0.04 s
5.00 %
0.10 Iref
3.00 %
No
VT connection:
CT starpoint connection:
At protected object
To protected object
.
Elements - Phase:
Active
Yes
Name
I #2 Phase
Tripping characteristic
IEC Definite Time
I Pick-up
3.00 Iref
Time
0.04 s
Reset Ratio
0.95
Direction
Non Directional
Test Module
Name:
Test Start:
User Name:
Company:
OMICRON Overcurrent
26-Aug-2016 14:23:26
Version:
Test End:
Manager:
3.01
26-Aug-2016 14:23:57
Test Settings:
.
Fault Model:
Time reference:
Load current:
Load angle:
Prefault time:
Abs. max time:
Post fault time:
Rel. max time:
Enable voltage output:
Fault voltage LN (for all but two phase faults):
Fault voltage LL (for two phase faults):
Decaying DC active:
Time constant:
CB char min time:
Thermal reset active:
Thermal reset method:
Thermal reset message:
Fault inception
0.00 A
0.00
0.10 s
240.00 s
0.50 s
100.00 %
No
30.00 V
51.96 V
No
0.05 s
0.05 s
No
Manual
Please reset the Thermal Memory of the device under
test before continuing.
Binary Inputs:
Trigger Logic:
And
Name
Trip
Trigger State
1
.
Pick-up / Drop-off Test:
Type
Angle
Resolution
I Pick-up
Reset Ratio
L1-L2-L3 n/a
L1-L2-L3 n/a
L1-L2-L3 n/a
0.05 s
0.05 s
0.05 s
nom
min
max
nom
15.00 A
15.00 A
15.00 A
14.50 A
14.50 A
14.50 A
15.50 A
15.50 A
15.50 A
0.95
0.95
0.95
.
Pick-up / Drop-off Test Results:
Type
Angle
L1-L2-L3 n/a
L1-L2-L3 n/a
L1-L2-L3 n/a
I Pick-up
nom
act
I Drop-off
act
Reset Ratio
nom
act
Error
15.00 A
15.00 A
15.00 A
14.95 A
14.95 A
14.95 A
0.95
0.95
0.95
5.97 %
5.97 %
5.97 %
14.85 A
14.85 A
14.85 A
.
State:
3 out of 3 points tested.
3 points passed.
0 points failed.
General Assessment: Test passed!
1.01
1.01
1.01
Result
Passed
Passed
Passed