Professional Documents
Culture Documents
Gers Gers: Generator Protection Setting Criteria
Gers Gers: Generator Protection Setting Criteria
Prestacin de
los servicios
de Diseo y
estudios
asociados a
sistemas
elctricos
Generator Protection
Setting Criteria
Certificado
No. 637-1
Juan M. Gers
Content
Examples
Preliminary
Lightning
Aging of insulation
Equipment failure
Animal presence
Rough environmental conditions
Branch fall
Improper design, maintenance or operation
Preliminary
Protection relays sense any change in the signal which they are
receiving, which could be of electrical or mechanical nature.
Protection requirements
Electromagnetic
Solid state
Microprocessor
Numerical
Non-electric (thermal, pressure, etc.,)
Electromagnetic
Torque
Solid State
Averaged
Ref
Hysteresis
Ref
Hysteresis
Microprocessor
Averaged
A/D
Numeric
Direct Samples
A/D
Reliability
Multifunctionality
Self-diagnosis
Event and disturbance records
Communication capabilities
Adaptive protection
Microprocessor
Memory module
Input module
Output module
Communication module
Numerical relays
Sampled Waveform
8
2
0
-2
Current
6 8 10 12 14 16 18 20 22
-4
3
-6
-8
Sample
Sine Wave
4 samples/cycle
DFT
I(n) = 2
DFT N
N=
n=
k=
N-1
[I (cos(nk 2 ))N
k=0 k
# samples/cycle fundamental
desired harmonic
sample index
2
jI k (sin( nk ))]
N
DFT
2
2
)=1 and sin (Nk ) = 0
N
N
2
2
nk
nk
For k = 1 , n=1 cos(
) =0 and sin (
)= 1
N
N
2
2
For k = 2 , n=1 cos( nk ) = -1 and sin ( nk )= 0
N
N
2
2
nk
nk
For k = 3 , n=1 cos(
) =0 and sin (
) = -1
N
N
For k = 0 , n=1
IDFT =
cos( nk
2 (I -jI -I +jI )
N 0 1 2 3
DESCRIPTION
Time-delay relay
Distance relay
Overexcitation / Volts per Hertz
Synchronism-check relay
Undervoltage relay
Third-Harmonic Undervoltage relay
Annunciator device
Reverse power relay
Undercurrent or underpower relay
Field excitation relay
Negative sequence overcurrent relay
Negative sequence overvoltage relay
Thermal relay
Instantaneous AC overcurrent relay
Split Phase Differential
Inadvertent Energizing
Breaker Failure
AC Inverse Time Overcurrent relay
Circuit breaker
Overvoltage relay
Third-Harmonic Voltage Differential Ratio
No.
60
63
64F
64B
64S
67
68
69
74
76
78
79
81
81R
83
85
86
87
94
DESCRIPTION
Voltage balance or loss of potential relay
Pressure device
Field Ground relay
Brush Lift-Off Detection
100% Stator Ground Protection by Low
Frequency Injection
AC directional overcurrent relay
Power Swing Blocking
Permissive relay
Alarm relay
DC overcurrent relay
Out-of-step relay
AC reclosing relay
Frequency relay
Rate of Change Frequency relay
Transfer device
Carrier or pilot-wire relay
Lock out relay
Differential relay
Auxiliary tripping relay
Safety
Ability to detect less harmful (hopefully)
phase-to-ground fault before phase-to-phase fault
occurs
Limit damage from ground faults
Stop transient overvoltages
Provide ground source for other system protection
(other zones)
Cheap
Usually done only on small generators
Definitely a good ground source
Generator likely to get damaged on internal ground fault
System
System
Moderately expensive
Used when generators are unit connected
System ground source obtained from unit xfmr
Generator damage minimized or mitigated from ground
fault
Ground fault current typically <=10A
51
N
52
F3
51
51
N
52
F2
52
B
51
51
N
52
F1
52
G
87
GD
G
51
G
Trip
Excitation,
Prime Mover
VS
59
N
24 Overexcitation
27 Undervoltage
59 Overvoltage
81U Underfrequency
81O Overfrequency
32 Reverse Power or Directional Power
49 Thermal Protection
51 Overcurrent
51VC/51VR or 21 System Backup
60 Loss of Voltage
78 Out-of-Step
64F Field Ground
Additional functions that may be provided include:
Sequential Trip Logic
Accidental Energization
Open Breaker Detection
60 Loss of Voltage
78 Out-of-Step
64F Field Ground
Additional functions that may be provided include:
Sequential Trip Logic
Accidental Energization
Open Breaker Detection
Medium up to 12.5 MW
Large up to 50 MW
Larger than 50 MW
BFPh
CT
50
DT
Programmable I/O
VT
Metering
52
Gen
87
25
Sequence of Events
Logging
VT
Waveform Capture
81R
User Interface
with PC
81
27
59
24
3Vo
VT
Communications
(MODBUS, Ethernet)
M-3921
+
67N
On Board HMI
LED Targets
64F
64B
27
60FL
21
78
32
51V
40
50/27
51T
46
CT
50
VT
59D
27
32
27
TN
59N
87
GD
50
BFN
50N
51N
CT
DESCRIPTION
21
24
25
Sync-check
27
27TN
32R
32F, 32LF
40
46
DESCRIPTION
50
50DT
50/27
50BF
Breaker Failure
51
51V
59
59D
60FL
DESCRIPTION
64F
64B
64S
67N
78
Out-of-step protection
81
81R
87
87GD
Distance Protection
Distance relaying with mho characteristics is commonly used
for system phase-fault backup.
These relays are usually connected to receive currents from
current transformers in the neutral ends of the generator
phase windings and potential from the terminals of the
generator.
If there is a delta grounded-wye step-up transformer between
the generator and the system, special care must be taken in
selecting the distance relay and in applying the proper
currents and potentials so that these relays see correct
impedances for system faults.
21 Distance element
Fault
Impendance
Load
(for Z1, Z2, Z3)
Blinder
+X
XL
XT
Z3
Z2
Z1
-R
+R
-X
Power
oror
PowerSwing
Swing
Load
LoadEncroachment
Encraochment
21 Distance Element
Fault
Impendance
Load
(for Z1 & Z2)
Blinder
+X
XL
XT
Z3
Z2
Z1
-R
+R
-X
Pow er Sw ing or
Load Encraochment
Distance Protection
Settings summary per IEEE C37.102-2005
Zone-1 = the smaller of the two following criteria:
1. 120% of unit transformer
2. 80% of Zone 1 reach setting of the line relay on the shortest
line (neglecting in-feed);
Time = 0.5 s
Distance Protection
PHYSICAL INSIGHTS
As voltage rises above rating leakage flux increases
Leakage flux induces current in transformer support
structure causing rapid localized heating.
GENERATOR
TRANSFORMER
EXCITATION
Voltage
Freq.
Hz
Synchronizing
(25)
Synchronizing
Improper synchronizing of a generator to a system may result
in damage to the generator step-up transformer and any type
of generating unit.
The damage incurred may be slipped couplings, increased
shaft vibration, a change in bearing alignment, loosened
stator windings, loosened stator laminations and fatigue
damage to shafts and other mechanical parts.
In order to avoid damaging a generator during synchronizing,
the generator manufacturer will generally provide
synchronizing limits in terms of breaker closing angle and
voltage matching.
Synchronizing
Undervoltage
(27)
Undervoltage
Generators are usually designed to operate continuously
at a minimum voltage of 95% of its rated voltage, while
delivering rated power at rated frequency.
Operating generator with terminal voltage lower than
95% of its rated voltage may result in undesirable effects
such as reduction in stability limit, import of excessive
reactive power from the grid to which it is connected,
and malfunctioning of voltage sensitive devices and
equipment.
Undervoltage
Settings summary per IEEE C37.102
Relays with inverse time characteristic and instantaneous
PU : 90%Vn; t= 9.0 s at 90% of PU setting
Inst : 80% Vn
Relays with definite time characteristic and two stages
Alarm PU : 90%Vn; 10< t < 15 s
Trip PU : 80% Vn; time: 2s
Reverse Power
(32)
Reverse Power
Prevents generator from motoring on loss of prime mover
From a system standpoint, motoring is defined as the flow of
real power into the generator acting as a motor.
With current in the field winding, the generator will remain in
synchronism with the system and act as a synchronous
motor.
If the field breaker is opened, the generator will act as an
induction motor.
A power relay set to look into the machine is therefore used
on most units.
The sensitivity and setting of the relay is dependent upon
the type of prime mover involved.
Reverse Power
Sequential Tripping
Used on steam turbine generators to prevent
overspeed
Recommended by manufacturers of steam turbine
generators as a result of field experience
This trip mode used only for boiler/reactor or
turbine mechanical problems
Electrical protection should not trip through this
mode
Sequential Tripping
STEP 1
Abnormal
detected
turbine/boiler/reactor
condition
is
STEP 2
Turbine valves are closed; generator allowed to
briefly motor (I.e., take in power)
STEP 3
A reverse power (32) relay in series with turbine
valves position switches confirms all valves have
closed
STEP 4
Generator is separated from power system
CONSIDER
High MVArs (out)
Low MW (in)
E-M relay can be fooled
Loss-of-Field
(40)
Loss of Field
CAUSES
Field open circuit
Field short circuit
Accidental tripping of field breaker
Regulator control failure
Loss of main exciter
Loss of Field
R-X Plot
Loss of Field
Loss of Field
1
Offset: X'd/2; Diameter: 1.0 pu; time: 0.1 s
UNIT
Loss of Field
Protective Approach # 1
Loss of Field
Protective Approach # 2
Negative Sequence
(46)
Negative Sequence
Unbalanced phase currents create negative sequence current in
generator stator
Negative Sequence
Settings summary per IEEE C37.102
PERMISSIBLE l2
PERCENT OF STATOR RATING
TYPE OF GENERATOR
Salient Pole
10
Cylindrical Rotor
Indirectly cooled
10
Negative Sequence
Type of Generator
Permissible l22t
40
Synchronous condenser
30
30
10
(VALUES TAKEN
FROM ANSI C50.13-1989)
Split Phase
Differential
(50DT)
Split-Phase Differential
Most turbine generators have single turn stator windings. If a
generator has stator windings with multiturn coils and with two
or more circuits per phase, the split-phase relaying scheme
may be used to provide turn fault protection.
In this scheme, the circuits in each phase of the stator winding
are split into two equal groups and the currents of each group
are compared.
A difference in these currents indicates an unbalance caused
by a single turn fault.
Split-Phase Differential
Operating errors
Breaker head flashover
Control circuit malfunctions
Combination of above
protection
disabled when
energized
machine
is
will
not
inadvertently
Overcurrent Protection
(50/51)
Overcurrent Protection
In some instances, generator overload protection may be
provided through the use of a torque controlled overcurrent
relay that is coordinated with the ANSI C50.13-2004 shorttime capability curve
This relay consists of an instantaneous overcurrent unit and
a time overcurrent unit having an extremely inverse
characteristic.
An overload alarm may be desirable to give the operator an
opportunity to reduce load in an orderly manner.
This alarm should not give nuisance alarms for external
faults and should coordinate with the generator overload
protection if this protection is provided.
Overcurrent Protection
Overcurrent Protection
Overvoltage (59)
Overvoltage
Generator overvoltage may occur without necessarily
exceeding the V/Hz limits of the machine.
Protection for generator overvoltage is provided with
a frequency-compensated (or frequency insensitive)
overvoltage relay.
The relay should have both an instantaneous unit
and a time delay unit with an inverse time
characteristic.
Two definite time delay relays can also be applied.
Overvoltage
Settings summary per IEEE C37.102
Relays with inverse time characteristic and instantaneous
PU : 110%Vn; t= 2.5 s at 140% of PU setting
Inst : 130 - 150% Vn
Relays with definite time characteristic and two stages
Alarm PU : 110%Vn; 10< t < 15 s
Trip PU : 150% Vn; time: 2s
Stator Ground
Field Ground
(64F)
Ground #2
Generator Out-Of-Step
Protection (OSP)
(78)
Background
During power system disturbances, the voltage and current which feed the
relays vary with time and, as a result, the relays will also see an impedance
that is varying with time.
P=
V S x VR
X
Sin
Two-Machine System
VS & VR
90
Constant
P=
V S x VR
X
Sin
P e r U n it T o rqu e o r P ow e r
F au lty L in e
S w itc he d O u t
L -G F a u lt
L -L F au lt
T0
L -L -G F au lt
3 F au l t
10
20
30
40
50
60
70
80
90
S
VS '
P
S'
R
A
3
Fault
n
R'
VR
Transmitted Power
Final
Operating
Point
J
II
Initial
Operating
Point
P
D
A Breaker Open
B Breaker Closed
During 3 Fault
H
F
45
A and B
Breakers Closed
90
135
Angle m
180
Fast clearing
Pilot systems
Breaker failure systems
Single pole tripping
High speed reclosing
Load shedding
B
VR
IS
Q
Increase in S
ZL
when V S = VR
O
VA / I S
VS
VS
IS
Impedance seen
by the relay
Power oscillation
with Vs >V r
Zone 3
Measuring unit
Zone 2
Blocking relay
characteristic
Load characteristic
The swing time should be greater than the time delay setting
Unstable
Stable
X d
XT
XS
Setting of 78 Relays
X
D
A
SYSTEM
X maxSG1
O
1.5 X TG
TRANS
XTG
M
Swing Locus
GEN
Xd
2Xd
ELEMENT
PICK-UP
ELEMENT
PICK-UP
C
BLINDER
ELEMENTS
MHO
ELEMENT
Setting of 78 Relays
Settings summary per IEEE C37.102-2005
Mho Diameter : 2X'd + 1.5 XTG
d = ((X'd + XTG + XmaxSG1)/2) x tan (90-(/2))
where
d: Blinder distance
: angular separation between generator and the
system which the relay determines instability.
If there is not stability study available = 120
t = as per transient stability study
typically 40 < t < 100 ms
Frequency (81)
Frequency
The operation of generators at abnormal frequencies
(either overfrequency or underfrequency) generally results
from full or partial load rejection or from overloading of the
generator.
Load rejection will cause the generator to overspeed and
operate at some frequency above normal
Steam and gas turbines are more limited or restrictive to
abnormal frequency than hydrogenerators.
At some point abnormal frequency may impact turbine
blades and result in damage to the bearings due to vibration.
Frequency
Settings summary per IEEE C37.102
It is important to consult turbine manufacturer and get turbine
off frequency operating curves or limits
Under frequency:
81U ALARM: 59.5 Hz time: 10 s
81U TRIP :
The generator 81U relay should be set below the pick-up of
under frequency load shedding relay set-point and above the
off frequency operating limits of steam turbine.
Over frequency:
81O ALARM
Pick-up: 60.6 Hz, Time Delay 5 sec.
Phase Differential
(87)
Phase Differential
Fast response time (under 1 cycle)
Percentage differential with adjustable slope
Phase Differential
Settings summary per IEEE C37.102
PU : 0.3 A
Slope1 : 10%
time: Instantaneous
IEEE No.
21
Distance
24
Overexcitation
25
Sync-check
27
Undervoltage
DESCRIPTION
A.2.3
4.5.4.2
5.7
A.2.13
32
40
46
FUNCTION
Reverse Power
Loss-of-field
Negative Sequence
Overcurrent
DESCRIPTION
4.5.5.3 &
A.2.9
4.5.1.3
4.5.2
UNIT 1
Offset: X'd/2; Diameter: 1.0 pu; time: 0.1 s
UNIT 2
Offset: X'd/2; Diameter: Xd; time: 0.5 to 0.6 s
Pickup setting should be below the permissible I2
percent expressed in percent of rated current, which
are indicated below:
Salient pole w/connected amortisseur windings: 10%
Salient pole non-connected amortisseur windings: 5%
Cylindrical rotor indirectly cooled: 10%
Directly cooled up to 960 MVA: 8%
Directly cooled 961 to 1200 MVA: 6%
Directly cooled 961 to 1200 MVA: 6%
Directly cooled 1201 to 1500 MVA: 5%
Permissible K (I22 x t)
Salient pole generator: 40
Synchronous condenser: 30
Cylindrical rotor indirectly cooled: 30
Directly cooled: 10
50/87
50/27
Inadvertent Energization
Overcurrent with 27, 81
Supervision
50 BF
51N
50/51N
51GN, 51N
FUNCTION
SECTION
DESCRIPTION
4.3.2.5.1
A.2.4
A.2.11
FUNCTION
SECTION
50/51
51VC
51VR
59
59N,
27-TH, 59P
Overvoltage
4.1.1.2
DESCRIPTION
51PU: 75-100% FLC, time: 7 s at 226% FLC. FLC
means full load current.
50PU: 115% FLC, time: instantaneous
A.2.6
A.2.6
4.5.6. &
A.2.12
4.3.3.1.1 &
A.2.7
64F
FUNCTION
DESCRIPTION
4.4
67IE
78
81
Out of Step
Over/under frequency
(60 Hz systems)
A.2.2
A.2.14
81U
ALARM:
59.5
Hz
time:
10
s
81U
TRIP:
The generator 81U relay should be set below the pickup of underfrequency load shedding relay set-point and
above the off frequency operating limits of steam
turbine.
81O ALARM:Pick-up: 60.6 Hz, Time Delay 5 sec.
FUNCTION
SECTION
87G
87GN
87UD
Unit Differential
A.2.5
DESCRIPTION
PU : 0.3 A
Slope : 10%
time: instantaneous
Types Of Data
Metering
Function Status
Breaker Monitoring
Fault Reporting
Oscillography
Testing
Metering
Function Status
Breaker Monitoring
Fault Reporting
Fault Reporting
Fault Reporting
Oscillography
E
F
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
All analog traces. This view shows peak values. RMS values may
also be displayed.
Controls for going to the beginning or end of a record, as well as
nudging forward or backward in time in a record
Zoom controls
Display controls for analog traces, RMS traces, fundamental
waveform display, frequency trace, power trace, power factor trace,
phasor diagram, impedance diagram and power diagram
Marker #1
Marker #2
Time at Marker #1
Time at Marker #2
Control status input and contact output traces (discrete I/O)
Scaling for each analog trace. This can be set automatically or
manually adjusted.
Date and timestamp for record
Time of trip command
Time at Marker #1
Time at Marker #2
Oscillography
R
S
O.
P.
Q.
R.
S.
Communications
Test Report
GERS
TEST REPORT
CONSULTING ENGINEERS
1. GENERAL SETTINGS
Parameter
Nominal Voltage [V]
Nominal Current [A]
Nominal Frequency [Hz]
Phase Rotation
C.T. Secundary Rating [A]
Delta - Y Transformer
2. READINGS CHECK
Description
V RY [V]
V YB [V]
V BR [V]
I R [A]
I Y [A]
I B [A]
I r [A]
I y [A]
I b [A]
Active Power [W/MW]
DATE
FEBRUARY 26 / 2004
TESTED BY:
R. Bravo - C. Quintero
APROVED BY:
A.Tasama - G. Williams
CIRCUIT : STG PROT. A
SYSTEM: AC01
BECHTEL LIMITED
GENERATOR PROTECTION
Value
120
3.98
50
ABC
5
Enable
LOCATION :
SERIAL NUMBER :
STG ELECT BUILDING
1815
Parameter
V.T. Configuration
Relay Seal-in Time [Cycles]
V.T. Phase Ratio
V.T. Neutral Ratio
C.T. Phase Ratio
C.T. Neutral Ratio
Injected
Theoretical Value
120.0
24000
120.0
24000
120.0
24000
5.0
13000
5.0
13000
5.0
13000
5.0
13000
5.0
13000
5.0
13000
900.0
468.00
519.6
270.20
Reactive Power [VAr/MVAr]
Power Factor
0.87
0.87
Frequency [Hz]
50.000
50.00
Note: IR, IY, IB = line side currents / Ir, Iy, Ib = generator side currents
Value
L-G to L-L
300
200
100
2600
25
Obtained Read
23960
23940
24020
13005
13021
13013
13018
13013
13000
466.36
275.21
0.86
50.00
% Error
-0.17%
-0.25%
0.08%
0.04%
0.16%
0.10%
0.14%
0.10%
0.00%
-0.35%
1.85%
-1.15%
0.00%
Test Report
16. FUNCTION 87. PHASE DIFFERENTIAL PROTECTION
16.1. Settings
Parameter
Minimum Operation current [A]
Slope
Time Delay [Cycles]
Value
0.3
10%
1
Trip output
Blocking input
Theoretical Value
10.00%
40.00%
20.00
0.29
0.00
0.29
0.15
0.00
0.29
0.15
3.00
2.70
0.30
2.85
2.70
0.30
2.85
5.00
4.52
0.48
4.76
4.50
0.50
4.75
% Error
3.33%
3.33%
3.33%
0.53%
0.00%
-5.00%
Result
0.29
0.29
0.29
10.53%
40.00%
19.00
IR
IY
IB
0.30
1
-
7.00
6.33
0.67
6.67
6.30
0.70
6.65
10.50
7.00
3.50
8.75
7.00
3.50
8.75
13.00
8.67
4.33
10.83
8.60
4.40
10.80
15.00
10.00
5.00
12.50
10.00
5.00
12.50
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2
Obtained
6
Theoretical
10
12
14
Test Report
Fixed
Varied
Calculated
Value
8.50
-5.2
85
50
Theoretical Value
20
6.06
3.30
1.00
Trip output
Blocking input
1
1 & FL
Result
5.99
3.34
1.01
% Error
1.17%
1.18%
0.50%
Questions?
jmgers@gersusa.com