GENERATOR

SET CONTROL

ALARM MODULE OR
MANUAL SYNC MODULE

PANEL
LIGHT

PUMP RUN
PUSHBUTTON

PANEL
LIGHT

PUMP STOP
PUSHBUTTON

VOLTAGE ADJUST
RHEOSTAT

RENR2477-02
July 2009

ENGINE MONITORING
SYSTEM

START AID
SWITCH

SCROLL SWITCH

MODE CLEAR
SWITCH

WARNING
SCROLL

PUMP
RUN

STARTING
AID

PUMP
STOP

HIGH
COOLANT
TEMP

ABBREVIATIONS

AFTS

AUTOMATIC FUEL TRANSFER SYSTEM

ALM

ALARM MODULE

ALR

ALARM RELAY

KWR

KILOWATT RELAY

ALT

ALTERNATOR

LOAD LEADS

ASR

AIR SHUT-OFF RELAY

LFLS

LOW FUEL LEVEL SWITCH

ATB

AC TRANSFORMER BOX

LFSR

LOW FUEL SHUTOFF RELAY

ATR

ALTERNATOR TEMPERATURE RELAY

DISPLAY

LOW
COOLANT
TEMP

CLEAR

LOW
OIL
PRESSURE

LOW OIL
PRESSURE

MODE

LOW
FUEL
LEVEL

EMERGENCY
STOP
HIGH WATER
TEMP

PANEL
LIGHTS

BATTERY

MAN

MANUAL

BC

BATTERY CHARGER

MPU

MAGNETIC SPEED PICKUP

BCF

BATTERY CHARGER FAILURE SWITCH

MV

MOTOR VALVE/SOLENOID VALVE

BTR

BEARING TEMPERATURE RELAY

CAM

CUSTOM ALARM MODULE

CB

CIRCUIT BREAKER

NC
NO

NORMALLY CLOSED
NORMALLY OPEN

CCM

CUSTOMER COMMUNICATION MODULE

OL

OVERLOAD CONTACTOR

CIM

CUSTOMER INTERFACE MODULE

CR

CRANK RELAY

CT

CURRENT TRANSFORMER

CTR

CRANK TERMINATION RELAY

PC
PL

PUMP CONTACTOR
PANEL ILLUMINATION LIGHT

PLS

PANEL LIGHT SWITCH

POT
PR
PRL
PRPB

POTENTIOMETER
PUMP RELAY
PUMP RUN LIGHT
PUMP RUN PUSHBUTTON

PS
PSL

PINION SOLENOID
PUMP STOP LIGHT

PSPB
PWM

PUMP STOP PUSHBUTTON


PULSE WIDTH MODULATED

RAN
RDM
RFI
RR

REMOTE ANNUNCIATOR
RELAY DRIVER MODULE
RADIATED FREQUENCY IMMUNITY
RUN RELAY

SASV

START AID SOLENOID VALVE

SAS
SEC
SHTC

START AID SWITCH


SECOND
CIRCUIT BREAKER SHUNT TRIP COIL

SM

STARTING MOTOR

SMMS

STARTING MOTOR MAGNETIC SWITCH

SMR

STARTING MOTOR RELAY

SP

SPEED ADJUST POTENTIOMETER

SR

SLAVE RELAY

T
TDR
TSC

GENERATOR LINE LEADS


TIME DELAY RELAY
TRANSFER SWITCH POSITION
INDICATING CONTACT

LH

LOW
BATTERY
VOLTAGE

ENGINE
OVERSPEED

BATT

DISPLAY

SYSTEM
NOT IN
AUTO

RH

LH/RH
SELECT

LOW
COOLANT
LEVEL
OVERCRANK
EMERGENCY
STOP

STOP
FAULT
SHUTDOWN

OFF
RESET

FAULT
ALARM
AUT

PHASE
SELECT

ENGINE
METER

LAMP
TEST

ALARM
CODES

EXIT

COOLDOWN
STOP

ALARM
SILENCE

SERVICE
MODE

AUTO

MAN

START
560-642

154-3045

SPEED ADJUST
POTENTIOMETER

ENGINE
CONTROL
SWITCH

EMERGENCY STOP
PUSHBUTTON

3456 Generator Set with EMCP II


Electrical System

PANEL
LIGHT
SWITCH

CCB1-UP
CAH1-UP
CBX1-UP
8AZ1-UP

DIODE

DVR

DIGITAL VOLTAGE REGULATOR

ECLS
ECM
ECS

ENGINE COOLANT LOSS SENSOR


ELECTRONIC CONTROL MODULE
ENGINE CONTROL SWITCH

ECTS

ENGINE COOLANT TEMPERATURE SENSOR

EFR

ENGINE FAILURE RELAY

EGR

ELECTRONIC GOVERNOR RELAY

EOPS

ENGINE OIL PRESSURE SENSOR

EOTS

ENGINE OIL TEMPERATURE SENSOR

EPIR

ETHER PULL-IN RELAY

ESPB

EMERGENCY STOP PUSH BUTTON

ESTS
EXC

EMERGENCY STOP SWITCH ON ENCLOSURE


EXCITOR

F
FCR
FRBS

GFR

EMCP II CONTROL BOX

FUSE BLOCKS

GENERATOR RUNNING RELAY

PWM MODULE

LOW FUEL
LEVEL SHUTDOWN RELAY

FUSE
FUEL CONTROL RELAY
FUEL RUPTURE BASIN SWITCH

GENSET FAULT RELAY

GNDFCT

GROUND FAULT CT

GNDFR

GROUND FAULT RELAY

GRR

GENERATOR RUN RELAY

GSC

GENERATOR SET CONTROL

HC

HEATER CONTACTOR

IC

REMOTE START/STOP INITIATE CONTACT

VAR

VOLTAGE ADJUST RHEOSTAT

VR

VOLTAGE REGULATOR

AC TRANSFORMER BOX

TIME DELAY RELAY


DIODES

CRANK RELAY

Volume 1 of 2: Electronic and AC/DC Panel Group and Schematic

ETHER START RELAY

Printed in U.S.A.

2009 Caterpillar
All Rights Reserved
F11
F12
+
~

F13

CATERPILLAR

FSM3U

AB

-B S

15

B1

A1

1mn

D +B

.8

.4

CR

B
18

16

A2

~
-

TDR GRR

F15 F23

TBC

A
8

LFSR

50

50

51

51

61

61

52

52

53

53

L1

L1

L3

L3

80

80

82

82

KILOWATT
RELAY

AC TERMINAL
STRIP

ALARM
RELAY

DC TERMINAL
STRIP

PUMP
RELAY

DC TERMINAL
STRIP

AC TERMINAL
STRIP

FUSE
BLOCKS

GROUND FAULT
RELAY
F50 F51 F52

B
8

KWR

GND6

GND5
50
50
50
T0
101
108
109
110
131
136
137
202
203
206
207
157
159
51
52
53

GND3
GND4

HC1
HC4
2
2
2
2
SV
SV
SV
SV
BO
ER
EL
MT
FP

87
88
89
ES

80
82

57
57
59
62
62
63
67
67
90
99
DD+
CCMCCM+
SP1
SP1A
SP2
SP2
SP3
SP4
21
GND2
22

17
18
19
20
20
30
30
30
30
37
38

4
34
6
10
10

GND1
1
1
1
1
2
2
2
2
5
5
46
45A
45
3

ALR

WINDING

A
7

TEMPERATURE

PR

AR

ATR

ARMING
RELAY

AC TERMINAL STRIP (TBA1)

DC TERMINAL STRIP (TBD1)

ATR

PUMP
CONTACTOR

RELAYS

GNDFR

PC

MERLIN GERIN

multi 9

C60N

ABCDEFGHIJ

ABCDEFGHIJ

adjust
set point
read

12

OFF

adjust
set point
read

567

12

F16 F17 F18 MCB1 F21 F22 F32 F33

567

HC

FUSE
BLOCKS
5
70
83
85
77

TERMINAL STRIP INTERFACE

HEATER
CONTACTOR

CIRCUIT
BREAKER
BC
ABCDEFGHIJ

ABCDEFGHIJ

adjust
set point
read

B
12

adjust
set point
read

567

12

567

DC PANEL

B
9

KWR

ALR

ABCDEFGHIJ

adjust
set point
read

adjust
set point
read

567

12

567

567

ABCDEFGHIJ
adjust
set point
read

adjust
set point
read

12

ATR

ABCDEFGHIJ

ABCDEFGHIJ

PR

ATR

12

12

BTR

DC 40 PIN
CONNECTOR

567

ATR

AC

DC

TEMPERATURE
RELAY

AR

O/UVR

GNDFR

PC

MERLIN GERIN

OFF

F16 F17 F18

OFF

MCB1

F21 F22 F32 F33

HC

(TBA 2)
CUSTOMER
TERMINAL STRIP

B
9

FUSE
BLOCKS

A
8

132 131 131 139 148 GND

(TBD 2)

(TBA 2)

CUSTOMER TERMINAL STRIP


(TBC)

MARSHALLING BOX

DC TERMINAL
STRIP

ALARM
RELAY

KILOWATT
RELAY

BC

154
156

PUMP
RELAY

multi 9

C60N

GND GND 133 131 132

132 131 133 GND GND

7W-9799

MARSHALLING BOX
(FRONT VIEW)

RFI

VOLTAGE
REGULATOR

GROUND

CUSTOMER
GROUND BAR

AC TERMS

AC 40 PIN
CONNECTOR

(TBD 2)

DC PANEL
VIEW B-B
CHASSIS ONLY SHOWN

AC PANEL

GND2

GND
140
142
209
210
EF1
EF2
120
122
124

133
136
137
157
159
202
203
206
207
132

GND1
101
108
109
110
133

SP1
SP2
SP3
SP4

BEARING

GND
2
2
2
3
6
10
10
30
30
36
71
72
74
81
81
84

AC TERMINAL
STRIP

F50 F51 F52

DC TERMS

BATTERY
CHARGER

ATR

AC PANEL

GND 148 139 131 131 132

DC CHASSIS

BTR

GND
2
2
3
6
6
10
30
57
61
63
87
88
89
90
99
D+
DCCM+
CCMATA+
ATARDM
47
48
49
231A
232A
233A
231B
232B
233B
231C
232C
233C
64
65
66

(Dimensions: 39 inches x 24 inches)

.2

30 Page,

.6

EPIR

RENR2477-02 VOL 1 of 2

1.0

CUSTOMER
240V
AC SUPPLY

SYMBOLS

240

L1

Lamp

ATB Terminal

23

Panel 70 way
Connector

Marshalling Box
Customer DC Term.

Customer Wiring

Generator Frame
(Chassis) Ground

Breakdown Diode
(Bi-directional)

Marshalling Box DC
Terminal

DC Connector No. 1
(Black)

Marshalling Box
Customer AC Term.

Package Options

Earth Ground

Diode

Marshalling Box AC
Terminal

DC Connector No. 2
(Grey)

Alternative Wiring

Solenoid

Fuse

GSC 40 Way
Harness Connector

AC Connector From
Gen (Green)

Coolant Loss Engine


Connector (ECLS)

Shielded Wire

Resistor

Emergency Switch

GSC Relay Module


Terminal

36

Marshalling Box 40
Way DC Connector

Oil Temp Engine


Connector (EOTS)

Engine Mounted
Component

Temperature Switch

Relay Coil

Control Panel
Terminal

11

Marshalling Box 40
Way AC Connector

Relay Contact
(Normally Open)

Liquid Level Switch

Circuit Breaker

L2

GND

Standard Wiring

Relay Contact
(Normally Closed)

132

133

Magnetic Pick-up
Engine Connector

NOTE Q
38

17

132

66

CR
136

136

136

F16
2A

19

137
2

137

141

HC

A1

A2

141

SPACE HEATER

HC
132

140

135

F17
8A

140

140

240 VAC

H1

H3

H2

H4

19

Engine 40 Way
Connector

CAT MONITORING SYSTEM


40 Way Connector

SASV 2 Way
Connector

B
HC
142

SEE CHART
BELOW

MCB1
132

HC

138

148

148

1L1

JACKET
WATER
HEATER

240 VAC BATTERY CHARGER TERMINAL CHART

BATTERY CHARGER

HC

139

139

134

BATTERY
CHARGER

UL

BATTERY DISCONNECT
SWITCH
NOTE BL

BATTERY

NOTE N

40

DESIGNATION

ALT

PS1

10 AMP NON-UL

240

5 AMP NON-UL

14 AWG

133

SM1

CB2 20A

SMMS1

24

1L2

25
2

PS1

GENERATOR WINDING OVERTEMPERATURE ALARM/SHUTDOWN

NOTE AE

LAMP 1
132

HC

138

F19
10A

133

57

GRR

87

139
7

ENCLOSURE LIGHTING
87

GND
7

88

1
59

WH

171

RD

172

USE E-C 2400 OHM

300

USE E-B 5600 OHM

380

USE E-B 5600 OHM

400

USE E-B 5600 OHM

416

USE E-A 7200 OHM

480

USE E-A 7200 OHM

WH

173

RD

174

30

74

VOLTAGE REGULATOR TERMINAL CHART

VR6-B

6A

5A

22

24

20

F1

F2

26

28

30

DIGITAL

45

B+

B-

22

24

20

F1

F2

26

28

30

45

44

PF/KVAR

B+

B-

22

24

20

F1

F2

26

28

30

5
7

75

11

GOVERNOR TERMINAL CHART


TERMINAL DESTINATION CROSS REFERENCE

GOVERNOR

95

131

PC

96

A1

ALR

ALR

207

203

203

65

70

PSL

42

203

RM3

66

38

12

TC5

GRR

181

182

TC2
NOTE R

PRL

40

202

202

202

54

30
74

WH

183

F7
10A

AUXILIARY CIRCUIT BREAKER CONTACT

RD

184

75

NOTE M

FIRST CIRCUIT BREAKER

NOTE AR

PC
132

208

F21

15A
120

L1

210

T4

15A

14

11

233A

231A

231

11

232A

F6
10A

14

11

231

233B

231B

F3
10A

232

132

136

136

136

F16
2A

66

CR

19

137
2

137

A1

11

131

232B

140

11

120 VAC

H1

231C

232C

148

1L1

AUTOMATIC FUEL TRANSFER SYSTEM 1


FUEL SUPPLY FROM BELOW FLOOR LEVEL BULK TANK

30

RM13

10
20
1

41

PSPB
F23
2 AMP

10

84

211
1B

81

18

83

MCB1

29

29

40

NOTE AS

1
2
10

81

AUTO

C
K

GND

J
E

PWM
NOTE T
21

86

NOTE BF
85

EPIR

3
H
G

F
1

10

SP

A
12
B
C
L

ES

3 MAN

PR

84
7

38

B
RM15

RM4

RM31
F2
10A

CR

13
6

FCR

3
3

81

10

ETHER START AID

131
PR

84

AUTOMATIC FUEL TRANSFER SYSTEM 2


FUEL SUPPLY FROM ABOVE GROUND BULK TANK

AUTOMATIC FUEL TRANSFER SYSTEM


207

F22
2A

PSPB

36

132

64

24

206

204

205

2A

1A

85

95

96

30

131

PC
A1

NOTE T
3
EPIR

MV

OL

PR

206

207

207

85
5

42

203

70

203

203

59

SPARE

85

63

36

193

RD

194

202

207

202

202

131

54

211

F23
2 AMP

10

84
1B

84

81

83

PC
132

OL
209

208

F21

15A

BT1
RTD
PT100

S
164

PC

3/4 HP, 1, 2 POLE


115/110-230-208
50/60 HZ
8 GPM
9.2/11.2 FLA

OL
210

210

T2,T4

18

WH

CTR

28

ER

ER

ER

24

SV

SV

SV

HC5

16

HC4

22

22

HC3

12

HC2

HC1

15

START 33

31

HC0

51

159

SL2
160

162

SYSTEM NOT IN
AUTO ALARM

14

161

163

57

57

NOTE AC

20

12 TEST

68

13 SILENCE

69

36

RM22

T11

H1

X1

T1

J1-1

T2

CT 3

53

T12

H2

T3

T13

H1

10

SPARE

SPARE

SPARE

SPARE

SPARE

BCF

22
69
23

GROUP
6

25

12

R5

3
4

TSC

30
C

2
3

26

28

R4

30
-B

2
1

31

NOTE AY

R3

99

32

1+

REMOTE
CUSTOM
16 LIGHT

34

H2

101

CIM

13 SILENCE

CUSTOMER
INTERFACE
MODULE

14 HORN

68
12

GROUND FAULT

36

69

SH
TC

92

J1-2

11

J1-3

X2

13

LFLS
R8
OUTPUTS

6
NOTE AL

5
LOW FUEL LEVEL ALARM

-7
3

SH
TC

93

R7
OUTPUTS

30

SH
TC

16

R6
OUTPUTS

NOTE AF
GEN BEARING OVERTEMP SHUTDOWN

1+

19

R5
OUTPUTS

151

51

51

BK

11
61
2

94

J1-4

SENSOR V-

31

62

PU

SENSOR V+

COOLANT LOSS

13

18

68

67L

67

20

62L

BR

BK

LOADSHARE
MODULE

10

T3

H1
PR1

COOLANT
LOSS

ECLS
C

18

LED #7

52

69

13 SILENCE

13

SILENCE

14

HORN

99

152

52

52

T4

H1

R3
OUTPUTS

19

12

95

J1-5

1+

R7

REMOTE
NFPA 99
16 LIGHT

NOTE BG

5
6

5
14
R6

13 12 11

10
10

153

53

53

10

62O

R2
OUTPUTS

LFSR

86
6

BK
50

50

J1-6

96

19

6
BR

19

D+

D-

D-

19
D-

16

PU

20

LFLS

R5

SPARE FAULT INPUT

LED #3

11

SPARE FAULT INPUT

LED #4

SPARE FAULT INPUT

LED #5

SPARE FAULT INPUT

LED #6

SPARE FAULT INPUT

LED #7

SPARE FAULT INPUT

LED #8

6
-7

30

HORN INPUT 1

HORN INPUT 2

13 SILENCE
14 HORN

-7

26

28

R4

99

29
1

31

1+

R3

32
2

20

34

R2

68

35

69

12

TEST

13

SILENCE

14

HORN

R1
OUTPUTS

17

7
17
72

NOTE AM

38

NOTE AJ

20

RFI

1+

30

RDM

RDM

K
L

20

REMOTE
NFPA 110
16 LIGHT

21

22

PF/KVAR
2
1

NOTE J

ADJUST

CCM+

CCM-

CCM-

CCM-

SP1

SP1A

14 HORN

DATA +

D-

CCM-

B+
99

99

1+

B-

61

SPARE 2

24

SP2

SP2

NOTE H

10

11

12

SPARE 3

NOTE J

25

SP2

SP3

SP3

14

CUSTOMER
COMMUNICATION
MODULE

24
SP3

20

10
68

49

2
H

VR

NOTE BH

HORN INPUT 1

HORN INPUT 2

-7

SPARE FAULT INPUT

LED #1

SPARE FAULT INPUT

LED #2

10

SPARE FAULT INPUT

LED #3

11

SPARE FAULT INPUT

LED #4

SPARE FAULT INPUT

LED #5

SPARE FAULT INPUT

LED #6

SPARE FAULT INPUT

11
36
+
NOTE P

13 SILENCE

LED #7

SPARE FAULT INPUT

14 HORN

LED #8

-7

30

BATTERY
CHARGER
NON-UL

AT CONTROL END ONLY

L5

NOTE G

122

F51
2 AMP

S
124

F52

LS2

2 AMP

F15

36

69

NOTE:
SHIELD TO BE GROUNDED

122

PM GENERATOR

LED #8

-7

30

12 TEST

LED #7

SPARE FAULT INPUT

CCM
99

SP1

2
12 PMG

SPARE FAULT INPUT

DATA-

CCM+
4

62

11 PMG

LED #6

18

60

LOADSHARE
MODULE

T0
N

SPARE FAULT INPUT

30

D+

GOV

LED #5

8
CCM+

CCM+

3
SPARE 1 23

EXC
F1GEN

SPARE FAULT INPUT

13 SILENCE
32

120

LED #4

DATA

NOTE AG
F2GEN

SPARE FAULT INPUT

NOTE Y

VOLTAGE ADJUST
POTENTIOMETER

C
24

LED #3

11

12 TEST

124

NOTE C

NOTE A

22

SPARE FAULT INPUT

NOTE BA

D+

33

NOTE B

REGULATOR

24

80

80
B

NOTE F
22

82

RFI FILTER

LED #2

10

RDM

17

122

82

6A

T9

LED #1

SPARE FAULT INPUT

RELAY
DRIVER
MODULE

VAR

SPARE FAULT INPUT

90

T6
J

R1

40

LFSR
A

37

99

NOTE D

13 PMG
M

F50
2 AMP

NOTES
NOTE A: FOR VR6-B VOLTAGE REGULATOR ONLY: JUMPER TERMINALS FOR THREE PHASE SENSING,
REMOVE JUMPER FOR SINGLE PHASE SENSING.
NOTE B: FOR VR6-B VOLTAGE REGULATOR ONLY: INSTALL JUMPER FOR 1:1 V/HZ SLOPE,
REMOVE FOR 2:1 V/HZ UNDERFREQUENCY SLOPE. (STANDARD IS TO REMOVE JUMPER)
NOTE C: FOR VR6-B VOLTAGE REGULATOR ONLY: REMOVE JUMPER WHEN VOLTS ADJUST POT FITTED.
NOTE D: REFER TO THE VOLTAGE REGULATOR TERMINAL CHART TO DETERMINE THE ACTUAL
DESIGNATION FOR THE SPECIFIC VOLTAGE REGULATOR.
NOTE E: COMPONENTS INSTALLED WITH THE GROUND FAULT RELAY OPTION. NOT AVAILABLE
WITH OPTIONAL DELTA CONNECTED GENERATORS.

LS1

120

NOTE G: OPTIONAL PM CONNECTIONS. STANDARD SE GENERATORS REQUIRE NO CONNECTIONS.


NOTE H: 24VDC POWER SUPPLIED ONLY WITH OPTIONAL DIGITAL VOLTAGE REGULATOR.

NOTE BS

120

NOTE L: COMPONENTS INSTALLED ONLY WITH OPTIONAL SPACE HEATERS.


NOTE M: COMPONENTS INSTALLED WITH EITHER THE AUTOMATIC FUEL TRANSFER SYSTEM 1
OR THE AUTOMATIC FUEL TRANSFER SYSTEM 3 OPTIONS.
NOTE N: COMPONENTS INSTALLED WITH OPTIONAL UL BATTERY CHARGER.
UL BATTERY CHARGERS WIRED 120 VAC.
NOTE P: COMPONENTS INSTALLED WITH OPTIONAL NON-UL BATTERY CHARGERS.
IEC BATTERY CHARGERS WIRED 240 VAC. FUSE F15 IS A 6 AMP FUSE
SUPPLIED WITH 5 AMP BATTERY CHARGER. FUSE F15 IS A 10 AMP FUSE
SUPPLIED WITH 10 AMP BATTERY CHARGER.
NOTE Q: COMPONENTS INSTALLED WITH ANY COMBINATION OF THE SPACE HEATER,
BATTERY CHARGERS, JACKET WATER HEATER, OR BLOCK HEATER OPTIONS.

NOTE F: OPTIONAL RFI FILTER INSTALLED ONLY WITH VR6-B REGULATOR


NOTE R: COMPONENTS INSTALLED WITH OPTIONAL GENERATOR RUNNING RELAY.
NOTE S: EMERGENCY STOP PUSHBUTTON INSTALLED WITH OPTIONAL PACKAGE ENCLOSURE.
JUMPERS BETWEEN 4 & 34 AND 45 & 46 ARE REMOVED WITH THIS OPTION.

NOTE J: PF/KVAR ADJUSTABLE POTENTIOMETER ONLY AVAILABLE WITH DVR WITH PF/KVAR CONTROL.

NOTE T: COMPONENTS INSTALLED WITH OPTIONAL ETHER START AID.

NOTE K: COMPONENTS INSTALLED ONLY WITH JACKET WATER HEATER OPTION.

NOTE U: COMPONENTS INSTALLED WITH OPTIONAL COMMON ALARM RELAY.

NOTE AC: CONNECT ALARM TERMINAL POINT 7 TO POINT 6 FOR NFPA 110 ALARM MODULE OPERATION
MODE. NO CONNECTION REQUIRED FOR NFPA 99 OPERATION.

NOTE AL: "LOW FUEL ALARM" 40% DECREASING

NOTE BA: OPTIONAL NFPA 110, (16) LIGHT REMOTE ANNUNCIATOR INSTALLED BY CUSTOMER

NOTE BM: CONTACT WIRED WITH OPTIONAL RUPTURE BASIN ALARM.

NOTE AM: "CRITICAL LOW" 5% DECREASING

NOTE W: REMOVE THIS JUMPER WIRE IF IT IS DESIRABLE TO TURN OFF


THE GSC AND ALARM VIA THE ENGINE CONTROL SWITCH (ECS) "OFF"
POSITION IN ORDER TO LIMIT BATTERY DRAIN.

NOTE AD: TERMINALS 12, 13 & 14 ARE WIRED FROM AN OPTIONAL CUSTOM ALARM MODULE TO
TERMINALS 12, 13 & 14 RESPECTIVELY, OF THE FIRST ALARM MODULE WHEN ORDERED
IN ADDITION TO EITHER AN NFPA 99, NFPA 110 OR CUSTOM ALARM MODULE.

NOTE AN: COMPONENTS INSTALLED FOR OPTIONAL FUEL TRANSFER SYSTEM #1.

NOTE BB: UP TO 3 ALARM MODULES WITH A COMBINED WIRE LENGTH OF 300 METERS
MAY BE DRIVEN FROM THE DATA LINK. WIRE 30 AND WIRE 99 TO BE
MINIMUM WIRE SIZE 12 AWG. ALL OTHER WIRES TO BE MINIMUM 16 AWG.

NOTE BN: SET TOP DIAL ON TIMER TO "E", SET MIDDLE DIAL TO "3s",
AND SET BOTTOM DIAL TO "0.7".

NOTE X: SEE GSC RELAY RATING CHART.

NOTE AE: COMPONENTS INSTALLED WITH OPTIONAL GENERATOR WINDING OVERTEMPERATURE RELAY.

NOTE V: SHUNT TRIPS ARE INSTALLED WITH EACH OPTIONAL CIRCUIT BREAKER
INSTALLED ON PACKAGE.

NOTE Y: CUSTOMER COMMUNICATION MODULE INSTALLED BY CUSTOMER. WIRES 2 & 99 MUST


BE A MINIMUM OF 16 AWG SHIELDED TWISTED PAIR CABLE. MAXIMUM DATA AND BATTERY
WIRE LENGTH IS 457 METERS, INCLUDING RUNS BETWEEN MULTIPLE GENSETS.
NOTE Z: COMPONENTS INSTALLED WITH OPTIONAL ENGINE MONITORING SYSTEM.
NOTE AA: COMPONENT INSTALLED FOR NFPA 99 OR NFPA 110 ALARM MODULE. SWITCHED INPUT
TERMINALS 10 AND 11 ON THE ALARM MODULE MUST BE JUMPERED TO TERMINALS
3 AND 4 RESPECTIVELY, IF IT IS DESIRED TO SOUND HORN IN CONJUNCTION WITH
FLASHING LAMP.
NOTE AB: COMPONENT INSTALLED FOR OPTIONAL CUSTOM ALARM MODULE. MODULE CONTAINS
SPARE INPUTS FOR CUSTOMER DESIRED USE WITH CUSTOMER PROVIDED SWITCH.
(RATED FOR 4mA, 12 VDC OPERATION)

NOT USED WITH FUEL FIRED JACKET WATER HEATER.

LED #2

10

30
12

ATB

5A

LED #1

SPARE FAULT INPUT

12 TEST
1

NOTE BG

PHASE ROTATION 1-2-3

SPARE FAULT INPUT

GROUP

39

72

20
D+

98

J1-8

D-

20

97

J1-7

D+

VOLTAGE REGULATOR

GEN

DATA

LFSR

T5

H1
PR1

T3
W

T12

LED #8

-7

ELECTRONIC CONTROL

RDM

PU

BK

D1

T11

LED #7

SPARE FAULT INPUT


30

90

11

36

67O

BR

BK

T10

SPARE FAULT INPUT

33

14 HORN

4
53

T8

LED #6

3
R4
OUTPUTS

LOW FUEL LEVEL SHUTDOWN

50

T7

SPARE FAULT INPUT

30
12 TEST

NOTE AK
11

1W

T5

LED #5

4
51

D2

T4

SPARE FAULT INPUT

NOTE AZ

23

25

TEST

20

22

12

9
R8

17

27

SHUNT TRIP CB
SPARE FAULT INPUT

LED #4

10

24

GEN WINDING OVERTEMP SHUTDOWN

76

SPARE FAULT INPUT

11

NOTE AE

75

SHUNT TRIP CB

NOTE V

12

1+

SHUNT TRIP CB

LED #3

11

12
R9

14
18

70

11

ALR

R9
OUTPUTS

NOTE AH

44

SPARE FAULT INPUT

R1

20

NOTE E

11

LED #2

10

12 TEST

37

21

X1

PR1

38

GNDFR
14

LED #1

SPARE FAULT INPUT

NOTE AU

GEN BEARING OVERTEMP ALARM

73

SPARE FAULT INPUT

R2

GEN WINDING OVERTEMP ALARM

71

ONLY FOR DVR

T2
V

2
C

REMOTE
NFPA 110
2 LIGHT

99

T1
U

10

B+

ELECTRONIC CONTROL
7

11

NFPA 110

CAM

32

NOTE BD

11

10

NOTE AE

15

32

X2

T2

BK

DROOP
CT

99

11

NOTE AF

10

PR1

50

R6

7
13 12

14

22

40

DC CONN 1

52

EMCP DIAGNOSTIC
FAULT

NFPA 99

CT 2

74

35

110

50

39

10

F13

GFR

30

NOTE AX

6
R7

20

38

10

-7

19

32

12

14 HORN

NOTE AB

91

F11

101

13 SILENCE

R8

CUSTOM ALARM MODULE

HORN INPUT 2

16

35

ALARM INPUT CHART

12 TEST

10

99

ALM INPUT
TERMINAL

51

HIGH COOLANT
TEMP ALARM

38

SEE ALARM CHART

300

11

HORN INPUT 1

NOTE BG

11

99

PL2

NOTE U

GNDFR

14

R9

14

30

DATA

36

SEE ALARM CHART

301

10

COMMON ALARM SHUTDOWN

50

OVERSPEED
FAULT

35

6
NOTE AL

14 HORN

10

108

F12

CT 1

70

99

LFLS

16

15

30

10

120

PR1

REMOTE
NFPA 99
8 LIGHT

29
NOTE AH

12

T1

TO

30

NOTE AD

RM7
F5
10A

122
7

30

NOTE AF

30

EF1

10

45

A2

EF2

TO

10A

RM34

118

A1

12

13

15

T3

T3

56

10

F10

AR
AR

T2

10

NOTE E

T1

58

PLS

RM39

RM12

108

GROUND FAULT RELAY

GNDFCT

30

90

24

OVERCRANK
FAULT

LOW FUEL LEVEL ALARM

PL1

NOTE BC

T2

55

IC

57

SS

T1

LED #8

6
-7

90

SLR1

SL1

LED #7

SPARE FAULT INPUT

76

-7

1+

2
157

SPARE FAULT INPUT

33

110

F32
2 AMP

T0

54

30

23

11

LED #6

5
13 SILENCE

SLR2

F33
2 AMP

154

SPARE FAULT INPUT

15

NOTE BM

15

C
3 OR 4 POLE
OPTIONAL MOLDED
CASE CIRCUIT
BREAKER

30

2
1

156

LED #5

16

21

FRBS

77

MANUAL SYNCHRONIZING MODULE

SPARE FAULT INPUT

17

44

AUTO 40

LOW OIL
PRESS ALARM

16

COOLDOWN/STOP 32

SP3

71

18

ALM

10
7

RUPTURE BASIN ALARM

LED #4

12

EXHAUST
TEMPERATURE
LOW COOLANT
TEMP ALARM

48

RM1

L3

LED #3

SPARE FAULT INPUT

99

FCR

LOAD

L2

SPARE FAULT INPUT

NOTE AW

HIGH COOLANT
TEMP FAULT

90

LED #2

11

LOW OIL
PRESS FAULT

ECS

LED #1

SPARE FAULT INPUT

10

NOTE AA

NOTE AQ

81

SPARE FAULT INPUT

12 TEST

30
8

30

27

OFF/RESET 39

L1

REMOTE
CUSTOM
8 LIGHT

SP2

A2

TDR

L0

1+

14 HORN

NOTE AS

81

99

NOTE AF

Q
R

NOTE W

PRPB

FUEL TRANSFER PUMP

131
3

T1,T3

209

75

B1
RM2

NOTE AT

90

10

START

90

TDR

PR

2B

X
MAN

3
A1
83

BTR
163

RD

90

LFLS

LFLS

-E

+D

NOTE M

GENERATOR

(Dimensions: 39 inches x 28 inches)

53

PSPB

PRL

40

NOTE AV

NFPA ALARM MODULES


PC

10

23

63
5

90

35

74

63

MV
7

GENERATOR BEARING OVERTEMPERATURE ALARM/SHUTDOWN

D+

P
Q

30

AUTO

T3

87

PR

131

62

61

30 Page,

RENR2477-02 VOL 1 of 2

PC

AUTOMATIC FUEL TRANSFER SYSTEM 3


FUEL SUPPLY FROM FREESTANDING BULK TANK

AUT

COOLDOWN
STOP

DPR

207

33

PSL

23

SASV

NOTE T

A2

T2

NOTE J

NOTE AS

NOTE AT

191
192

WH

PR

131

ENGINE INSTRUMENTATION

20

83

83

6
33

LFLS

LFLS

84

84

F23
2 AMP

OFF
RESET

AUX

31

THROTTLE
10

NOTE AP
4

NOTE BJ

13

SP2

MCS

DROOP
12
START AID SWITCH
38

NOTE T

14

85

Engine
ECM

ETHER
START AID

T1

SCS

DIGITAL SENSOR
RETURN

SAS
5

1
26

NOTE Z

45A

32

7
CAT DATA LINK (-)
6
ETHER START
RELAY21

81

2
27

45

40

148

120V
BLOCK
HEATER

86

CAT DATA LINK (+)

16 AMP
HC

1R1

SR

45

32
ATA DATA LINK (-)
31
ATA DATA LINK (+)

81

1R2

ELECTRONIC
LOADSHARE

PRPB

-E

+D

SRV

PR

2B

GND

138

39

START/RUN/STOP 2
83

3
28

30

LFLS

LFLS

84

1L2

132

28

39

START/RUN/STOP 1
2

RM14
EGR

NOTE AT

131

28

NOTE N
4

1L4

CLR

BATT. (+)

87

NOTE AN

1L3

30

B+

PR

NOTE L

JACKET
WATER
HEATER

10 AWG

46

H4

SPACE HEATER

B+
15

45

46

BATT. (+) (SWITCH)

120 VAC

BATTERY
CHARGER

NOTE K
148

2R1

SR
A+

B16

30

30

E-STOP SWITCH 2

H3

30

MCB1
138

2R2

NOTE S

142

32 AMP
132

1L4

E-STOP SWITCH 1

HC

17

17

1L3

17

NOTE S

CB3 15A

131

SMM 3
S1

233C

TC6

1L2

TC3

38

RM B+

H2

34

12

140

140

1L2

1L1

34

RM21

RM28

231

232

135

F17
8A

1L1

45
C

14

HC
132

14

RM28
233

A2

BREAKER AUX
131

SMR

BREAKER AUX

131

HC

CR

SMR

THIRD CIRCUIT BREAKER


38

RM18

RM6

12

NOTE Q
17

39

ESPB

RR

ESTS

BREAKER AUX
131

RM24

RM8

RM33

233

132

RM35

B21

ATR3
232

X
X

12

BREAKER AUX
C

MPU

SECOND CIRCUIT BREAKER

GND

GSC

BK
RD

22

1
2
3

NOTE X

BREAKER AUX

3/4 HP, 1, 2 POLE


115/110-230-208
50/60 HZ
8 GPM
9.2/11.2 FLA

T2,T3

210

11

FUEL TRANSFER PUMP

2
OL

212

F24

T1

209

PC
133

233

OL
209

21

BREAKER AUX
CUSTOMER
120V
AC SUPPLY

RR

RM9

D
-

RM23

RM36
131

CAT MONITORING SYSTEM

PC
53

S
19

RM17

CTR

1
3

99

207

ATR2

F1
10A

62

61

CTR

RM30

131

PWM

37

RM16

-E

+D

ASR

10A

64
4

LOADSHARE

RM19

RM5

RM32

F4

NOTE U

PC

COMMON ALARM SHUTDOWN

A2
33

RM27

FLYBACK 27

CIRCUITRY

STOP

INTERNAL

MANUAL

205
9

5A, 24VDC
7.5A,110VAC

OFF/RESET

206

2A

1A

10A, 24VDC
OR 110VAC

1
204

10A, 24VDC

OL

PR

206

207

207

24

10A, 24VDC

TERMINAL DESTINATION CROSS REFERENCE

AUTO

207

F22
2A

64

*N/A

0-.45A, 24VDC

CONTACTS

132

PSPB

36

16,
18,
21, 20,
24,
36,

AUTOMATIC FUEL TRANSFER SYSTEM


5

14,

15,
17,
19,
22,
23,

SP2
89

13,

* DO NOT CONNECT INDUCTIVE LOADS TO


THESE TERMINALS

REGULATOR

21

37

33

89

RATING FOR
INDUCTIVE
LOADS

RATING FOR
RESISTIVE
LOADS

30

NOTE BG

32

88

131

TC1

30

58

GRR

133

LAMP 2

31

USE E-D 1760 OHM

240

ATR1

T3

TC4

NOTE R

NOTE BK

T2

GENERATOR RUNNING RELAY

HC

134

F20
10A

T1

10 AMP

240V
BLOCK
HEATER

208

-E

+D

OUTPUT LOAD SPECIFICATIONS


FOR GSC RELAY MODULE
RELAY MODULE
TERMINAL NO.

ELS

148
6

SYNCHRONIZING
RESISTOR TAP
SETTING CHART

VOLT LINE
TO LINE

CB1 60A

14 AWG

SLR CHART

NOTE L

NOTE P

NOTE K

16 AMP
1

240 VAC

BATTERY
CHARGER

1600 OHM

142

640 OHM

F18
8A

142

3200 OHM

141

1760 OHM

133

ALARM OVERTEMPERATURE FACTORY SET TO 130C FOR PRIME POWER, 160C FOR STANDBY POWER.
SHUTDOWN OVERTEMPERATURE FACTORY SET TO 135C FOR PRIME POWER, 165C FOR STANDBY POWER.
NOTE AF: COMPONENTS INSTALLED WITH OPTIONAL GENERATOR BEARING OVERTEMPERATURE RELAY
ALARM OVERTEMPERATURE FACTORY SET TO 70C.
SHUTDOWN OVERTEMPERATURE FACTORY SET TO 90C.
NOTE AG: THE INPUT TO THE GSC SPARE SHUTDOWN INPUTS MUST BE A B- SIGNAL
APPLIED FOR 250mSEC OR LONGER TO ASSURE PROPER OPERATION. CUSTOMER
PROVIDED SWITCH TO BE RATED FOR 4mA, 12VDC OPERATION.
NOTE AH: CONTACT WIRED WITH OPTIONAL LOW FUEL LEVEL ALARM.
NOTE AJ: LOW FUEL LEVEL SHUTDOWN WIRED WHEN OPTIONAL FUEL TANK BASE IS ORDERED.
NOTE AK: TERMINAL 23 OF REMOTE ANNUNCIATOR TO BE WIRED TO TERMINAL 14 OF THE
THE LOCAL ALARM MODULE.

NOTE AP: COMPONENTS INSTALLED FOR OPTIONAL FUEL TRANSFER SYSTEM #2.
NOTE AQ: COMPONENTS INSTALLED FOR OPTIONAL FUEL TRANSFER SYSTEM #3.
NOTE AR: OPTIONAL AUXILLIARY CIRCUIT BREAKER CONTACTS RATED FOR
6 AMPS AT 240/480VAC, 50/60HZ; 3 AMPS AT 600VAC, 50/60HZ;
2.5 AMPS AT 48VDC; 0.8 AMPS AT 125VDC; 0.3 AMPS AT 250VDC:

NOTE BC: COMPONENTS INSTALLED WITH MANUAL SYNCHRONIZING OPTION.


SEE SLR TABLE FOR RESISTOR CONNECTIONS.
NOTE BD: COMPONENTS INSTALLED ONLY WITH LOADSHARE OPTION.
NOTE BE: LOADSHARING LINES ARE COMMON TO ALL UNITS.
NOTE BF: REFER TO GOVERNOR TERMINAL CHART TO DETERMINE THE ACTUAL TERMINAL
DESIGNATION FOR SPECIFIC GOVERNORS.

NOTE AS: "PUMP OFF" 90% INCREASING


NOTE AT: "PUMP ON" 50% DECREASING
NOTE AU: CUSTOMER INTERFACE MODULE INSTALLED BY CUSTOMER.

NOTE BG: COMPONENTS INSTALLED WITH OPTIONAL ENCLOSURE LIGHTING

NOTE AV: OPTIONAL CUSTOM (8) LIGHT REMOTE ANNUNCIATOR INSTALLED BY CUSTOMER.

NOTE BH: FOR VR6-B VOLTAGE REGULATOR ONLY: REMOVE JUMPERS BETWEEN:
TERMINALS 20 & 28, 22 & 30, AND 24 & 26 FOR OPTIONAL PM GENERATORS.

NOTE AW: OPTIONAL NFPA 99, (8) LIGHT REMOTE ANNUNCIATOR INSTALLED BY CUSTOMER.
NOTE AX: OPTIONAL NFPA 110, (2) LIGHT REMOTE ANNUNCIATOR INSTALLED BY CUSTOMER.
NOTE AY: OPTIONAL CUSTOM (16) LIGHT REMOTE ANNUNCIATOR INSTALLED BY CUSTOMER

NOTE BK: COMPONENTS INSTALLED ONLY WITH 240 VAC BLOCK HEATER OPTION.

NOTE AZ: OPTIONAL NFPA 99, (16) LIGHT REMOTE ANNUNCIATOR INSTALLED BY CUSTOMER

NOTE BL: COMPONENT INSTALLED ONLY WITH BATTERY DISCONNECT OPTION.

THIS SCHEMATIC IS FOR THE 3456 GENERATOR SET with EMCP II


VOLUME 1 of 2: DESCRIPTION

NOTE BJ: COMPONENTS INSTALLED ONLY WITH 120 VAC BLOCK HEATER OPTION.

Components are shown installed on a fully operable machine with the key and engine off, transmission shifter
in neutral and with parking brake set.
Refer to the appropriate Service Manual for Troubleshooting, Specifications and Systems Operations.

LFSR

D3

51
61

53-TBA1-53T
OR 153-LSGOV-9

53

52

.8

L1

B B

B B

B B

NOTE D

U1

GND-70 WAY-68
GND-CHASSIS STUD

110-F13

131-PSL-X2
131-70 WAY-70
136-CR-2
136-70 WAY-38
137-CR-8
137-70 WAY-66
202-PRL-X1
202-70 WAY-40
203-PSL-X1
203-70 WAY-42
206-PSPB-2A
206-70 WAY-64
207-PSPB-1A
207-70 WAY-36
157-SS-4
157-70 WAY-23
159-SS-6
159-70 WAY-51
51-TBC-51 OR 51-LSGOV-4
51-AC CONN-1
52-TBC-52 OR 52-LSGOV-6
52-AC CONN-2
53-TBC-53 OR 53-LSGOV-8
53-AC CONN-3

108-F11

T0-AC CONN-8

101-70 WAY-14

50-AC CONN-12

50-TBC-50
50-AC CONN-11

B B

B B

Fuse: A component in an electrical circuit that will open the circuit if too much current flows
through it.
Switch (Normally Open): A switch that will close at a specified point (temp, press, etc.). The
circle indicates that the component has screw terminals and a wire can be disconnected from it.

80

SP2-TBD1-SP2BT

51
52
53

159

207

157

206

202

203

137

136

131

Switch (Normally Closed): A switch that will open at a specified point (temp, press, etc.).
No circle indicates that the wire cannot be disconnected from the component.
Ground (Wired): This indicates that the component is connected to a grounded wire. The
grounded wire is fastened to the machine.

B B

B B

B B

B B

B B

B B

B B

B B

B B

B B

B B

B B

B B B

B B

B B B

B B

B B

B B

3456 Generator Set with EMCP II


Electrical System

4-TBD1-34L

4-TBD1-4L

10-EMSII CONN-1

20-LSGOV-20

30-TBD1-GND2L

90-ALM-2

D(-)-EMSII-14

D(+)-EMSII-5

SP1A-TBD1-SP1AL

SP1A-TBD1-SP1L

21-MPU-1

30-TBD1-30DL

22-MPU-2

82-VR6B-7
OR 82-DVR-7

2-TBD1-2DL

ET(-)-EMT-B

ET(+)-EMT-A

ET-EMT-C

17

18

19

30

31

32

33

43

44

45

46

47

57

58

59

60

61

6-TBD1-6B

87
88
89

ES-ECM-38

16

29

63-TBD1-63B

15

D(-)-TBD1-D(-)B

80-VR6B-6A
OR 80-DVR-45
5

D(+)-TBD1-D(+)B

90-TBD1-90B

22

72-LFSR-A
84-F23-B
OR 84-PRPB-3
81-PRPB-4
4

30-TBD1-30AT

57-TBD1-57BB

3-TBD1-3T

71-CAM-9

2-TBD1-2BT

57
57
59
62
62
63
67
67
90
99
DD+
T1-F11

T0-TBA1-T0T

T3-F13

50-TBA1-50AB

50-TBA1-50BB

50-TBA1-50CB

17
18
19
20
20
30
30
30
30
37
38

10-TBD1-10BT

2-TBD1-2AT

Sender: A component that is used with a temperature or pressure gauge. The sender
measures the temperature or pressure. Its resistance changes to give an indication to
the gauge of the temperature or pressure.

Relay (Magnetic Switch): A relay is an electrical component that is activated by electricity.


It has a coil that makes an electromagnet when current flows through it. The
electromagnet can open or close the switch part of the relay.

CCB1-UP
CAH1-UP
CBX1-UP
8AZ1-UP

GND4

46-TBD11-46L
2-TBD1-2BB

GND3

46-TBD1-45L

203-TBA1-203B

2-TBD1-2EL

1-TBD1-1DL

62-TBD1-62AB

18-TBD1-18B

Reed Switch: A switch whose contacts are controlled by a magnet. A magnet closes the
contacts of a normally open reed switch; it opens the contacts of a normally closed reed switch.

Solenoid: A solenoid is an electrical component that is activated by electricity. It has a


coil that makes an electromagnet when current flows through it. The electromagnet
can open or close a valve or move a piece of metal that can do work.
Magnetic Latch Solenoid: A magnetic latch solenoid is an electrical component that is
activated by electricity and held latched by a permanent magnet. It has two coils (latch and unlatch)
that make electromagnet when current flows through them. It also has an internal switch that places
the latch coil circuit open at the time the coil latches.

Harness and Wire Symbols


Wire,
Cable,
or
Harness
Assembly Identification: Includes
Harness Identification Letters and
Harness Connector Serialization
Codes (see sample).

101-TBA1-101B

2-EPIR-85

SV
SV
SV
SV
BO
ER
EL
MT
FP

1-TBD1-5AL

67-TBD1-67AB

62-TBD1-62AT

157-TBA1-157B

2
2
2
2

L L

HC1

HC4

207-TBA1-207B

ES

74-CAM-8

RDM-GSC-30

80
82

21

1-TDR-A1

GND2

SP4

SP3

SP2

SP2

SP1

SP1A

19-TBD-19B

67-TBD1-67AT

CCM+

CCM-

4
34
6
10
10

20-TBD1-20AB

45
3

45A

1
1
1
1
2
2
2
2
5
5
46

GND1

1-EPIR-30

GND-BODY STUD
GND-TBD1-GND3T

BODY STUD

GND-CHASSIS STUD

Ground (Case): This indicates that the component does not have a wire connected to ground.
It is grounded by being fastened to the machine.

CHASSIS STUD
GND-DOOR STUD
GND-GSC-GND

ER-EMSII CONN-8

GND-CHASSIS STUD

110-SLR2

108-SLR1

SV-EMSII CONN-24

MPU-SHIELD
VAR-SHIELD

21-GSC-1

SP1A-GSC-23
SP2-GSC-24
SP2-70 WAY-61
SP2-D2-U2
SP2-D3-U2
SP2-LFSR-4
SP3-GSC-25
SP3-70 WAY-62

59-EPIR-87
59-DC CONN2-3
62-DC CONN1-10
62-DC CONN1-7
62-GSC-31
63-GSC-36
63-70 WAY-6
67-DC CONN1-12
67-DC CONN1-9
67-GSC-9
90-GSC-35
90-70 WAY-5
99-RM-9
99-70 WAY-35
D(-)-GSC-20
D(-)-70 WAY-20
D(+)-GSC-19
D(+)-70 WAY-19
CCM(-)-GSC-22
CCM(-)-70 WAY-33
CCM(+)-GSC-21
CCM(+)-70 WAY-32
SP1-70 WAY-60

110

109

108

GND5

91-GSC-10
92-GSC-11
93-GSC-12
94-GSC-4
95-GSC-5
96-GSC-6
97-GSC-16
98-GSC-17

CHASSIS STUD

B B

Symbols and Definitions

L2

76-BTR-7

SP2-TBD1-SP2BT

L2

75-ATR-7

72-70 WAY-17

30-LFSR-9
30-TBD1-30DB

57-ECS-4
57-GSC-33
57-70 WAY-30

38-RM-16
38-GRR-A

37-RM-19

20-RM14
20-DC CONN2-10
20-ESPB-1R2
20-SAS-2
30-70 WAY-16
30-DC CONN2-4
30-ESPB-1L4
30-RM-28
30-PWM-B(-) OR 30-LSGOV-16
30-ECS-1
30-TDR-A2
30-LFSR-7

17-ESPB-1L3
17-GSC-38
18-GSC-13
18-DC CONN1-8
19-DC CONN1-11

10-DC CONN2-8
10-PLS-3

34-ESPB-1L2
6-RM-22
6-70 WAY-2
10-RM-39
10-70 WAY-45

GND-REAR COVER
GND-TBA1-GND6B

4-DC CONN2-6

45-DC CONN1-4
3-70 WAY-3
3-CR-9

45A-DC CONN1-5

46-ESPB-1R1

5-ECS-9

2-TBD1-2DT
GND-70 WAY-47
1-DC CONN2-1
1-DC CONN2-2
1-RM-30
1-RM-36
1-F15-T
1-ECS-6
1-F23-T
1-RM-2
2-DC CONN2-11
2-CR-B
2-70 WAY-15
2-DC CONN2-12
2-PL2-1
2-RM-27
2-TBD1-GND1T
2-PL1-1
5-70 WAY-48
5-TDR-16

TBD1

82
2-CR-B

89-TBD1-89T

U1

Harness Identification Letter(s):


(A, B, C, ..., AA, AB, AC, ...)

22

23

24

36

37

38

12

13

25

26

27

28

39

40

41

42

48

49

50

51

52

53

54

55

56

62

63

64

65

66

67

68

69

70

L-C12
3E-5179

Harness Connector Serialization Code:


The "C" stands for "Connector" and the
number indicates which connector in the
harness (C1, C2, C3, ...).

Part Number: for Connector Receptacle

14

Plug

Receptacle
Pin or Socket Number

1
2

Deutsch connector: Typical representation


of a Deutsch connector. The plug contains all
sockets and the receptacle contains all pins.

1
2

Sure-Seal connector: Typical representation


of a Sure-Seal connector. The plug and receptacle
contain both pins and sockets.

5A
9X-1123

Fuse (5 Amps)

Component
Part Number

131-TBA1-131B

GND-TBA1-GND6T

202-TBA1-202B

137-TBA1-137B

136-TBA1-136B

NOTE D

206-TBA1-206B

325-AG135 PK-14
159-TBA1-159B

21

35

36-F15-B

20

34

99-TBD1-99B

11

5-TBD1-5AT

10

SP3-TBD1-SP3B

70 WAY

CCM(-)-TBD1-CCM(-)B

SP2-TBD1-SP2AB

AC CONN
(GREEN)

53-TBA1-53B

SP1-TBD1-SP1B

10

GND-TBD1-GND1B

11

CCM(+)-TBD1-CCM(+)B

12

89-TBD1-89B

52-TBA1-52B

1-TBD1-1AB

1-TBD1-1AT

45-TBD1-45T

41-RM 13

DC CONN 2
(GREY)

45A-TBD1-45AT

41-RM 13

10-TBD1-10AB

DC CONN 1
(BLACK)

10

88-TBD1-88B

11

87-TBD1-87B

12

T2-F12

GND-TBA1-GND5B

51-TBA1-51B

4-TBD1-4B

10

30-TBD1-30AB

11

59-TBD1-59B

12

L-C12
3E-5179

AG-C4
111-7898
Part Number: for Connector Plug

Circuit Breaker
Symbol

Flow
Symbol

L3

A
8

30-LFSR-7

2-CR-B

211-PSPB-1B
OR 84-70 WAY-4

~
-

30-TBD1-30DT

A2

36-70 WAY-49

.4

.2

18

5-TBD1-5AB

39-RM-24

3-TBD1-3B

2-TBD1-2AL

16

10-PLS-3

30-TBD1-30CT

S-SPD-ECM-10

D-SPD-ECM-12

2-GRR-B
2-TBD1-2AB
2-LFSR-B

D +B

8-ECM-21

-B S

8
137-TBA1-137T

.6

38-TBD1-38B

0
1.

CATERPILLAR

Level
Symbol

TBA1

101

GRR

1mn

F23

D2

CR

F15

FSM3U

51-TBA1-51T
OR 151-LSGOV-5
52-TBA1-52T
OR 152-LSGOV-7

Temperature
Symbol

GND6

AB

50-TBA1-50AT
GND-AC CONN-4
50-TBA1-GND5T
50-AC CONN-10

86-CAM-6

SP2-TBD1-SP2BB

1-TBD1-1DT

2-EMSII CONN-6

Symbols

Pressure
Symbol

2-EMSII CONN-22

50

50
50
50
T0

1-TBD1-1CT

87-TBD1-87T

7-RM-1

50-TBA1-50BT

HC4-EMSII CONN-16
2-EMSII CONN-2
2-EMSII CONN-31
2-SCS-2
2-EMSII CONN-12

TBC

HC1-EMSII CONN-3

110-TBA1-110T

L1

82-VAR-1

TDR

F13

87-GRR-4
87-70 WAY-57
88-GRR-1
88-70 WAY-58
89-GRR-7
89-70 WAY-59
ES-SAS-3

F12

T3-AC CONN-9

108-TBA1-108T

80-VAR-3

15

B1

A1

L1

T2-AC CONN-5

Harness And Wire Electrical Schematic Symbols

RENR2477-02
July 2009

GND-REAR COVER
F11

22-GSC-2

54-ECS-7

1-TBD1-1CL
+
~

88-TBD1-88T

EPIR

13-RM-15

136-TBA1-136T

59-TBD1-59T

1-TBD1-1AL

42-SP-3

44-SP-2

43-SP-1

NOTE E

76-CAM-4

75-CAM-3

ATB
T1-AC CONN-7

Volume 2 of 2: Control Panel and Marshalling Box

Harness identification code:


This example indicates wire group 325,
wire 135 in harness "AG".

Wire Gauge
Wire Color

Printed in U.S.A.

2009 Caterpillar
All Rights Reserved

38

28

18

37

27

17

36

26

16

35

25

15

34

24

14

33

23

13

2-MCS-2
CLR-MCS-6

VAR

9-PL2-2

10

X2

SAS

X1

X2

NO

PRPB

161

1760 OHM

PSPB

PL1
2

PL2
2-TBD1-2CT

9-PLS-2

CONTROL PANEL DOOR

9-PLS-2

1600 OHM

56-ECS-3

55-ECS-2

17-TBD1-17B

X1

1A NC 2A
1B NC 2B

43-SP-1

44-SP-2

Failure mode not identifiable.

12

Bad device or component.

13

Out of calibration.

10

10 11 12 13

Component Identifiers (CID'S)


For (EMCP II )

14

CID
100
GND

A
B

153-TBC-53

53-TBA1-53T

152-TBC-52

151-TBC-51

52-TBA1-52T

51-TBA1-51T

REAR COVER

GND-TOP COVER
GND-CHASSIS STUD

Description
Pressure Sensor (Engine Oil)

110

Temperature Sensor (Engine Coolant)

111

Fluid Level Sensor (Engine Coolant)

168

Electrical System Voltage

190

Speed Sensor (Engine)

248

CAT Data Link

268

EMCP Electronic Control (Generator Set)

269

Sensor Power Supply

333

Alarm Module Control

SYNCHRONIZING
RESISTOR TAP
SETTING CHART

334

Spare Output

336

Switch (Engine Control)

208

USE E-D 1760 OHM

441

Electronic Governor Relay

240

USE E-C 2400 OHM

442

Generator Fault Relay

300

USE E-B 5600 OHM

380

USE E-B 5600 OHM

400

VOLT LINE
TO LINE

PRL

PSL

SLR CHART

63-TBD1-63T

2-TBD1-2DB

120-TBA2-120U

81-70 WAY-18

131-PSL-X2

202-TBA1-202T

84-PSPB-2B
84--70 WAY-4

20-TBD1-20BB

ES-TBD1-ES

57-TBD1-57AB

84-PRPB-3

38 39 40

206-TBA1-206T

35 36 37

58-ECS-5

207-TBA1-207T

RDM-70 WAY-7
62-TBD1-62BB
90-TBD1-90T

32 33 34

122-TBA2-122U

NOTE E: SET TOP DIAL ON TIMER TO "E", SET MIDDLE DIAL TO "3s",
AND SET BOTTOM DIAL TO "0.7".

CCM(-)-TBD1-CCM(-)T
CCM(+)-TBD1-CCM(+)T

26 27 28

29 30 31

Abnormal rate of change.

11

WARNING

SLM

211-F23-B

SP3-TBD1-SP3T

10

NOTE D: WIRES 51, 52, AND 53 ARE CONNECTED TO TERMINAL STRIP


"TBC" UNLESS OPTIONAL LOADSHARE GOVERNOR IS PROVIDED.

SP1A-TBD1-SP1AB

Abnormal update.

= COMPONENT LOCATED ON ENGINE OR BASE

NOTE C: WIRES 108 AND 110 CONNECT TO THE SYNCHRONIZING LIGHT


RESISTORS (SLR1 & SLR2) OF THE SYNCHRONIZING MODULE
REFER TO SLR CHART BELOW FOR PROPER CONNECTIONS.

131-PRL-X2

24 25

9
10

REV.

NOTE B: WIRE JUMPER FROM TERMINAL 6 TO 7 IS PROVIDED ONLY


FOR OPTIONAL NFPA 110 ALARM MODULE.

131-TBA1-131T

23

Mechanical system not responding properly.


Abnormal frequency, pulse width, or period.

= 10 AWG

= COMPONENT LOCATED IN MARSHALLING BOX

203-TBA1-203T

SP2-TBD1-SP2AT

21 22

19 20

7
8

LOAD
GAIN

DROOP

NOTE A: ALL WIRE IS STRANDED 16 AWG UL & CSA, 90C, 600 VAC
INSULATION WIRE UNLESS OTHERWISE INDICATED.

98-ATB J1-8
D(-)-TBD1-D(-)T
D(+)-TBD1-D(+)T

Current below normal or open circuit.


Current above normal or grounded circuit.

LOAD
SHARING
MODULE

124-TBA2-122U

16 17 18

2 1

5
6

SERIAL NO.

LOAD SHARING MODULE

SL1

93-ATB J1-3
92-ATB J1-2
97-ATB J1-7

Voltage above normal or shorted high.


Voltage below normal or shorted low.

15 16 17 18 19 20 21 22 23 24 25 26 27 28

3
4

WOODWAR D

640 OHM

13 14 15

10 11 12

SRV-MCS-3
SRV-CAT MONITORING
SYSTEM CONN-23
2-MCS-2
2-TBD1-2FT

PART NO.

WOODWAR D

PLS

Data valid but below normal operational range.


Data erratic, intermittent, or incorrect.

The FMI is a diagnostic code that indicates what type of failure has occurred.

SRV-SCS-3
2-MCS-5
2-SCS-2

3200 OHM

18-TBD1-18T

2
1

7
67-TBD1-67BB

3
3

1
2

MCS
6

SCS

B
C
SLR1

91-ATB J1-1

CLR-MCS-4
CLR-CAT MONITORING SYSTEM CONN-33

11

42-SP-3

21

31

12

2-TBD1-2ET
2-TBD1-2FB
10-TBD1-10BL

20-TBD1-20BL

22

D(-)-TBD1-D(-)L
HC1-TBD1-HC1T

S-SPD-ECM-10

SRV-SCS-3
CLR-MCS-6
2-TBD1-2GT

163

162

D(+)-TBD1-D(+)L

SV-TBD1-SVAT

10-PLS-3

2-TBD1-2EB

SL2

SLR 2
C
D

2-TBD1-2HT

30-TBD1-30CT

2 1

ER-TBD1-ERT

Failure Description
Data valid but above normal operational range.

CONTROL PANEL
REAR SUB PANEL

443

Crank Termination Relay

USE E-B 5600 OHM

444

Starting Motor Relay

416

USE E-A 7200 OHM

445

Run Relay

480

USE E-A 7200 OHM

446

Air Shutoff Relay

447

Fuel Control Relay

475

Relay Driver Module

500

EMCP Electronic Control (Generator Set)

566

Unexpected Shutdown

590
Engine Electronic Control Module
The CID is a diagnostic code that indicates which component is faulty.

(Dimensions: 39 inches x 24 inches)

56-GSC-40

57-TBD1-57AT

30-TBD1-30CB

1-TBD1-1CB

5-TBD1-5BT
5-ECS-10

5-ECS-10

5-ECS-9
5-ECS-8
54-TDR-B1
58-GSC-32

55-GSC-39

20-TBD1-20BT

30-TBD1-30BT

34-TBD1-34B

14-RM-18

19

ECS

9-PL1-2

160

29

96-ATB J1-6

95-ATB J1-5

94-ATB J1-4

22-TBD1-22B

39

32

SP
5
SS
2

FMI No.

10-ALM-1

NOTE A

10

HC4-TBD1-HC4T

DOOR STUD

20

30-ALM-7
86-LFSR-6
76-D3-L2
75-D2-L2

30

20 Page,

74-70 WAY-21

Failure Mode Identifiers (FMI)

40

82-TBD1-82B

90-TBD1-90L
10-CAM-1
10-RM-39

7
6
5
4
3
2
1

80-TBD1-80B

60-ALM-12
70-70 WAY-44
73-GNDFR-14
71-70 WAY-1

14
13
12
11
10
9
8

10-PWM-B(+)
OR 10-LSGOV-15

69-ALM-14
68-ALM-13

10-TBD1-10BB

30-CAM-7
30-RM-B-

110-TBA1-110L

30-ALM-7

21-TBD1-21B

17-TBD1-17T

46-TBD1-46B

7-TDR-15

RM

1R2

10

GND-TBD1-GND4T
SP-SHIELD

7
6
5
4
3
2
1

13
14

B-

30-TBD1-30BB

1-TBD1-1DB

1-TBD1-1BB

10-ALM-1

1-TBD1-1BT

F10

NC

SP-SHIELD-DOOR STUD

2-TBD1-2CB

24
25
26
27
28

60-CAM-12
70-70 WAY-44

14
13
12
11
10
9
8

43-PWM-3
OR 43-LSGOV-28

39-CR-A

22
23

6
7
8
9
10
11
12

1R1

1L4

ESPB
69-CAM-14
68-CAM-13

42-PWM-1
OR 42-LSGOV-26
44-PWM-2
OR 44-LSGOV-27

6-TBD1-6T

34
35
36
37
38
39

4
5

108-TBA1-108L

37-TBD1-37B

F1
F2
F3
F4
F5
F6
F7
F8
F9

157-TBA1-157T

14-ESPB-1L1

29
30
31
32
33

159-TBA1-159T

16
17
18
19
20
21

NC
NO

1L2

1L3

1L1

1
2
3
99-TBD1-99T

38-TBD1-38T

NOTE B

B+

20-TBD1-20AT
41-DC CONN1-1
41-DC CONN1-2

15

CAM

13-CR-6

ALM
-

10-TBD1-10AT

CAT MONITORING SYSTEM

RENR2477-02 VOL 2 of 2

GND-TBD1-GND4B

COMPONENTS INSIDE CONTROL PANEL

9
8
7
6
5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B

RDM
47
48
49
231A
232A
233A
231B
232B
233B
231C
232C

233C

64
65
66

MARSHALLING BOX
AC CHASSIS

MCB1
OFF
OFF

46 47 48 49 50

AC CHASSIS STUD

T/R

F21 F22

T/R

F24

11

21

F32

12

22

7
A1

F33

MCB1
OFF

2
8

HC

MARSHALLING BOX CUSTOMER TERMINAL BLOCK

1
3
5

2
4
6

142
209
210
EF1
EF2
120
122
124

GND2

B
B
B
B
B
B
B
B
B
B
B

T
T
T
T
T
T
T
T
T
T
T

GNDFR
14
A1
1 3

98

53

54

97
95

2
4

209-OL-2
210-OL-4
EF1-GNDFR-K
EF2-GNDFR-L

124-LSGOV-2 @

GND-PUMP-GND

PC
62

24
14

OL

36-TBD2-36T
2-TBD2-2CB

140-TBA2-140T

142-TBA2-142T

124-TBA2-124T

F50
F51
F52

124-VR6B-24 OR 124-DVR-24

122-TBA2-122T

122-VR6B-22 OR 122-DVR-22

120-TBA2-120T

NOTE C: WIRES 20, 22, AND 24 ARE CONNECTED FROM THE GENERATOR
UNLESS AND RFI FILTER IS PROVIDED.

120-VR6B-20 OR 120-DVR-20

GND-PUMP-GND

120-LSGOV-3 @
U

122-LSGOV-1 @

14
210-PUMP-T4
U

124-LSGOV-2 @

14
209-PUMP-T1

14

142-SPH-H4

14

14

140-SPH-H1

GND-JWH-GND
OR GND-BLH

148-JWH-IL1
OR 148-BLH

139-JWH-IL2
OR 139-BLH

133-TBA2-133AU

133-MCB1-3 14

133-TBA2-131BT

14

124-TBA2-124T

122-TBA2-122T

124-F52-T

120-F50-T
120-GNDFR-A2
122-F51-T
122-AR-A

140

GND

148

139

131

131

GND

GND-TBC-GNDB

14 148-HC-6

14 148-HC-8

8 131-TBC-131T

131-PC-A2
131-AC CONN-33

132

122-LSGOV-1 @

207-F22-B

207-PC-53

203-TBA2-203T

131-TBA2-131AT

204-PC-A1

210-TBA2-210B
205-PR-6

212-F24-B

204-OL-96

208-F21-B

133

F52

209-TBA2-209B

(K) (L)
202-TBA2-202T

140-BC-L
140-HC-2

207-PC-61

134-MCB1-4 14
OR 134-F20-B

141-F18-B

139-TBA2-139B

138-MCB1-2 14
OR 138-F19-B

141-F18-B

132

135-F17-B

206
207

137-TBA2-137T

203

73-CAM-10 @

159
202

148-TBA2-148B

30-TBD2-30BT

157

156-TBC-156T

137

8 132-TBC-132B
14 132-MCB1-1

136

14

14

multi 9

A2

154-TBC-154T

110

142-TBA2-142B

MERLIN GERIN

EF2-TBA2-EF2B

109

120-LSGOV-3 @

140-TBA2-140B

C60N

120-TBA2-120B
120-AR-B

137-HC-A1
137-AC CONN-19
157-F32-B
157-AC CONN-11
159-F33-B
159-AC CONN-15
202-PC-54
202-AC CONN-1
203-PC-62
203-AC CONN-3
206-PR-9
206-AC CONN-24
207-F22-B
207-AC CONN-5
132-F16-T
132-F21-T

136-F16-B
136-AC CONN-17

10 133-TBC-133B

101
108
B

133

GND1
B

159-TBA2-159T

HC

118-AR-7

122-AR-A

101-AC CONN-38

157-TBA2-157T

F20

M-

133-TBA2-133AB

AR

212-PC-3

F33

EF1-TBA2-EF1B

A
M+

132-F21-T

A1

207-PC-61
207-TBA2-207T

F19

132-TBA2-132AB
132-F22-T

208-PC-1

133-TBA2-133BU 14

122-TBA2-122B
122-AR-4

14 134-HC-7

14

132-TBA2-132BB

14 138-HC-5

F17 F18

TBC

118-GNDFR-A1

133-TBA2-133BB

138-HC-7

F16

132-TBA2-132BB

61

138-HC-5

96

133-TBA2-133AT

120-GNDFR-A2

A2
13

141-HC-A2
141-HC-3

95

GND-AC CHASSIS STUD


GND-PANEL GND

GND-TBA2-GND1T
GND-AC CONN-21

D(+)-TBC-D(+)T

132-F16-T

132-F17-T
132-TBA2-132AT

TBA2

135-HC-1

136-TBA2-136T

OL

156-F33-T

14

154-F32-T

24

62

PC

97

156

120-TBA2-120T

14

210-PUMP-T2/T4

14

14

131-SPH-H2
131-SPH-H4
209-PUMP-T1/T3

154

GND

GND-TBA2-GNDAT

GND

10

GND2

133-TBA2-133BT

124

133

122

120

131-TBA2-131BT

EF2

131

EF1

F51

124-VR6B-24 OR 124-DVR-24

210

F50

122-VR6B-22 OR 122-DVR-22

209

120-VR6B-20 OR 120-DVR-20

142

140-SPH-H3

140-SPH-H1

10

GND-JWH-GND
OR GND-BLH

207-PC-53

140

10

10

148-JWH-IL1
OR 148-BLH

131-JWH-IL2
OR 131-BLH

131-BC-N
131-TBA2-142B

98

124-F52-T

GND

GND

148

139

131

131

132-TBA2-132BT

54

131-PC-3

EF2-GNDFR-L

132

= COMPONENT LOCATED IN THE CONTROL PANEL


U

207-F22-B

53

203-TBA2-203T

10-TBD2-10T

204-PC-A1

A1
1 3

66-ALR-7

61-TBC-61T
3-TBD2-3T

65-ALR-1

90-TBC-90T

210-TBA2-210B
205-PR-6

30-TBD2-30AT

64-ALR-4

14

120-F50-T
120-GNDFR-A2
122-F51-T
122-AR-A

131-TBA2-131AT
131-PC-A2

204-OL-96

CB3-AUX-14

209-TBA2-209B

EF1-GNDFR-K

208-F21-B

207-PC-61

CB3-AUX-11

202-TBA2-202T

210-OL-4

209-OL-2

CB3-AUX-12

CB2-AUX-14

GND-TBC-GNDB

207

= COMPONENT LOCATED ON ENGINE OR BASE

U
U

CB2-AUX-11

131-TBA2-131AT

GND-BC-GND
140-BC-L
140-HC-2

10 148-HC-6

206

132

203

157
159

137

202

136

133

120V AC OPTIONS

CB2-AUX-12

3
131-TBA2-131BB

10

8 131-TBC-131T
131-HC-A2

131-PC-3
131-AC CONN-33

132-TBC-132B
10 132-MCB1-1

110

CB1-AUX-14

44 45

138-MCB1-2

109

133

101
108

GND1

SP4

SP3

NOTE B: CONNECT WIRES 2, 3, AND 30 FROM ATR2 TO ATR3 IF


BTR IS NOT PROVIDED. IF BTR IS PROVIDED, CONNECT
WIRES 2, 3, AND 30 FROM ATR2 TO BTR AS INDICATED.

CB1-AUX-11

A1

CB1-AUX-12

49-KWR-4

48-KWR-7

NOTE C

10 148-TBA2-148B

137-TBA2-137T

135-F17-B

22

47-KWR-1

MARSHALLING BOX
DC CHASSIS

73-CAM-10

30-TBD2-30BT

120-TBA2-120B
120-AR-B

137-HC-A1
137-AC CONN-19
157-F32-B
157-AC CONN-11
159-F33-B
159-AC CONN-15
202-PC-54
202-AC CONN-1
203-PC-62
203-AC CONN-3
206-PR-9
206-AC CONN-24
207-F22-B
207-AC CONN-5
132-F16-T
132-F21-T

136-F16-B
136-AC CONN-17

10 133-TBC-133B

101-AC CONN-38

GND-AC CHASSIS STUD


GND-PANEL GND

SP1
SP2

81-TBD2-81T

85-TBD2-85B

205-OL-95

65-TBC-65T

64-TBC-64T

84-LFLS-3

81-LFLS-4

81-LFLS-1

72-LFLS-7

30-FRBS-2

30-LFLS-6

10-LFLS-8

3-BTR-D
3-ATR1-D

2-MV-1

2-BTR-E
2-ATR1-E

132

F32

ATA-

J1

F21 F22

ATA+

multi 9

140-TBA2-140B

VR6-B
C60N

21

12

ATA(+)-ADEM-31
ATA(+)-SERVICE CONN-J
ATA(-)-ADEM-32
ATA(-)-SERVICE CONN-H
RDM-DC CONN-7

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
MERLIN GERIN

11

CCM(-)-DC CONN-18

T/R

F17

(K) (L)

NOTE G

8
M-

124-F52-B
122-F51-B
120-F50-B

M+

F16

CCM-

CCM+

B+ B- 20 22 24 26 28 30 F1 F2

= 8 AWG

D(-)-DC CONN-20
D(-)-SERVICE CONN-E
CCM(+)-DC CONN-8

2-TBC-2AB
36-TBD2-36B
GND-DC CHASSIS STUD

AR

SP1-TBD2-SP1B

T/R

D-

82-TBD1-82L @
276-PF/KVAR-1
80-TBD1-80L @
275-PF/KVAR-3

SP2-TBD2-SP2B

A2

157-TBA2-157B

GND-TBA2-GND1T
GND-AC CONN-21

83-TBD2-83T

49-TBC-49T

NOTE A: ALL WIRE IS STRANDED 16 AWG UL & CSA, 90C, 600 VAC
INSULATION WIRE UNLESS OTHERWISE INDICATED.

D(-)-ADEM-6

A1

D(+)-DC CONN-19
D(+)-SERVICE CONN-D

11

AC CHASSIS STUD

71-TBD2-71B

D+

99

5
B

D(+)-ADEM-7

63-TBC-63T

99-DC CONN-38

DVR

21

K L M N O P Q R S

31

90

16

90-DC CONN-5

26

6-TBD2-6T

6A-DROOP-D1
5A-DROOP-D2

87-TBC-87T

12

89

36

EF2-TBA2-EF2B

70-TBD2-70B

89-DC CONN-33

88-DC CONN-32

16

GND-AC CHASSIS STUD


202-TBA2-202B

22

5-TBD2-5B

88

26

EF1-TBA2-EF1B

36

NOTE E

32

13

11

88-TBC-88T

23

14

87

RDM-TBC-RDMT

156-TBC-156T

159-TBA2-159T

17

87-DC CONN-31

27

40 41 42 43 5

33

24

SP3-TBD2-SP3B

63

37
118-AR-7

74-TBD2-74B

61-DC CONN-13
61-KWR-A
63-DC CONN-6

21

89-TBC-89T

34

12

SP4-TBD2-SP4B

15

61

17

154-TBC-154T

27

157-TBA2-157T

37

57-DC CONN-30

22

72-TBD2-72B

124-F52-B
122-F51-B
120-F50-B

13
203-TBA2-203B

25

159-TBA2-159B

57

DC CHASSIS
3

23

35

122-TBA2-122B
122-AR-4

206-TBA2-206B
2-TBD2-2BB

18

20

14

207-TBA2-207B

28

RFI FILTER
24

38

30

K L M N O P Q R S

15

99-TBC-99T
81-TBD2-81B

CCM(-)-TBC-CCM(-)T
CCM(+)-TBC-CCM(+)T

132-F21-T

136-TBA2-136B

207-PC-61
207-TBA2-207T

31

25

19

84-TBD2-84B

32

18

29

10

6A-DVR-6

39

20

20

33

28

30

131-TBA2-131AB

19

40

137-TBA2-137B

10

PF/KVAR

29

10

D(-)-TBC-D(-)T

122-AR-A

57-TBC-57T

118-GNDFR-A1

34

20

DC CONN
(40 WAY)

132-TBA2-132AB
132-F22-T

PANEL GND

208-PC-1

AC CONN
(40 WAY)

35

30

2 - TBD1 - 2 F T

38

TBA2

39

WIRE NO.

(IF REQUIRED)
TERMINAL CONNECTION POINT
T=TOP
B=BOTTOM
U=UPPER

132-TBA2-132BB 10

B
SP4-DC CONN-34

DEVICE TERMINAL NUMBER

10 138-HC-5

40

DEVICE ABBREVIATION

24

101-TBA2-101B

DROOP RESISTOR

22
24

NOTE F: UL LISTED BATTERY CHARGER WILL BE ENGINE MOUNTED.


NOTE G: REMOVE JUMPERS FOR OPTIONAL PM GENERATOR.
B

22
3
2

T
(IF REQUIRED)
SPECIFIC TERMINAL BLOCK
FOR WIRE NO. I.E.: 'A' IS
THE FIRST BLOCK, 'B' IS
THE SECOND BLOCK,...,'F'
IS THE SIXTH BLOCK

ATR2

WIRING EXAMPLE

D1

6-SHUNT TRIP3-C2

2-SHUNT TRIP3-C1

84-TBD2-84T
84-PR-8

NOTE D: WIRES 5A AND 6A AR TO BE SOLDERED TO RESISTOR.

132-F16-T

SERVICE CONNECTOR

8
B
NOTE E: WIRES 26, 28, AND 30 WILL NOT BE CONNECTED WITH
A STANDARD SE GENERATOR.

135-HC-1

5A-DVR-5

GND-TBC-GNDT
GND-TBA2-GND1B
GND-TBD2-GNDB

SP1-DC CONN-4

9
84-PR-7

2-TBD2-2AT
2-SERVICE CONN-B
2-SHUNT TRIP1-C1
2-SHUNT TRIP2-C1
3-TBD2-3B
3-GNDFR-A1
6-TBD2-6B
6-ALR-A
6-SHUNT TRIP1-C2
6-SHUNT TRIP2-C2
10-TBD2-10B
10-SERVICE CONN-A
30-TBD2-30AB

206-TBA2-206T

SP2-DC CONN-14
77-TBD2-77T
SP3-DC CONN-24

7
2-TBD2-2AB

PR

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

136-TBA2-136T

132-F17-T
132-TBA2-132AT

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

= 14 AWG

120-GNDFR-A2

D2

= 10 AWG

14

GND-PANEL GND

BTR

8
A
6-TBC-6B

ALR

276-DVR-44

5A-DROOP CT
6A-DROOP CT
80-TBD1-80L @
82-TBD1-82L @

K L M N O P Q R S

275-DVR-45

ATR3

10

NOTE C
20-GEN-20 OR 20-RFI-20
22-GEN-22 OR 22-RFI-22
24-GEN-24 OR 24-RFI-24
26-GEN PM
OTE E
N28-GEN PM
30-GEN PM
F1-GEN FIELD LEAD
F2-GEN FIELD LEAD

adjust
set point
read

10-TBD2-10U
2-TBD2-2BT
20-GEN
22-GEN
24-GEN
26-GEN PM
28-GEN PM
30-GEN PM
F1-GEN FIELD LEAD
F2-GEN FIELD LEAD

A B C D E F G H I J

20-GEN

10-TBC-10B

adjust
set point
read

ATA(+)-TBC-ATA(+)B

A B C D E F G H I J

24-GEN

8
B

66-TBC-66T

KWR

D(+)-TBC-D(+)B

A
2-TBD2-2CT

47-TBC-47T

61-TBC-61B

20-VR6B-20

1 2 3 4

24-VR6B-24

1 2 3 4

ATA(-)-TBC-ATA(-)B

ATR1

48-TBC-48T

D(-)-TBC-D(-)B

K L M N O P Q R S

22-GEN

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

22-VR6B-22

181-TC5-WH
182-TC5-RD

TBD2

2-ATR1-E
2-ATR3-E

5-TBD2-5T

191-TC6-WH
192-TC6-RD

adjust
set point
read
T

3-ATR1-D
3-ATR3-D

2
2
2
3
6
10
10
30
30
36
71
72
74
81
81
84

GND

2-ATR2-E

A B C D E F G H I J

30-ATR2-1
30-ATR3-1
75-ATR1-7
75-ATR3-7

84-PR-7
84-DC CONN-10

74-ATR1-3
74-DC CONN-37
81-PR-4
81-DC CONN-9

75-ATR2-7

adjust
set point
read
B

3-ATR2-D

1 2 3 4

30-ATR3-1

A B C D E F G H I J

72-DC CONN-17

T
B

30-ATR1-5
30-ATR2-5
74-ATR1-3
74-ATR3-3

D
B

171-TC4-WH
172-TC4-RD

T
B

2-TBD2-2AU
2-ATR2-E

74-ATR2-3

1 2 3 4

10-DVR-B(+)
30B-DC CONN-15
30-TBC-30T
30-GNDFR-11
30-ATR1-1
30-BTR-1
36-BC-(+)
36-DC CONN-11
71-BTR-3
71-DC CONN-16

163-BT1-RD
164-BT1-WH

T
3-TBD2-3U
3-ATR2-D

2-DC CONN-35
2-ALR-B
2-BC-(-)
3-DC C0NN-3
3-TBC-3T
6-DC CONN-2
6-TBC-6T
10-DC CONN-12
10-TBC-10T

30-ATR2-5
30-ATR3-5

C
U

30-ATR1-1
30-ATR2-1
@ 75-D2-L2
75-ATR2-7

30-TBD2-30BB
30-ATR1-5
74-TBD2-74T
74-ATR2-3

B
77-TBD2-SP3T

@ 76-D3-L2

T
B

2-TBD2-2AU

3-TBD2-3U

U
B

30-BTR-1

77

77-FRBS-1

85

85-MV-2

83

B
T
B

71-TBD2-71T

30-TBD2-30BB
30-BTR-5

83-LFLS-2

T
70-DC CONN-36
70-LFLS-5
GND-DC CHASSIS STUD
GDN-PANEL GND
83-PR-A
2-TBC-2T
2-PR-B
85-PR-5
2-DVR-(B-)

5-KWR-B
5-DC CONN-22

DC CHASSIS STUD

70

GND-TBD2-GNDT
GND-DC CONN-21

B
U

(Dimensions: 39 inches x 24 inches)

GND

20 Page,

RENR2477-02 VOL 2 of 2

9
2
1

240V AC OPTIONS

A2
A2

+
-

A
AC TERMINALS
DC TERMINALS

NOTE: This Terminal Block is common for both 120V AC and 240V AC Options.

THIS SCHEMATIC IS FOR THE 3456 GENERATOR SET with EMCP II


VOLUME 2 of 2: DESCRIPTION

Components are shown installed on a fully operable machine with the key and engine off, transmission shifter
in neutral and with parking brake set.
Refer to the appropriate Service Manual for Troubleshooting, Specifications and Systems Operations.

A2
13

GNDFR
61

96

4
8

NOTE F

BC

MARSHALLING BOX
AC CHASSIS