You are on page 1of 13

DESIGN CRITERIA

PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

PROJECT NAME : DETAILED ENGINEERING DESIGN FOR


FACTORY BUILDING CONSTRUCTION

LOCATION : KENDAL INDUSTRIAL PARK - CENTRAL JAVA

TITLE DOCUMENT : CIVIL DESIGN CRITERIA

REV. NO DATE DESCRIPTION PRE'D CHK'D APP'D

A 05/02/2020 Issued for Information


DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

TABLE OF CONTENTS

TABLE OF CONTENTS …...........................................................................................................


2
REVISION CONTROL SET …....................................................................................... 3
COMMENT'S SHEET CONTROL …............................................................................. 3

1. GENERAL 4
1.1 OUTLINE OF STRUCTURE …...............................................................................................................
…...................................................
4
1.2 APPLICABLE SPECIFICATIONS, CODES AND STANDARD …...........................................
4
1.3 ALLOWABLE STRESS AND UNIT WEIGHT OF MATERIAL …...........................................................
4
1.4 UNIT OF MEASUREMENT …...............................................................................................
4

2. STABILITY PARAMETER …….................................................................................................


5

3. BASIC ASSUMPTION ….............................................................................................................


5

4. LOAD COMBINATION
4.1 LOAD COMBINATION - UNFACTORED (ASD) …...................................... 5
4.2 LOAD COMBINATION - FACTORED (LRFD)…............................................... 5

5. LOADING INPUT
5.1 SELFWEIGHT STRUCTURE (DS) …........................................................... 6
5.2 DEAD LOAD (DL) …............................................................... 6
5.3 LIVE LOAD (LL) …................................................................................ 7
5.4 WIND LOAD (W) …................................................................................ 7
5.5 QUAKE LOAD (EQ) …............................................................................. 7

7. PERHITUNGAN STRUKTUR ATAS …...................................................................... 16


7.1 PERMODELAN STRUKTUR …..................................................................... 16
7.2 INPUT PEMBEBANAN …............................................................................ 17

8. CEK HASIL ANALISIS …........................................................................................ 21


8.1 CEK STRESS RATIO ….............................................................................. 21
8.2 CEK STABILITAS STRUKTUR ….................................................................. 22

DAFTAR LAMPIRAN
LAMPIRAN 1 GAMBAR DASAR PERHITUNGAN STRUKTUR
LAMPIRAN 2 REFERENSI STANDAR PERATURAN YANG DIGUNAKAN
LAMPIRAN 3 GAMBAR REKOMENDASI PERKUATAN STRUKTUR

Page 2 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

REVISION CONTROL SET

REV. NO DATE DESCRIPTION


A 05/02/2020 Issued for Information

COMMENT'S SHEET CONTROL

PAGE COMMENT'S

Page 3 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

1. GENERAL
1.1 OUTLINE OF STRUCTURE
Scope : CIVIL DESIGN CRITERIA
Project : DETAILED ENGINEERING DESIGN FOR
FACTORY BUILDING CONSTRUCTION
Location : KENDAL INDUSTRIAL PARK - CENTRAL JAVA
Structure type : CONCRETE AND STELL

1.2 APPLICABLE SPECIFICATIONS, CODES AND STANDARD


1. Project Specification : -

2. Codes and Standards


SNI-03-1727-2013 : Pedoman Perencanaan Pemebebanan Untuk Rumah dan Gedung
SNI-03-1726-2012 : Tata Cara Perencanaan Ketahanan Gempa untuk Bangunan Gedung
PIP STC01015 : (Process Industry Practices Structural) Structural Design Criteria
SNI-03-1729-2015 : Tata Cara Perhitungan Struktur Baja Untuk Bangunan Gedung
ASCE 7-10 : American Society of Civil Engineering

1.3 ALLOWABLE STRESS AND UNIT WEIGHT OF MATERIAL


Specification for material concrete :
Precast Concrete (Spun Pile, Sheet Pile, etc) fc' = 42 Mpa
Pedestal fc' = 25 Mpa
Pile Cap fc' = 25 Mpa
Tie Beam fc' = 25 Mpa
Slab fc' = 25 Mpa
Equipment Slab fc' = 30 Mpa
Practice Column fc' = 14.5 Mpa
Modulus Elasticity Ec = 23500 Mpa
Quality Deforrmed Bar (Deform bar) fy = 400 Mpa
Quality Plain Reinforcement (Plain bar) fy = 240 Mpa
Concrete Specific Gravity gc = 24 kN/m3
Structural steel
Steel Structure = Q235 / A36 / SS400
Anchor Bolt = A307
High Strength Bolt = A325

1.4 UNIT OF MEASUREMENT


Unit of measurement in design shall be in SI metric system.

2. STABILITY PARAMETER
Bearing Capacity of Shallow Foundation = 3
Bearing Capacity of Depth Foundation
Axial Capacity = 3
Friction Capacity = 5
Settlement = 25 mm

Sliding = 1.5
Overtunning = 1.5
Uplift = 1.5

Page 4 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

3. BASIC ASSUMPTION
- Unfactored Load Comb for Stability Check
- Factored Load Comb for Strength Check.

4. LOAD COMBINATION
Basic combination Refer to SNI 1727-2013 :

4.1 LOAD COMBINATION - UNFACTORED (ASD)


LC LOAD COMBINATION DESCRIPTION
1.1 DS + DL Selfweight + Dead
1.2 DS + DL + LL Selfweight + Dead + Live
1.3 DS + DL + 0.7 EQX Selfweight + Dead + Quake
1.4 DS + DL + 0.7 EQZ Selfweight + Dead + Quake
1.5 DS + DL + 0.6 WX Selfweight + Dead + Wind
1.6 DS + DL + 0.6 WZ Selfweight + Dead + Wind

4.2 LOAD COMBINATION - FACTORED (LRFD)


LC LOAD COMBINATION DESCRIPTION
2.1 1.4 (DS + DL) Selfweight + Dead
2.2 1.2 (DS + DL) + 1.6 LL Selfweight + Dead + Live
2.3 1.2 (DS + DL) + EQX Selfweight + Dead + Quake
2.4 1.2 (DS + DL) + EQZ Selfweight + Dead + Quake
2.5 1.2 (DS + DL) + WX Selfweight + Dead + Wind
2.6 1.2 (DS + DL) + WZ Selfweight + Dead + Wind

5. LOADING INPUT
5.1 SELFWEIGHT STRUCTURE (DS)
Self weight automatic added by software with multiplier is 1
Weight for floor plate add bondeks 0.105 kN/m2 :
No. Thick. Slab Min. (cm) Load Value (kN/m2) Placement
1 20 4.91 Ground
2 13 3.23 Second floor

5.2 DEAD LOAD (DL)


Reffering to PPIUG 1987 :
No. Type of load Thickness (cm) Load Value (kN/m2)
1 Mortar 2 0.42
2 Sand 2 0.032
3 Ceramics 1 0.24
4 Ceiling - 0.11
5 ME Instalation - 0.25
6 Partition Wall - 0.72
Total 1.772
Masonry = 2.50 kN/m2
Water Tank for Toilet = 15.00 kN/m2

Page 5 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

5.3 LIVE LOAD (LL)


Mengacu kepada SNI 1727-2013, Tabel 4.1 :
No. Penggunaan Nilai Beban (kN/m2)
1 Warehouse (Light) 6.00
2 Warehouse (Heavy) 11.97
3 Office 2.40
4 Roof 0.96
5 Meeting Room 4.79
6 Stairs 3.00
7 Balcony 4.79

5.4 WIND LOAD (W)


Refer to PPIUG 1987 :
Load value for Eclat project is 0.40 kN/m2, because near the beach.

Page 6 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

5.5 QUAKE LOAD (EQ)


Earthquake load refer to SNI 1726 - 2012.
Location project in Kendal - Center Java, with coordinate data (KIK based on Google Maps) :
Latitude = -6.935448
Longitude = 110.248002
Assumtion is soft soil.

Page 7 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

Page 8 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

Page 9 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

Page 10 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

Page 11 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

Page 12 of 13
DESIGN CRITERIA
PT. WAHANACIPTA
ECLAT TEXTILE INTERNATIONAL
BANGUNWISMA
Document No. Rev. Description Date
CDC-001 A Issued for Information 05/02/2020

Refer to Puskim.pu.go.id and SNI 1726-2012 :

No. Variable Value


1 PGA (g) 0.304
2 SS (g) 0.657
3 S1 (g) 0.252
4 FA 1.386
5 FV 2.990
6 Sms 0.911
7 Sm1 0.755
8 SDS (g) 0.607
9 SD1 (g) 0.503

R = Modification factor respons (Table 9, SNI 1726-2012) :


R = 4.5
Ωo = Strength system (Table 9, SNI 1726-2012) = 3
Cd = Deflection factor (Table 9, SNI 1726-2012) = 4
Ie = Importance factor (Table 2, SNI 1726-2012) = 1.50
Ct = (Table 15, SNI 1726-2012) = 0.0724
x = (Table 15, SNI 1726-2012) = 0.8
T = Fundamental period Ct * hx = 0.67

Page 13 of 13