You are on page 1of 2

Overcurrent_Beckwith_M3311B:

Test Object - Overcurrent Parameters


.
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.10 Iref
3.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

.
Elements - Phase:
Active
Yes

Name
I #2 Phase

Tripping characteristic
IEC Definite Time

I Pick-up
3.00 Iref

Time
0.04 s

Reset Ratio
0.95

Direction
Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
26-Aug-2016 14:23:26

Version:
Test End:
Manager:

3.01
26-Aug-2016 14:23:57

Test Settings:
.
Fault Model:
Time reference:
Load current:
Load angle:
Prefault time:
Abs. max time:
Post fault time:
Rel. max time:
Enable voltage output:
Fault voltage LN (for all but two phase faults):
Fault voltage LL (for two phase faults):
Decaying DC active:
Time constant:
CB char min time:
Thermal reset active:
Thermal reset method:
Thermal reset message:

Fault inception
0.00 A
0.00
0.10 s
240.00 s
0.50 s
100.00 %
No
30.00 V
51.96 V
No
0.05 s
0.05 s
No
Manual
Please reset the Thermal Memory of the device under
test before continuing.

Binary Inputs:
Trigger Logic:

And

Name
Trip

Trigger State
1

.
Pick-up / Drop-off Test:
Type

Angle

Resolution

I Pick-up

Reset Ratio

L1-L2-L3 n/a
L1-L2-L3 n/a
L1-L2-L3 n/a

0.05 s
0.05 s
0.05 s

nom

min

max

nom

15.00 A
15.00 A
15.00 A

14.50 A
14.50 A
14.50 A

15.50 A
15.50 A
15.50 A

0.95
0.95
0.95

.
Pick-up / Drop-off Test Results:
Type

Angle

L1-L2-L3 n/a
L1-L2-L3 n/a
L1-L2-L3 n/a

I Pick-up
nom
act

I Drop-off
act

Reset Ratio
nom
act

Error

15.00 A
15.00 A
15.00 A

14.95 A
14.95 A
14.95 A

0.95
0.95
0.95

5.97 %
5.97 %
5.97 %

14.85 A
14.85 A
14.85 A

.
State:
3 out of 3 points tested.
3 points passed.
0 points failed.
General Assessment: Test passed!

1.01
1.01
1.01

Result
Passed
Passed
Passed