Installation length Lm
In order to make maximum use of the total movement available in any bellow, it is correct to install
the unit into the piping system pre-stretched to use its full compression potential. The degree
of stretching is termed its cold- pull or sprung dimension. Knowing the anticipated maximum (tmax) and minimum (tmin) operating temperatures is vital to make suitable provision for thermal
expansion at installation (tmon).
=
tmon - tmin
- (
).
tmax - tmin
2
(mm)
COLD-PULL
(+) extension, (-) compression
(mm)
Lv (mm)
Lm (mm)
installation length
(pre-stretched)
Guides
The guides do not only support the pipework, but also maintain the correct alignment, so that the Expansion Joint works adequately.
The positioning of the guides in accordance with the rules detailed further on, will prevent buckling of
the line due to the flexibility of the expansion joint.
1.20
MACROFLEX
In principle we can divide the guides into two large groups. Those for strictly axial guiding and those
which will also allow movement in a plane perpendicular to the axial movement.
The axial guides, besides guiding and supporting the weight of the pipework can withstand a lateral
thrust of app. 15% of the axial thrust. It is advantageous if the first two guides immediatelly adjacent to
the Expansion Joint are concentric with the pipe.
w
(less value is valid)
2
L 1
min 4 x DN or 2 x DN +
L 2
14 x DN
L3
L1
PB
L1
Legend:
w
pipe movement
DN nominal diameter
L2
L3