Medium-Voltage Equipment
Selection and Ordering Data
Catalog HG 11.05 2010
R-HG11-172.tif
3AH5 Vacuum
Circuit-Breakers
Medium-Voltage Equipment
Catalog HG 11.05 2010
Invalid:
Catalog HG 11.05 2007
Catalog HG 11.05 2008 (PDF version only)
Contents
Contents
Page
Description
General
10
Equipment Selection
11
12
13
15
Additional equipment
20
21
Technical Data
23
24
31
Circuit diagrams
32
Annex
33
Inquiry form
34
Configuration instructions
35
Configuration aid
Foldout page
R-HG11-173.tif
Description
Contents
Contents
Page
Description
General
R-HG11-174.tif
Pole assemblies
Operating mechanism
Trip-free mechanism
Releases
Closing
Interlocking
Standards
Maintenance-free design
Ambient conditions
Dielectric strength
10
Basic equipment
10
Description
General
R-HG11-185.eps
R-HG11-201.eps
Description
Construction and mode of operation
The 3AH5 vacuum circuit-breaker consists of the pole assemblies (1) and the operating mechanism box (2). The pole
assemblies are fixed to the operating mechanism box via
post insulators (3). The switching movement is transferred
by means of operating rods (4) and levers.
Pole assemblies
8
7
HG11-2543 eps
Circuit-breaker structure
1 Pole assembly
5 Vacuum interrupter
3 Post insulator
4 Operating rod
8 Brace
Operating mechanism
R-HG11-186.tif
3AH5 vacuum circuit-breakers have a trip-free mechanism according to IEC 62271-100. In the event of an opening command being given after a closing operation has been initiated,
the moving contacts return to the open position and remain
there even if the closing command is sustained. This means
that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible according to
IEC 62271-100.
R-HG11-187.tif
Trip-free mechanism
Description
Construction and mode of operation, standards and maintenance-free design
Releases
Description
Ambient conditions, current carrying capacity and dielectric strength
Ambient conditions
The vacuum circuit-breakers are designed for the normal
operating conditions defined in IEC 62271-100.
Condensation can occasionally occur under the ambient
conditions shown opposite. 3AH5 vacuum circuit-breakers
are suitable for use in the following climatic classes
according to IEC 60721, Part 3-3:
Class 3K4 1)
Class 3B1
Class 3M2
Class 3C2 2)
Class 3S2 3)
-5C
HG11-2515_en eps
40C
Dielectric strength
2600
1400
U W U0 x Ka
U
U0
Ka
Example
For a requested rated lightning impulse withstand voltage
of 75 kV at an altitude of 2500 m, an insulation level of
90 kV under reference atmosphere is required as a minimum:
1000
600
1
10
20
30
1500
2000
40
50
60 C 70
Ambient air temperature
1.50
Altitude correction factor
1800
2200
HG11-2545c_en eps
3400
A
3000
1.40
1.30
1.20
HG11-2517c_en eps
1.10
1.00
1000
2500
90 kV W 75 kV x 1.2
Description
Product range overview and basic equipment
Rated voltage
kV
kA
12
13.1
16
20
25
31.5
25
31.5
16
20
25
16
25
17.5
24
36
1250
2000
2500
210
n
n
n
n
n
n
n
n
275
160
210
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
275
350
210
275
350
210
n
n
n
n
n
n
n
n
n
n
n
n
n
275
n
n
n
n
n
n
n Available design
Basic equipment
In the basic version, the 3AH5 is equipped with a manual spring-operated mechanism. The following overview shows the
alternatively selectable or additional equipment, as well as the possibility of designing the switching device with storedenergy mechanisms.
n Basic equipment
4)
10
Not available
Mechanical
interlocking
Circuit-breaker
tripping signal
Counter
n
2nd release
64-pole
plug connection
24-pole
plug connection
24-pole
terminal strip
Without
terminal strip
Auxiliary switch
12 NO + 12 NC
Auxiliary switch
6 NO + 6 NC
Auxiliary switch
2 NO + 2 NC
Electrical
closing lock-out 3)
Closing solenoid
Type of operating
mechanism
Equipment Selection
Contents
Contents
Page
Equipment Selection
Ordering data and configuration example
11
12
13
13
Voltage level 24 kV
14
Voltage level 36 kV
14
15
16
R-HG11-184.tif
Operating voltage,
shunt release
16
17
18
18
19
19
20
21
R-HG11-188.eps
1st
11
Equipment Selection
Ordering data and configuration example
Special versions ()
Order codes
Individual equipment versions, marked with 9 or Z in the
9th to 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.
a: alphabetical
Position:
Order No.:
1st position
n: numerical
10 11 12
13 14 15 16
3 A H 5
Order codes
n n n
Primary part
Superior group
Switching devices
2nd position
Main group
Circuit-breaker
3rd position
Subgroup
Circuit-breaker type series
Basic equipment
Design and ratings
primary part
Secondary part
Secondary equipment
Operating mechanism, releases, operating
voltages and further auxiliary equipment
Order codes
Group of 3 after the Order No.
Format: a n a
Special versions ()
Initiated with -Z
Group of 3 after the Order No.
Format: a n n
Configuration example
In order to simplify the selection of the correct order number
for the requested circuit-breaker type, you will find a configuration example on each page of the chapter Equipment
Selection. For the selection of the secondary part, always the
last example of the primary part was taken over and continued,
so that at the end of the equipment selection (page 20) a
completely configured circuit-breaker results as an example.
12
3 A H 5
1 n n n n n n n n
Equipment Selection
Selection of basic types, circuit-breakers
kV
kV
kV
kA
12
75
28
13.1
10 11 12
13 14 15 16
Order codes
n n n
See page 20
See page 19
See page 19
See page 18
See page 18
Rated short-circuit
making current
(at 50/60 Hz)
Ima
See page 17
Rated short-circuit
breaking current
at 36 % DC component
Isc
See page 16
Rated short-duration
power-frequency
withstand voltage
Ud
Pole-centre distance
Rated voltage
Ur
3 A H 5 n n n n n n n n n n n n
See page 16
Position:
Order No.:
50/60 Hz
See page 15
12 kV
Ir
kA
mm
33/34
160
210
160
800
800
16
40/42
800
1250
210
800
1250
20
50/52
160
800
1250
210
800
1250
2000
25
63/65
160
800
1250
210
800
1250
2000
2500
31.5
80/82
160
1250
210
1250
2000
2500
Special version Ud = 42 kV (available for all 12 kV W 25 kA circuit-breakers)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
3
2
2
3
3
2
2
3
3
3
4
4
5
5
3
3
2
3
3
3
1
1
2
2
2
2
3
3
3
3
3
4
4
4
4
4
4
5
5
5
5
1
1
1
2
1
2
1
2
1
2
4
1
2
1
2
4
6
2
2
4
6
6 n n n n n n n n
17.5 kV
50/60 Hz
Ur
Up
Ud
Isc
Ima
kV
kV
kV
kA
kA
mm
17.5
95
38
25
63/65
160
Ir
A
800
1250
210
800
1250
2500
31.5
80/82
160
1250
210
1250
2000
2500
Special version Ud = 42 kV (available for all 17.5 kV circuit-breakers)
Configuration example
3AH5 vacuum circuit-breaker
Rated voltage Ur = 17.5 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2500 A
Pole-centre distance = 210 mm
Special version Ud = 42 kV
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
H
H
H
H
H
H
H
H
H
5
5
5
5
5
5
5
5
5
2
2
2
2
2
2
2
2
2
0
0
1
1
1
0
1
1
1
4
4
4
4
4
5
5
5
5
1
2
1
2
6
2
2
4
6
3 A H 5
3 A H 5
E 1 3
13
Equipment Selection
Selection of basic types, circuit-breakers
kV
kV
kV
kA
kA
mm
125
50
16
40/42
210
800
1250
800
1250
1250
2000
2500
1250
2000
2500
1250
2500
1250
2500
275
50/52
210
275
25
10 11 12
13 14 15 16
63/65
210
275
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
H
H
H
H
H
H
H
H
H
H
H
H
H
H
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2
2
2
2
2
2
2
2
2
2
2
2
2
2
7
7
8
8
7
7
7
8
8
8
7
7
8
8
2
2
2
2
3
3
3
3
3
3
4
4
4
4
1
2
1
2
2
4
6
2
4
6
2
6
2
6
3
3
3
3
3
A
A
A
A
A
H
H
H
H
H
5
5
5
5
5
3
3
3
3
3
2
1
2
1
1
2
2
4
4
4
2
2
2
2
4
4 n n n n n n n n
36 kV
50/60 Hz
Ur
Up
Ud
Isc
Ima
kV
kV
kV
kA
kA
mm
36
170
70
16
40/42
25
63/65
275
350
275
350
1250
1250
1250
1250
2000
Ir
Configuration example
3AH5 vacuum circuit-breaker
Rated voltage Ur = 36 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-centre distance = 350 mm
3 A H 5
14
Order codes
3 A H 5
See page 20
See page 19
See page 19
See page 18
Ir
24
20
See page 18
Rated short-circuit
making current
(at 50/60 Hz)
Ima
See page 17
Rated short-circuit
breaking current
at 36 % DC component
Isc
See page 16
Rated short-duration
power-frequency
withstand voltage
Ud
Pole-centre distance
Rated voltage
Ur
3 A H 5 n n n n n n n n n n n n
See page 16
Position:
Order No.:
50/60 Hz
See page 15
24 kV
n n n
Equipment Selection
Selection of secondary equipment
n
n
n
n
n
n
n
10 11 12
M
N
R
U
U
V
V
n
n
n
n
n
n
13 14 15 16
Order codes
n n n
See page 20
See page 19
See page 19
See page 18
See page 18
See page 17
See page 16
C.t.-operated release
with tripping pulse
W 0.1 Ws (20 O)
C.t.-operated release
with tripping pulse
W 0.1 Ws (10 O)
C.t.-operated release
1.0 A
C.t.-operated release
0.5 A
3 A H 5 n n n n n n n n n n n n
See page 16
Position:
Order No.:
Undervoltage release
9th position
Release combination
Configuration example
3AH5 vacuum circuit-breaker
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-centre distance = 350 mm)
1st shunt release; c.t.-operated release
with a rated normal current of 1.0 A
Example for Order No.:
Order codes:
3 A H 5
3
4
U
3 A H 5
A 4 6
4 U n n n n n n n
15
Equipment Selection
Selection of secondary equipment
10 11 12
13 14 15 16
Order codes
n n n
See page 20
See page 19
See page 19
Special voltages
See page 18
3 A H 5 n n n n n n n n n n n n
See page 17
Standard voltages
Position:
Order No.:
See page 18
10th position
Operating voltage of the closing solenoid
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
A
B
C
D
E
F
H
J
K
Z
Z
Z
Z
Z
Z
Z
Z
Z
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
K
K
K
K
K
K
K
K
K
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
L
L
L
L
L
L
L
L
L
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
11th position
Operating voltage of the 1st shunt release
Standard voltages
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
100 V AC
110 V AC
230 V AC
Special voltages
1
2
3
4
5
6
7
8
9
9
9
9
9
9
9
9
9
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
16
3 A H 5
A
4 U
C
2
4 U C
2 n n n n n
Equipment Selection
Selection of secondary equipment
10 11 12
50/60 Hz 1)
50/60 Hz 1)
50/60 Hz 1)
Order codes
n n n
See page 20
See page 19
See page 19
Special voltages
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
125 V AC
240 V AC
13 14 15 16
3 A H 5 n n n n n n n n n n n n
See page 18
Standard voltages
Position:
Order No.:
See page 18
12th position
Operating voltage of the 2nd release
0
1
2
3
4
5
6
7
8
9
9
9
9
9
9
9
9
9
M
M
M
M
M
M
M
M
M
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
9
9
9
9
9
9
9
9
M
M
M
M
M
M
M
M
2 D
2 E
2 F
2 G
3 D
3 E
3 F
3 G
Special version
To operate the 2nd release as an undervoltage release on an
energy store type AN1902- (for DC) or AN1901-2 (for AC),
both make Bender, the operating voltage must be defined
and whether the energy store will be provided by the customer
or included in the scope of supply.
Energy store
Type
60 V DC
110 V DC
220 V DC
100/110/230 V AC
60 V DC
110 V DC
220 V DC
100/110/230 V AC
AN1902AN1902AN1902AN1901-2
AN1902AN1902AN1902AN1901-2
In the scope
of supply
no
no
no
no
yes
yes
yes
yes
Configuration example
3AH5 vacuum circuit-breaker
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-centre distance = 350 mm)
2nd release as c.t.-operated release with a rated normal current of 1.0 A
Example for Order No.:
Order codes:
3 A H 5
3
4 U C
2
0
3 A H 5
A
4 U C
n n n n
6
Siemens HG 11.05 2010
17
Equipment Selection
Selection of secondary equipment
13th position
Counter and circuit-breaker tripping signal
Position:
Order No.:
10 11 12
13 14 15 16
Order codes
3 A H 5 n n n n n n n n n n n n
n n n
n
n
n
1)
1)
n Equipment to be selected
See page 20
See page 19
See page 19
Definition
15th position n
(see page 19)
64-pole plug
A, B
E, F, G
and H
E, F, G
and H
1)
J, K, L
and M
Dependent equipment
1)
1)
24-pole terminal
strip/plug
Without terminal
strip/plug
Counter
Circuit-breaker
tripping signal
14th position
Operating voltage of the operating mechanism/
type of operating mechanism
Type of operating mechanism /
standard voltages
Special voltages
Manual operat. stored-energy mechan. (hand crank incl. in the scope of supply)
Manual spring-operated mechan. (hand crank incl. in the scope of supply)
A
X
B
C
D
E
F
H
J
K
Z
Z
Z
Z
Z
Z
Z
Z
Z
Configuration example
3AH5 vacuum circuit-breaker
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-centre distance = 350 mm)
With counter and circuit-breaker tripping signal
Manual operating stored-energy mechanism
Example for Order No.:
Order codes:
18
3 A H 5
3
U C
2
A
3 A H 5
A
4 U C
A n n
P
P
P
P
P
P
P
P
P
1 A
1 B
1 C
1 D
1 E
1 F
1 K
1 L
1 M
Equipment Selection
Selection of secondary equipment
15th position
Position:
Auxiliary switch, secondary connection, interlocking Order No.:
10 11 12
13 14 15 16
Order codes
3 A H 5 n n n n n n n n n n n n
n n n
1
n
n
1
n
n
n
1 2) or 2
n
n
1 2) or 2
n
n
n
1 2) or 2
n
n
1 2) or 2
n
n
n
5
n
n
5
n
n
n
5
n
n
5
n
n
n
Special versions gold-plated contacts and pins
Auxiliary switch 6 NO + 6 NC and 64-pole plug connector (J or K)
Auxiliary switch 12 NO + 12 NC and 64-pole plug connector (L or M)
See page 20
See page 18
Mechanical
interlocking
64-pole
plug 2)
24-pole
plug
24-pole
terminal strip
Without
terminal strip 1)
Auxiliary switch
12 NO + 12 NC 2)
Auxiliary switch
6 NO + 6 NC
Auxiliary switch
2 NO + 2 NC 1)
Definition
13th position n
(see page 18)
n
n
n
n
n
n
n
n
n
n
A
B
E3)
F3)
G3)
H3)
J4)
K4)
L4)
M4)
Z
Z
A
A
2
2
0
1
16th position
AC frequency of operating voltages
Languages of operating instructions and rating plate
n
n
50 Hz and DC
60 Hz and DC
50 Hz
60 Hz
n
n
DC
n
n
Frequency selection
Spanish
French
English
German
Language selection
0
1
2
3
4
5
6
7
n
n
n
n
n
n
n
n
n
Other languages on request
Special versions
Additional information on the rating plate (only after consultation with
the order processing department of the Switchgear Factory Berlin).
Information in clear text.
Configuration example
3AH5 vacuum circuit-breaker
(Ur = 36 kV, Isc = 25 kA, Ir = 2000 A, pole-centre distance = 350 mm)
Auxiliary switch 6 NO + 6 NC, 24-pole plug and mechanical interlocking
Frequency DC, operating instructions and rating plate in English
Example for Order No.:
Order codes:
3 A H 5
3
U C
A
H
2
3 A H 5
A 4 6
4 U C
A H 2
19
Equipment Selection
Selection of additional equipment
Additional equipment
Position:
Order No.:
10 11 12
13 14 15 16
Order codes
3 A H 5 n n n n n n n n n n n n
n n n
Options
Z
Z
Z
Z
Z
Z
A
A
A
A
B
F
1
3
3
4
0
2
0
0
1
7
0
0
Configuration example
3AH5 vacuum circuit-breaker
Rated voltage Ur = 36 kV
Rated short-circuit breaking current Isc = 25 kA
Rated normal current Ir = 2000 A
Pole-centre distance = 350 mm
1st shunt release, c.t.-operated release with a rated normal current of 1.0 A
Operating voltage of the closing solenoid 48 V DC
Operating voltage of the 1st shunt release 48 V DC
2nd release as c.t.-operated release with a rated normal current of 1.0 A
With counter and breaker tripping signal
Manual operating stored-energy mechanism
Auxiliary switch 6 NO + 6 NC, 24-pole plug and mechanical interlocking
Frequency DC, operating instructions and rating plate in English
Routine test certificate enclosed
Example for Order No.:
Order codes:
20
3 A H 5
4
U
C
2
0
2
A
H
2
3 A H 5
A 4 6 +
3
F
1
2
4
0
4 U C
A H
Equipment Selection
Accessories and spare parts
Retrofitting
When releases/solenoids are retrofitted, the order numbers
of the mounting parts must also be specified. For other additional equipment, the required mounting parts are included
in the delivery.
HG11-2587b_en eps
The order numbers are applicable to vacuum circuitbreakers of current manufacture. When mounting parts
or spare parts are being ordered for an existing vacuum
circuit-breaker, always quote the type designation, serial
number and the year of manufacture of the circuit-breaker
to be sure to get the correct delivery.
Spare parts
As spare parts, the vacuum interrupters are always supplied
as a complete pole including post insulator.
To select the correct spare interrupter, please specify the
type designation, serial number and year of manufacture of
the circuit-breaker. All data is given on the rating plate.
Vacuum interrupters and other spare parts must only be
replaced by instructed personnel.
Note:
For any query regarding spare parts,
subsequent deliveries, etc. the following
three details are necessary:
Type designation
Serial No.
Year of manufacture
Designation
Hand crank
Wire bundle
Remarks
Order No.
3AX15 30-2B
With 10 wires for auxiliary switch connection to
64-pole plug connector
24-pole plug connector
24-pole terminal strip
Upper part of plug incl. sockets
Lower part of plug incl. pins
Complete plug connector
Upper part of plug incl. socket insert
Lower part of plug incl. pins
Complete plug connector
(for wire cross-section 1.5 mm2)
Crimp pins for lower part of plug
Crimp sockets for upper part of plug
Crimping pliers
Disassembly tool
3AX11 34-2D
3AX11 34-2B
3AX11 34-2C
3AX11 34-5A
3AX11 34-5B
3AX11 34-6A
3AX11 34-5C
3AX11 34-5D
3AX11 34-7A
24-pole
64-pole
64-pole
3AX11 34-3A
3AX11 34-4B
3AX11 34-4C
3AX11 34-4D
3AX11 34-4G
21
R-HG11-201.eps
22
Technical Data
Contents
Contents
Page
Technical Data
23
26
Voltage level 24 kV
28
Voltage level 36 kV
30
Operating times
31
31
31
Circuit diagrams
32
R-HG11-202.tif
Voltage level 12 kV
R-HG11-203.tif
23
Technical Data
160
13.1
36
14.7
800
160
16
36
17.9
1250
160
16
36
17.9
800
160
20
36
22.4
1250
160
20
36
22.4
1250
160
31.5
36
35.4
800
210
13.1
36
14.7
800
210
16
36
17.9
1250
210
16
36
17.9
800
210
20
36
22.4
1250
210
20
36
22.4
2000
210
20
36
22.4
2000
210
25
36
28
2500
210
25
36
28
1250
210
31.5
36
35.4
2000
210
31.5
36
35.4
2500
210
31.5
36
35.4
800
160
25
36
28
1250
160
25
36
28
800
210
25
36
28
1250
210
25
36
28
kV
mV
75
28
6.0
90
135
88
95
35
S_ 441 00641
1.1
75
28
3.4
120 135
71
95
40
S_ 441 00643
1.3
75
28
3.4
120 135
71
95
40
S_ 441 00643
1.3
75
28
3.4
120 135
71
95
40
S_ 441 00643
1.3
75
28
3.4
120 135
71
95
40
S_ 441 00643
1.3
75
28
3.0
129 135
60
95
40
S_ 441 00651
1.5
75
28
6.0
90
135 138
95
35
S_ 441 00642
1.2
75
28
3.4
95
40
S_ 441 00644
1.4
75
28
3.4
95
40
S_ 441 00644
1.4
75
28
3.4
95
40
S_ 441 00644
1.4
75
28
3.4
95
40
S_ 441 00644
1.4
75
28
1.8
129 135
91
95
55
S_ 441 00646
1.6
75
28
1.8
129 135
91
95
55
S_ 441 00646
1.6
75
28
1.8
129 135
91
95
55
S_ 441 00646
1.6
75
28
3.0
95
45
S_ 441 00645
1.7
75
28
1.8
129 135
91
95
55
S_ 441 00646
1.6
75
28
1.8
129 135
91
95
55
S_ 441 00646
1.6
75
28
3.8
90
135
75
95
40
S_ 441 01301
1.8
75
28
3.8
90
135
75
95
40
S_ 441 01301
1.8
75
28
3.8
90
135 125
95
45
S_ 441 01302
1.9
75
28
3.8
90
135 125
95
45
S_ 441 01302
1.9
Minimum clearance,
phase-to-phase
kV
800
kA
33/
34
40/
42
40/
42
50/
52
50/
52
80/
82
33/
34
40/
42
40/
42
50/
52
50/
52
50/
52
63/
65
63/
65
80/
82
80/
82
80/
82
63/
65
63/
65
63/
65
63/
65
Weights
kA
Ud
Minimum clearance,
phase-to-earth
Up
kA
Ima
mm
Isc
O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO
Pole-centre distance
Order No.
Ir
tk
50/60 Hz
12 kV
DC component in %
of the rated short-circuit breaking current
mm mm mm mm
kg
24
Technical Data
Electrical data, dimensions and weights
20 000
20 000
10 000
10 000
is shown as a function
of the breaking current
(r.m.s. value). All vacuum
2 000
5 000
2 000
1 000
1 000
500
M2 and C2 according
500
100
parameters defined in
20
10
0.5
200
100
2
1
HG11-2546d_en eps
80
50
30
200
10 16 20 25 kA 50
50
25
20
10
0.5
5 kA 10 13.1 20 31.5
HG11-2547d_en eps
5 000
Operating cycles
Operating cycles
50
tive application.
Dimension
drawing
a
mm
b
mm
c
mm
d
mm
1.1
160
432
490
392
1.2
210
534
592
492
1.3
160
432
490
409
1.4
210
534
592
509
1.5
160
432
490
422
1.6
210
534
592
539
1.7
210
534
592
522
1.8
160
432
490
405
1.9
210
534
592
505
d
c
HG11-2548a eps
44
435
170
482 (558)
90
a = Pole-centre distance
b = Width of cross member
c = Width of cross member incl. lugs
d = Largest energized width
25
Technical Data
kA
kA
kV
kV
mV
mm mm mm mm
kg
63/
65
63/
65
80/
82
63/
65
63/
65
63/
65
80/
82
80/
82
80/
82
95
38
3.4
40
S_ 441 00705
2.1
95
38
3.4
40
S_ 441 00705
2.1
95
38
2.7
40
S_ 441 00652
2.1
95
38
3.4
45
S_ 441 00706
2.2
95
38
3.4
45
S_ 441 00706
2.2
95
38
1.6
55
S_ 441 00649
2.3
95
38
2.7
45
S_ 441 00648
2.2
95
38
1.6
55
S_ 441 00649
2.3
95
38
1.6
55
S_ 441 00649
2.3
3AH5 204-1
800
160
25
36
28
3AH5 204-2
1250
160
25
36
28
3AH5 205-2
1250
160
31.5
36
35.4
3AH5 214-1
800
210
25
36
28
3AH5 214-2
1250
210
25
36
28
3AH5 214-6
2500
210
25
36
28
3AH5 215-2
1250
210
31.5
36
35.4
3AH5 215-4
2000
210
31.5
36
35.4
3AH5 215-6
2500
210
31.5
36
35.4
Minimum clearance,
phase-to-phase
Ud
Weights
Up
kA
Ima
Minimum clearance,
phase-to-earth
mm
Isc
O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO
Pole-centre distance
Order No.
Ir
tk
50/60 Hz
17.5 kV
DC component in %
of the rated short-circuit breaking current
26
Technical Data
Electrical data, dimensions and weights
Operating cycles
10 000
5 000
2 000
1 000
500
M2 and C2 according
to IEC 62271-100. The
curve shape beyond the
100
parameters defined in
IEC 62271-100 is based on
6
20
10
0.5
HG11-2549c_en eps
80
50
200
7
1
10 kA 20 25 31.5 50
b
a
Dimension
drawing
a
mm
b
mm
c
mm
d
mm
d
c
HG11-2550a eps
86
435
170
482 (558)
630
90
2.1
160
432
490
422
2.2
210
534
592
522
2.3
210
534
592
534
a = Pole-centre distance
b = Width of cross member
c = Width of cross member incl. lugs
d = Largest energized width
27
Technical Data
210
16
36
17.9
3AH5 272-2
1250
210
16
36
17.9
3AH5 273-2
1250
210
20
36
22.4
3AH5 273-4
2000
210
20
36
22.4
3AH5 273-6
2500
210
20
36
22.4
3AH5 274-2
1250
210
25
36
28
3AH5 274-6
2500
210
25
36
28
3AH5 282-1
800
275
16
36
17.9
3AH5 282-2
1250
275
16
36
17.9
3AH5 283-2
1250
275
20
36
22.4
3AH5 283-4
2000
275
20
36
22.4
3AH5 283-6
2500
275
20
36
22.4
3AH5 284-2
1250
275
25
36
28
3AH5 284-6
2500
275
25
36
28
kA
kV
kV
mV
mm mm mm mm
kg
125
50
3.8
55
S_ 441 00660
3.1
125
50
3.8
55
S_ 441 00660
3.1
125
50
3.8
55
S_ 441 00662
3.2
125
50
2.2
80
S_ 441 00663
3.3
125
50
2.2
80
S_ 441 00663
3.3
125
50
3.8
55
S_ 441 00662
10
3.2
125
50
2.2
80
S_ 441 00663
10
3.3
125
50
3.8
55
S_ 441 00661
3.4
125
50
3.8
55
S_ 441 00661
3.4
125
50
3.8
55
S_ 441 00664
3.5
125
50
2.2
80
S_ 441 00668
3.6
125
50
2.2
80
S_ 441 00668
3.6
125
50
3.8
55
S_ 441 00664
10
3.5
125
50
2.2
80
S_ 441 00668
10
3.6
40/
42
40/
42
50/
52
50/
52
50/
52
63/
65
63/
65
40/
42
40/
42
50/
52
50/
52
50/
52
63/
65
63/
65
Minimum clearance,
phase-to-phase
Ud
800
3AH5 272-1
kA
Weights
Up
kA
Ima
Minimum clearance,
phase-to-earth
mm
Isc
O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO
Pole-centre distance
Order No.
Ir
tk
50/60 Hz
24 kV
DC component in %
of the rated short-circuit breaking current
28
Technical Data
Electrical data, dimensions and weights
Operating cycles
20 000
10 000
5 000
1 000
500
M2 and C2 according
to IEC 62271-100. The
200
100
parameters defined in
20
10
0.5
HG11-2551b_en eps
50
35
25
8
1
10
5
10 16 20 25 kA 50
Breaking current (r.m.s. value)
670
537
d
c
HG11-2553a eps
123
435
170
568 (572)
700
90
Dimension
drawing
a
mm
b
mm
c
mm
d
mm
3.1
210
534
592
516
3.2
210
534
592
530
3.3
210
534
592
541
3.4
275
650
708
645
3.5
275
650
708
660
3.6
275
650
708
690
a = Pole-centre distance
b = Width of cross member
c = Width of cross member incl. lugs
d = Largest energized width
29
Technical Data
kA
kA
kV
kV
mV
mm mm mm mm
kg
40/
42
63/
65
63/
65
40/
42
63/
65
170
70
3.0
85
S_ 441 00910
11
4.2
170
70
3.0
85
S_ 441 00910
12
4.2
170
70
2.5
110
S_ 441 00676
12
4.2
170
70
3.0
75
S_ 441 00990
11
4.1
170
70
3.0
75
S_ 441 00990
12
4.1
3AH5 312-2
1250
350
16
36
28
3AH5 314-2
1250
350
25
36
28
3AH5 314-4
2000
350
25
36
28
3AH5 322-2
1250
275
16
36
28
3AH5 324-2
1250
275
25
36
28
Minimum clearance,
phase-to-phase
Ud
Up
kA
Ima
Weights
mm
Minimum clearance,
phase-to-earth
Isc
O - 0.3 s - CO - 15 s - CO
O - 0.3 s - CO - 3 min - CO
Pole-centre distance
Order No.
Ir
tk
50/60 Hz
36 kV
DC component in %
of the rated short-circuit breaking current
20 000
10 000
b
a
5 000
2 000
90
1 000
170
435
500
607 (682)
973
Operating cycles
200
100
50
25
20
10
0.5
11
1
12
d
c
10 16 20 25 kA 50
Dimension
drawing
a
mm
b
mm
c
mm
d
mm
4.1
275
650
708
668
4.2
350
810
868
818
30
a = Pole-centre distance
b = Width of cross member
c = Width of cross member incl. lugs
d = Largest energized width
HG11-2554a eps
214
80
HG11-2552b_en eps
Technical Data
Operating times, short-circuit protection of motors and consumption data of releases
Operating times
Operating times at rated voltage of the secondary circuit
Equipment of circuit-breaker
Closing time
Opening time
Operating time
of circuit-breaker
< 65 ms 1)
< 55 ms 1)
< 45 ms
< 15 ms
< 70 ms
< 60 ms
300 ms
< 75 ms
< 60 ms
45 ms
40 ms
20 ms
> 15 ms
> 10 ms
< 15 s
2 ms
Arcing time
Break time
Dead time
CLOSE/OPEN contact time
V
24 DC
48 DC
60 DC
110 DC
220 DC
110 AC
230 AC
Operating voltage
max. V
26
53
66
121
242
121
244
min. V
20
41
51
93
187
93
187
W (at DC)
500
500
500
500
500
Smallest possible
rated current 2) of the m.c.b.
(miniature circuit-breaker)
with C-characteristic
VA (at AC)
650
650
A
8
6
4
3
2
3
2
2) The current inrush in the drive motor can be neglected due to its very short presence.
Power consumption
Tripping ranges
Operation at
DC
AC 50/60 Hz
Tripping voltage
approx. W
approx. VA
at DC
Tripping voltage
or tripping current
at AC 50/60 Hz
140
140
140
140
85 to 110 % U
70 to 110 % U
85 to 110 % U
85 to 110 % U
70
50
70 to 110 % U
85 to 110 % U
20
20
10 3)
35 to
35 to 0 % U
90 to 110 % Ia
0%U
3) Consumption at pickup current (90 % of the rated normal current) and open armature.
31
Technical Data
Circuit diagrams
Circuit diagrams
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
(-Y2)
-X0
-Y9
(-Y7)
HE
-M1 M
-S22
-S3
(-Y9)
-S4
-S1
-S7
-Y1
11
13
21
23
31
33
41
43
51
53
61
63
12
14
22
24
32
34
42
44
52
54
62
64
1) 2) 2) 1)
-S6
HG11-2780b eps
-S21
HA
-Y1
-X0
The available possible combinations are described in the chapter Selection of secondary equipment.
21
22
-S1
22
-V6
5)
-K1
4 3 +
A1
-M1 1M=
3)
A1
D2
22
-X0
Motor charging
for DC
-Y9
-S22
21
22
-X0
-X0
23 (33)
21
13
22
14
21
22
-S7
31
-S4
32
3)
u 4) -K1
A2
13
14
13
21
14
22
-S6
21
22
13
14
A1
A2
6)
-X0
-X0
Closing and
anti-pumping
-X0
-S1
24 (34)
-S3
12
A1
-S12
-X0
-S1
HG11-2761b eps
HG11-2760b eps
-K1
D2
21
-S22
3)
-M1 1M=
11
-X0
-X0
HG11-2763 eps
21
-S21
-S21
-X0
-X0
HG11-2764 eps
-X0
HG11-2762c eps
-X0
Circuit-breaker tripping
for 24 / 64-pole plug
connector
-X0
23 (33)
-S1
24 (34)
43
44
1) Internally wired
-Y1
A1
A2
3)
u 4)
-Y1
3)
u 4)
A1
A2
-Y4
(-Y2)
(-Y2)
A1
-Y6
A2
A1
-Y7
A2
2) Not wired
3)
u 4)
D1
D2
3) Integrated varistor
for W 60 V DC
4) Integrated varistor
for W 100 V AC / DC
5) Additional rectifier
only required for AC
-X0
Low-energy
current-transformer
operated release
-X0
HG11-2767b eps
-X0
1st currenttransformer
operated release
HG11-2768 eps
-X0
HG11-2769 eps
-X0
HG11-2766c eps
HG11-2765c eps
-R1
6) Only in connection
with mechanical
interlocking
Undervoltage
release
Legend
HA
HE
K1
M1
P
R1
32
Manual opening
Manual closing
Contactor (anti-pumping)
Motor operating mechanism
Energy store
Resistance
S1
S3
S4
S6
S7
Auxiliary switch
Position switch (opens when
closing spring is charged)
Position switch
(indicates the charging state)
Circuit-breaker tripping signal
Cutout switch for circuitbreaker tripping signal
S12
S21,
S22
V6
X0
Y1
Mechanical interlocking
Position switches
(to de-energize the motor operating
mechanism after charging)
Rectifier
Lower part of plug
1st shunt release
Y2
Y4
Y6
Y7
Y9
Annex
Contents
Contents
Page
Annex
33
Inquiry form
34
Configuration instructions
35
Foldout page
R-HG11-181.tif
Configuration aid
R-HG11-180.eps
33
Annex
Inquiry form
Please copy, fill in and return to your
Siemens partner or you can use our
prompted online configurator under
www.siemens.com/energy
Inquiry concerning
o 3AH5 circuit-breaker
Please
o Submit an offer
o Call us
o Visit us
Technical data
o 12 kV
o 24 kV
o 17.5 kV
o 36 kV
o _ _ _ kV
o 75 kV
o 125 kV
o 95 kV
o 170 kV
o _ _ _ kV
Rated short-duration
power-frequency withstand voltage
o 28 kV
o 50 kV
o 38 kV
o 70 kV
o 42 kV
Rated short-circuit
breaking current
o 13.1 kA
o 25 kA
o 16 kA
o 31.5 kA
o 20 kA
o 800 A
o 2000 A
o 1250 A
o 2500 A
o 160 mm
o 210 mm
Rated voltage
Pole-centre distance
Your address
Other values
o _ _ _ kV
o _ _ _ kA
o ___A
o 275 mm
o 350 mm
Secondary equipment
For possible combinations see pages 15 to 19
Company
Circuit-breaker equipment
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
Closing solenoid
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
o _ _ _ V DC
o _ _ _ V AC, _ _ _ Hz
o 0.5 A
Undervoltage release
o _ _ _ V DC
Auxiliary switch
o 2 NO + 2 NC
o 6 NO + 6 NC
o 12 NO + 12 NC
Low-voltage connection
o without
o 24-pole
terminal strip
o 24-pole plug
o 64-pole plug
o English
o German
o French
o Spanish
Dept.
Name
Street
Postal code/city
Phone
Fax
E-mail
o 1A
o W 0.1 Ws 10 c o W 0.1 Ws 20 c
o _ _ _ V AC, _ _ _ Hz
o Mechanical interlocking
o Counter
Siemens AG
Dept.
Operating instructions
Name
34
_ _ _ Please fill in
Ir:
3 A H 5
13 14 15 16
Possible options:
Release combination
(position 9)
Closing solenoid
(position 10)
Operating voltage of the releases
(positions 11/12)
Equipment with circuit-breaker tripping signal
(position 13)
Type of operating mechanism and operating voltage of a motor,
if available (position 14)
50 Hz/60 Hz
3 A H 5
35
3 A H 5
3 A H 5
Should you still need more options than the possible special equipment like halogen-free and
flame-retardant or silicone-free version, condensation protection or an additional rating plate, etc.,
please contact your responsible sales partner.
See page 20
See page 19
See page 18
See page 19
+
3 A H 5
step: Do you have any further requirements concerning the equipment? (Please refer to page 20)
See page 18
3 A H 5
See page 17
3 A H 5
3 A H 5
3rd
9 10 11 12
3 A H 5
See page 16
Ur:
Up:
Ud:
Isc:
See page 15
See page 16
See page 13
and
1st step: Definition of the primary part (see pages 13 and 14)
Possible options:
Page 14
3 A H 5 n n n n n n n n n n n n Z
R-HG11-174.eps
www.siemens.com/energy