PROJECT
CLIENT
CONSULTANT
EPC
CONTRACTOR
Document ID
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Input Data
1.1
Type of Panel
Cubical Type
1.2
System
1.3
Rated Voltage
415V
1.4
degree of Protection
50 Hz.
1.5
1000
1.6
50
1.7
50
1.8
85
1.9
70
1.10
Degree of Protection
:
:
:
1 x 1 x 125 x 10 MM
1 x 125 x 06 MM
1
:
:
1.12
125
10
750
1.13
1250
1.14
Type of Insulator
1.15
2.5KV RMS
b. Bus bar
Minimum Clearance:
a. Phase to Phase
25 mm
b. Phase to Earth
20 mm
1.11
a
1.16
1.17
1.18
Applicable Standard
1.19
Degree of Protection
1.20
0.5mtr. (500mm)
Page 1 of 4
2
2.1
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
50
85
200
1.007851794
650.226
2.2
2.2
1250
Conclusion:
2.3
3
3.10
The required cross section 650.226 Sq.mm is less than actual cross section 1250 Sq.mm of the bus bar
selected. Hence, the bus bar size chosen is safe for the envisaged system.
Bus bar Selection for Continuous Current Rating :
Bus bar Selected
As per Clause1.11
1850
1 x 1850
:
:
1850
150
3.13
Enclosed Size in (W x D x H ) mm
3.14
800 x 400 mm
3.15
50 Deg. C
3.16
35 Deg. C
3.17
Enclosure Material
MS Steel
3.11
3.12
Page 2 of 4
3.18
3.19
3.20
3.21
4
4.10
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
De-rating / Up rating:
a Ambient correction factor for 35 Deg. Rise
0.9
0.87
=
=
=
0.9
0.95
1
0.67
1850 x 0.67
= 1238.51025
Rating of Panel required (As per Clause 1.5)
= 1000
Conclusion :
The de-rated Current rating 1238.51 amp of Panel selected is more than the required current rating 1000 amp
of Bus duct Bus bar. Hence, the bus bar size chosen is safe for the envisaged system.
Support Insulator Span Calculation During Short Circuit
Fm = Peak Electromagnetic force along the centre
= K x 16 x Isc x 10 / S
line of busbar without enclosure
50
0.250
0.904
corresponding to a that is 60
Fm (Nm / cm )
14400.000
Fm ( Kg / cm ) = (Fm x 0.1019716)
F = Force acting on top of the insulator
=
=
1468.391
Fm (H+h)/4H
38
75
1091.632813
Sk / (SF x F )
1600
SF = Safety factor
2.5
586.278
4.12
a
b
4.13
b
Length of Span of insulator in mm
Adopted Span is
OK
Conclusion:
4.4
Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe for the system
envisaged.
Page 3 of 4
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
5.1
1238.51025
5.2
1000
5.3
35
5.4
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )
24.64
OK
T2
Calculated Temperature is
1.64
Conclusion :
5.5
The Calculated Temperature rise of bus bar is 24.64 Deg. C, which is within the design Specified Temp. 35
Deg. C and it is safe for the System envisaged.
Checked By : Kamlakar D.
Page 4 of 4
Approved By : A.B.H