.
423
1062
0.0/1128.0 =
Shear
637.1/2832.0 =
0.00
0.22
564.0
1416.0
1:46 PM
1/27/2006
Date:
Page:
1/27/2006
38
2 - AR3100
Part
Seismic Force
Weight (lbs)
Frame
550.4
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Ca =
0.28
Z (in)
Ip =
1.0
(Importance)
38.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.9
Y (in)
21.05
(Zone 0-3)
Fp =
0.247
(2000lbs.x 2units)
Fp,min =
0.14
23.6
30.6
Fp,max =
0.80
Use Fp =
0.25
4000
38.5
Longitudinal Overturning
Overturning
Moment =
43214
lb-in
0.9xResisting
Moment =
96650
lb-in
Netshelter SX
plan
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1122.4 lbs.
Design Bolts for 0 lbs tension, 1122.4 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
43214
lb-in
0.9xResisting
Moment =
86207
lb-in
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1122.4 lbs.
Netshelter SX
plan
Design Bolts for 0 lbs tension, 1122.4 lbs. shear, transverse direction, ganged fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
39
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
0
SHEAR FORCE
(LBS.)
1122.4
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 4
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.625
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.33
Min. Conc Slab Thickness (1.5x embed. Length) 2.4 in. conc. cover, min.
423
1062
0.0/1128.0 =
Shear
2244.9/2832.0 =
0.00
0.79
564.0
1416.0
1:46 PM
1/27/2006
Date:
Page:
1/27/2006
40
Seismic Force
Center of Gravity Location
Ca =
0.28
(Zone 0-3)
Unit
Part
Weight (lbs)
X (in)
Y (in)
Z (in)
Ip =
1.0
(Importance)
2 - AR3100
Frame
550.4
23.6
21.05
56.5
ap =
1.0
(Cabinets)
Rp =
3.0
(Cabinets)
hx/hr =
0.9
Max Load
Longitudinal Anchorage Spacing (in) =
Transverse Anchorage Spacing (in) =
Fp =
0.247
(2000lbs.x 2units)
Fp,min =
0.14
23.6
30.6
Fp,max =
0.80
Use Fp =
0.25
4000
56.5
Longitudinal Overturning
Overturning
Moment =
63417
lb-in
0.9xResisting
Moment =
96650
lb-in
Netshelter SX
plan
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1122.4 lbs.
Design Bolts for 0 lbs tension, 1122.4 lbs. shear, longitudinal direction, ganged fully loaded
Transverse Overturning
Overturning
Moment =
63417
lb-in
0.9xResisting
Moment =
86207
lb-in
Seismic Force
2 ganged units
Anchorage Force =
Shear Force =
0
lbs
1122.4 lbs.
Netshelter SX
plan
Design Bolts for 0 lbs tension, 1122.4 lbs. shear, transverse direction, ganged fully loaded
1:32 PM
1/27/2006
M:\2005jobs\05240\AR3100\calcs\AR3100 Zone 0-3 (Non-California).xls
1/27/2006
41
Load Cases:
Ganged Fully Loaded Unit
(On 18" RAISED COMPUTER FLOOR SYSTEM, <=90% OF BUILDING HEIGHT)
ANCHORAGE FORCES
CONDITION
SINGLE UNIT
ANCHORAGE
FORCE (LBS.)
0
SHEAR FORCE
(LBS.)
1122.4
ANCHORAGE DESIGN
Use Hilti Kwik Bolt 3 Anchors (ICC ESR-1385)
Number of Brackets Used: 4
Anchor Diameter (in2): 0.375
Embedment Length (in.): 1.625
(shallow anchor, increase load per UBC 1632.2)
Embed. length /Dia = 4.33
Min. Conc Slab Thickness (1.5x embed. Length) 2.4 in. conc. cover, min.
423
1062
0.0/1128.0 =
Shear
2244.9/2832.0 =
0.00
0.79
564.0
1416.0
1:46 PM
1/27/2006
0
4
0
1.05
1/27/2006
42
Tension Force
0
0.0066
0.00
50
1.05 in
NOTE: (1) APC 870-11101A pallette bracket may be used in lieu of (2) APC7701 brackets
1:46 PM
1/27/2006