Professional Documents
Culture Documents
IEEMA Realistic-Ct-Specs PDF
IEEMA Realistic-Ct-Specs PDF
: Flux
ISRS : Secondary resistance voltage drop
ISXS : Secondary reactance voltage drop
IP NP : Total primary ampere turns.
ICNp : Component of primary ampere turns
required to supply core losses (usually
very small)
IM NP : Component of primary ampere turns
required to produce the flux.
ISNS : Secondary Ampere Turns.
IP NP : Component of primary Ampere Turns
required to neutralize secondary Ampere
Turns; opposite to ISNS
For bar primary, NP =1
2. CURRENT TRANSFORMER
CLASSIFICATION
Current transformers may be classified in the
following categories based on the application:
i. General protection class used for protective
relaying.
ii. Special protection class (Class PS) used in
current balance protection schemes.
iii. Metering class used in metering circuits.
3. PARAMETERS FOR CURRENT
TRANSFOMER SPECIFICATION
The key parameters required for complete current
transformer specification:
i. C.T. Ratio
ii. Number of cores
4. CT RATIO
CT ratio is defined as the ratio of rated primary
current to the rated secondary current.
4.1 Rated primary current
Factors influencing rated primary current:
i. Rating based on continuous thermal rating
A:
Maximum load current (mandatory) + 20%
overload capacity.
ii. Rating based on short time thermal rating
B: Rated short time current for 1 sec / 150
The higher current of the above two values (IA, IB)
decides primary current rating. This ensures robust
construction of the current transformer.
Fig.8
It may be mentioned in passing that, even if very
low burden numerical relays are used, only RR in
above expression is low but other factors are
significant.
The design value of CT secondary voltage is given
by
VDESIGN = Burden x Accuracy Limit Factor (A.L.F)
RAT (Secondary)
3
Fig.11
Now, CT1 has to develop enough voltage to drive
current through the complete CT circuit.
VREQUIRED during external fault condition with CT2
saturated,
VREQUIRED = IF (Rct1 + RL1+RL3+Rct2 + RL4+ RL2)
Assuming, Rct1 = Rct2 = Rct and
RL1= RL3= RL4= RL2= RL
VREQUIRED = IF (2*Rct + 4*RL)
VREQUIRED = 2* IF (Rct + 2*RL)
Therefore, knee point voltage, for Class PS CTs is
Vk (min) > VREQUIRED = 2 * IF (RCT + 2RL)
where,
VK (min) = Minimum Knee Point Voltage
IF = Max. through fault current to which CTs
are subjected to.
RCT = C.T secondary resistance typically varies
from 1 to 8
RL = Lead resistance typically 8 ohms / km for
2.5 mm2 Cu control cable
Fig.10
4
3 KA
RAT
e.g. - ------- = ------------- = 0. 05 5%
2F
2 x30 KA
As seen from above, under healthy conditions,
voltage required to be developed by CT is only 5%
of the knee point voltage. Therefore, specifying EX
@ VK / 4 (25%) is more than adequate whereas
specifying EX @ VK / 2 (50%) is a conservative
design resulting in bigger size of CTs. The exciting
current at VK / 4 is less than that at VK / 2 (Refer
Fig. 14). Considering a limiting value of 30mA for
exciting current, specifying 30mA @ Vk/4 is
adequate.
Fig.12
Therefore for such schemes the relay pickup
current is set based on the number of CTs in the
circuits and the exciting current for each CT.
Assuming a relay pickup of 10% i.e 0.1 A for a 1A
CT, the exciting current of CTs can be <30mA
when used for a three winding transformer (Refer
Fig.13). It can be even 45mA for a 1A CT for a two
winding transformer. On similar lines 150mA is
normally specified for 5A CT.
Fig.14
Generally identical class PS CTs are used in both
sides of the protected equipment. It is not
necessary to order both CTs from same vendor as
long as class PS requirements are met. Point by
point matching of saturation characteristics for the
CTs is not mandatory and not required. For
example, if EX < 30 mA @ VK/4 for both the CTs,
they are acceptable. (Refer Fig. 15).
Fig.13
Fig.15
6.2.2 EX to be specified at VK / 4 or VK / 2?
is relevant only during normal operating
EX
conditions to ensure stability and prevent false
tripping and is not relevant during faults. Under
fault conditions,
Knee point voltage (Vk) = 2F (RCT + 2 RL)
Under normal conditions,
RAT
VCT = RAT (RCT + 2 RL) = Vk ------2F
Special Protection
General Protection
Class
Class
1600/5A, Cl. PS, Vk >
1600/5A, Cl. 5P20, 20VA
130, Ie < 150mA @
Vk/4, Rct < 0.8 ohm
Current
Current
Volts
Volts
(mA)
(mA)
10
10
10
75
42
40
12
130
71
80
20
143
85
120
33
158 (Vk)
111
171 (Vk)
77
174
181
190
132
Table-1
6.3 Secondary winding resistance (Rct)
Winding resistance is part of the CT burden and is
taken into account while determining knee point
voltage requirement of CT. For special protection
class CTs (Class PS), CT secondary winding
resistance is usually specified. However it is
preferable to furnish expression for knee point
voltage, fault current and lead resistance values
and not to specify both knee point voltage and Rct
to the vendor. The vendor can then optimally
choose Rct to get the desired knee point voltage.
This will avoid oversizing of CTs.
Metering Class
General Protection
Class
Volts
Current
(mA)
Volts
Current
(mA)
40
12
10
80
20
20
12
120
33
30 (Vk)
22
171 (Vk)
77
33
33
190
132
Table-2
Generally I.S.F. is specified less than 5. However
this does not have much practical significance and
I.S.F = 10 is acceptable as the ammeters and
current coils of meters are designed to withstand
10 times the rated current for 5 seconds.
It may be noted that a current transformer with
high accuracy class and low I.S.F cannot be
realised in practice. High accuracy class requires
low excitation current which in turn results in
bigger core. The saturation point of a bigger core
is high which contradicts the requirement of low
I.S.F.
7. METERING CLASS
7.1 Accuracy class
Accuracy class is defined as the maximum ratio
error at rated current and at rated burden. Class
0.1, 0.2 and 0.5 CTs are used for precision
industrial metering / tariff metering. As per IS 2705 accuracy is not guaranteed for current less
than 20% of the rated current. If current through
the metered line is much less than the rated
current of CT, for majority of time, anticipated
accuracy is never realised in practice. This is
mostly true for tie lines connecting industrial plants
with captive power plant and grid.
8. CONCLUSION
The article covers salient aspects that the user
should consider to realize CTs that are not
oversized. A radical rethink when selecting
primary rating of CT for protection application is
needed. Extreme care shall be exercised when
selecting knee point voltage and exciting current
for CTs used in current balanced schemes. I.S.F
for metering CTs can be 10 without endangering
meters. The practicing engineer is encouraged to
apply the ideas presented here to realize optimally
sized CTs.
9. REFERENCES
i. Protective Relays- Application Guide GEC
Measurements
ii. The design of Electrical Systems for large
projects (in India) N Balasubramanyam
iii. Electrical Measurements and Measuring
Instruments E. W. Golding