Professional Documents
Culture Documents
A Study On The PDF
A Study On The PDF
312~319, 2012
http://dx.doi.org/10.5370/JEET.2012.7.3.312
1. Introduction
Power transformers are unlikely to suffer from a
breakdown, however if a breakdown occurs it may cause a
huge damage to society and economy. The power
transformers installed during the rapid growth of the
economy, and came close to a 30 year operation. The life of
the power transformer should be calculated with statistical
data in order to establish the criteria. But its materials and
manufacturing technologies change over the years and any
normal distribution has not been formed. Therefore just
plain statistical methodology is not enough to determine
the life of the transformer [1]. The life of the power
transformer depends on the life of the cellulose paper
whose deterioration is affected by temperature, moisture
and oxygen. However, since the effects of moisture and
oxygen on cellulose papers deterioration can be controlled
for it to remain in minimum, it may be stated that the
deterioration of the cellulose paper is largely affected by
temperature [2]. In particular, as temperature distribution
inside the power transformer is not uniform, the cellulose
paper around the hot spot temperature will be deteriorated
the most. Therefore, the standards define the transformers
15000
+ 273
H
(1)
313
Specification
OS4200
20 ~ 275
~10pm/ (1.7pm/)
0.2 seconds
1.07 27.1mm
SMF28-compatible
Over 17mm
Over 70%
Over 15dB
Specification
11,280W
78,956W
90,236W
154/22.9kV
Single-phase, 15/20MVA, 60Hz
Shell
Top liquid 60
Average winding 65
ONAN/ONAF
20%
11,000 liters
314
to the total losses (the sum of no-load loss and load loss) of
the transformer. After the top liquid temperature rise test
has been established, the average winding temperature rise
test is continued without a break with the test current
reduced to rated current equivalent to load loss (the sum of
copper loss and stray loss). For the convenience of the test,
however, the two steps of the test may be combined in one
single application of power.
The primary rated voltage is a voltage to generate
maximum loss; 77,798V was measured on the lowest tap
(21 tap) equivalent to the lowest voltage under the rated
phase voltage ( 154kV / 3 12.5% ). No-load loss is
indicated a loss when the rated voltage is applied to the
primary winding and the secondary winding is open; it was
measured to be 11,280W. Load loss is the sum when
copper loss (62,769W) and stray loss (16,277W) are added;
it was measured 78,956W. Therefore, the total loss was
90,236W by adding no-load loss and load loss.
The rated current ( I r ), equivalent to load loss is;
Rated capacity
15MVA
=
= 192.8A
Primary rated voltage
77,798V
192.8
= 2.410 A
400 / 5
Total loss
Load loss
90,236
=
78,953
206.1 A
206.1
I =
= 2.576 A
t 400 / 5
u b
2
= 73.7
66.2 42.3
= 61.7
2
315
temperature
variation
after
(2)
(3)
316
W =
RW
(235 + 1 ) 235
R1
(4)
o
1
u b
1
= 20
20 19
= 19.5
2
I
gc = g r
Il
317
h = o + ( H g c )
The hot spot temperature appeared to be 98.3 on the
high voltage winding and 97.3 on the low voltage
winding.
(8) Hot spot temperature rise ( h )
The hot spot temperature rise is the difference between
the hot spot temperature and the ambient temperature. The
hot spot temperature rise appeared to be 73.6 on the
high voltage winding and 72.6 on the low voltage
winding.
318
References
Fig. 10. Temperature at each point of the transformer
Fig. 10 shows the temperature at each point of the
transformer with the rated power. As in Fig. 10, the hot
spot temperature appeared between turn 2 and turn 3 on the
upper side of the low voltage winding, recording 105.9.
The hot spot temperature also appeared between turn 2 and
turn 3 on the upper side of the high voltage winding as in
the low voltage winding, and was 92.4. The hot spot
temperature of the low voltage winding as measured by the
optical fiber sensor was 13.3 higher than 92.6, which
is the hot spot temperature calculated by the heat run test.
The power transformer can change in loss of the winding,
heat transfer, fluid flow, etc. depending on its design. The
hot spot factor (H) should be determined on an individual
basis which ranges from 1.0 to 2.1, depending on the
transformer size according to IEC 60076-2; however, the
power transformer in general is recommended to be 1.3. In
this paper, when applying the hot spot temperature
measured by an optical fiber sensor to the IEC, the hot spot
factor (H) appeared to be 2.0.
4. Conclusion
In this paper, the hot spot temperature of 154kV
transformer was measured by the optical fiber sensors and
compares the value with the hot spot temperature
calculated by the conventional heat run test in the factory
test.
The top liquid temperature rise on the rated power
measured by the thermocouple in the heat run test appeared
to be 49.0. This satisfies the top liquid temperature rise
limit of 60 as in the transformer specification. The
average winding temperature rise appeared to be 58.1 on
the high voltage winding and 57.3 on the low voltage
winding. This satisfies the average winding temperature
rise limit of 65 as in the transformer specification. The
hot spot temperature at the ambient temperature 20
shown in the heat run test was 93.6 on the high voltage
winding and 92.6 in the low voltage winding.
However, the hot spot temperature as measured by the
optical fiber sensor appeared between turn 2 and turn 3 on
the upper side of the low voltage winding, recording
[1]
319