PROJECT NAME:

Underground Pump House Design


YCL, Youngone (CEPZ) Ltd.

Designed BY:

LUMINARS ENGINEERS ASSOCIATION

Ensuring Smart & Secure Future

1|Page

LUMINARS ENGINEERS ASSOCIATION

Design Calculation for YCL Pump House


Pump house self-weight = { ( 17x 11 x 2) + ( 29x 11x 2) + ( 30x 18x 2) } .833x 1150x 1.5
= 392093 lb
= 392.093 Kip
Assume,
Machinery weight = 10 Ton
= 22000 lb
= 22 Kip
Surcharge weight = 100 lb/Sft
= (100x 15x 27)
= 40500 lb
= 40.5 Kip.
Total weight = (393 + 22+41) Kip
= 456 Kip
Applied pressure = (456/ 19x 31) kip/ ft 2
= 0.774 kip/ft 2

Bearing capacity Check


After proper foundation improvement as per provide design, drawings we can assume bearing
capacity of soil = 1.5 Kip/ fi2, Fs = 2.5
Applied load = 456 Kip
Required Area, A r = 456 / 1.5
= 304 Sft
Now, provided Area, A p = (31 x 19)
= 589 sft.
Here, Ar < A p
So, foundation is safe for soil bearing capacity.

Luminars Engineers Association


Chittagong Office:56,Jibon Bima Bhaban,Agrabad,Chittagong, Bangladesh,. Phone: +8801778726136, +8801827424211, +8801714289454, +8801911464136

LUMINARS ENGINEERS ASSOCIATION

Flexure capacity check for wall

T=10"

P
H=10'

Wb

WV

HS

Hb

10"

VB
Here Assume,
Concrete strength, f c
Rebar Strength, f y
Lateral soil pressure, P a
Passive pressure, Pp
Surcharge weight, W s
Service gravity load P
Thickness of stem, T
Height of stem, H
Footing Thickness

=
=
=
=
=
=
=
=
=

3000 psi
60000 psi
30 pcf.
250 psf / f.
100 psf.
2 Kip/f.
10"
10'.
10"

Here,
H b = SP a H2 = 1.50 Kips.
H s = Ws P a H = .3 Kip.
H p = .5 Pp (hp + h f) =.11Kips.
W s = W s LH = .2 Kips.
R B = Hs + HB - R T = .4 Kip.
W w = T (Hp) m = .92 Kip.
P = VB - WWS (H)
= 2.77 Kips @ M max section.

Luminars Engineers Association


Chittagong Office:56,Jibon Bima Bhaban,Agrabad,Chittagong, Bangladesh,. Phone: +8801778726136, +8801827424211, +8801714289454, +8801911464136

LUMINARS ENGINEERS ASSOCIATION

Here,
S = 1.63 ft.
M Amax = SRB - SHS S/H2 -.5 Pa s3- Pa (H-S) 2 S/6.
= 0.60 ft/ Kips.

MMAX
S

RB
VB
Maximum allowable moment for provided section,
Mallow able = As Fs (d - kd/3) + P (tc/2 - kd/3)
= 1.74 ft - Kips.
Here,
Fs = 24 Ksi
t e = 9.63 in.
d = 6.13 in.
Hence Mallow able > M max
So, pump house wall is safe for flexural status.

Designed Prepared by

Design Checked by

Engr. MIZANUR RAHMAN SIFAT


B.Sc Engineer (Civil), CUET.
Assistant Engineer,

MOHAMMAD TAREQUL ALAM


Asst Professor,
Department of Civil Engineering,
Chittagong University of Engineering &
Technology.
MIEB-23164

Luminars Engineers Association


CELL: +8801827424211

Luminars Engineers Association


Chittagong Office:56,Jibon Bima Bhaban,Agrabad,Chittagong, Bangladesh,. Phone: +8801778726136, +8801827424211, +8801714289454, +8801911464136

You might also like