You are on page 1of 197

LSHORT-CIRCUIT CURRENT

..

CALCULATIONS

AND PROTECTIVE RELAY COORDINATION FOR


INDUSTRIAL AND COMMERCIAL POWER SYSTEMS,

A Thesis Presented to
The Faculty of the College of Engineering and Technology
Ohio University

In Partial Fulfillment
of the Requirements for the Degree
Master of Science

Houshang C. Mohammadi
s
August, 1986

OHIO UNIVERSITY
LIBRARY

ACKNOWLEDGEMENTS

I would
to

Dr.

their

like to offer my appreciation and thanks

J.F. Keri my advisor, and Dr. H.W. Hill for

Albert

guidance and encouragement in the preparation of this

thesis.

I owe
company

who

gave

education while
my

thanks

to

great
me

deal to my employer,

this

opportunity

to

E.I. Dupont

continue

my

I was working. I would also like to express


Mr.

R.L. Doughty senior project engineer at

E.I. Dupont company who checked my work through this study.


Finally,

I would like to express my thanks to the

faculty and all members of staff at Ohio University who have


contributed a great deal towards this work.

TABLE OF CONTENTS

CHAPTER

CHAPTER

CHAPTER

ABSTRACT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

xii

1.

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1

Statement of the problem . . . . . . . . . . . . . . . .

1.2

Literature search . . . . . . . . . . . . . . . . . . . . . . .

1.3

State of the art . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.

Sources of short circuit . . . . . . . . . . . . . . . . . 7

2.1

Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

2.2

Synchronous motors . . . . . . . . . . . . . . . . . . . . . . . 8

2.3

Induction motors . . . . . . . . . . . . . . . . . . . . . . . . . 10

2.4

Electric utility systems . . . . . . . . . . . . . . . . . 11

2.5

Rotating machine reactance . . . . . . . . . . . . . . . 12

2.6

Symmetrical and asymmetrical currents . . . . 15

3.

Short-circuit-current calculation . . . . . . . . 17

3.1

Important assumptions . . . . . . . . . . . . . . . . . . . . 18

3.2

Single line diagram . . . . . . . . . . . . . . . . . . . . . . 18

3.3

Impedance diagram . . . . . . . . . . . . . . . . . . . . . . . . 19

3.4

Type and location of faults required . . . . . 22

3.5

Symmetrical short-circuit current . . . . . . . . 22


calculation

3.6

Momentary short circuit calculation . . . . . . 25

3.7

Interrupting short circuit calculation . . . 27

CHAPTER

4.

General equipment used for protection .

4.1

Overcurrent relays . . . . . . . . . . . . . . . . .

CHAPTER

31

4.3

....... 32
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.4

Generator protection

4.5

Transformer protection . . . . . . . . . . . . . . . . . .

5.

Coordination of protective devices . . . . . . . 47

5.1

Primary considerations for coordination . . 48

5.2

Data required for a coordination . . . . . . . . . 51

5.3

Methods of coordination. . . . . . . . . . . . . . . . . . 52

5.4

Testing of protective devices . . . . . . . . . . . . 66

6.

Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2

CHAPTER

...

....................

40

44

72

BIBLIOGRAPHY

....................

APPENDIX 1 .

Impedance data . . . . . . . . . . . . . . . . . . . . . . . . . .

77

Al.l

ANSI standard reactance values . . . . . . . . . .

77

A1.2

Transmission line impedances . . . . . . . . . . . .

78

A1.3

1 5 K V cable impedances . . . . . . . . . . . . . . . . . . .

79

A1.4

5KV cable impedances . . . . . . . . . . . . . . . . . . . .

80

A1.5

Correction factors for non magnetic ducts 81

APPENDIX

APPENDIX

APPENDIX

APPENDIX

2.

Belle plant short circuit study . . . . . . . . .

82

A2.1

Description of the work . . . . . . . . . . . . . . . . .

82

A2.2

12KV air circuit breaker ratings . . . . . . . .

84

A2.3

System assumptions . . . . . . . . . . . . . . . . . . . . . .

84

A2.4

Belle plant single line diagram . . . . . . . . .

85

A2.5

Belle plant impedance diagrams . . . . . . . . . .

87

A2.6

Belle plant short circuit calculation . . .

93

3.

System generator protection . . . . . . . . . . . . .

98

A3.1

Belle plant generator protection . . . . . . . .

98

A3.2

Belle plant bus protections . . . . . . . . . . . . .

115

4.

Belle plant- transformer protection . . . . .

120

A4.1

~~~e HU-1 transformer differential relay

120

5.

Belle plant coordination curves . . . . . . . .

126

and detailed diagrams

"A" switch house. BANK No.1 and 12KV BUS

126

ECR No.6. 12KV BUS "A'f. . . . . . . . . . . . . . . . . .

128

ECR No.6, 12KV BUS "B" . . . . . . . . . . . . . . . . . .

130

Cogeneration generator . . . . . . . . . . . . . . . . . .

132

BANK No.7 feeder No.18. . . . . . . . . . . . . . . . . .

134

2.4KV 600HP motor river pump house . . . . . .

136

2.4KV 450HP motor boiler feeder pump No.5 138

A5.8

2.4KV 75HP motor ash pump . . . . . . . . . . . . . . .

140

A5.9

2.4KV 200HP motor recirculating pump . . . .

142

A5.10 2.4KV 200HP motor F . D . fan boilers .

.....

144

A5.11 2.4KV feeders sheet No.1 & BANK No.60 . . .

146

A5.12 2.4KV feeders sheet No.2 & BANK No.59 .

..

148

A5.13 2.4KV feeders ECR No.5 . . . . . . . . . . . . . . . . . .

150

A5.14 2.4KV 150HP motor boiler No.10 mills . . . .

152

A5.15 2.4KV 550HP motor 1 . D fan boilers . . . . . . .

154

No.6 & 9

No . 14 & 15
A5.16 2.4KV 400HP motor 1 . D fan boilers . . . . . . .

156

No.6 & 9
A5.17 480V feeders ECR No.8 sheet 1 . . . . . . . . . . .

158

A5.18 480V feeders ECR.No.8 sheet 2 . . . . . . . . . . .

160

A5.19 480V feeders ECR No.8 sheet 3 . . . . . . . . . . .

162

A5.20 2.4KV 550HP motors 1 . D fan boiler No.10. 164

APPENDIX

6.

Westinghouse overcurrent relay curves . . .

166

A6.1

Type CO-7 Over Current Relay . . . . . . . . . . . .

166

A6.2 Type CO-9 Over Current Relay . . . . . . . . . . . .

167

Type CO-11 Over Current Relay . . . . . . . . . . .

168

A6.4 Type COM-5 Over current Relay . . . . . . . . . . .

169

A6.3

A6.5

Type CV-2 Under Voltage Relay . . . . . . . . . . . . 170

A6.6

Type CV-7 Under Voltage Relay . . . . . . . . . . .

171

A6.7 Westinghouse type Amptector 11-A . . . . . . . .

172

APPENDIX

APPENDIX

A6.8

Westinghouse type DSL-206 Limiters . . . . . .

173

A6.9

Two pole type AA12P Overload Relay

......

174

7.

Buss fuses curves . . . . . . . . . . . . . . . . . . . . . . .

180

A7.1

Type

LPS-RK Low Peak Dual Element fuse . .

180

A7.2

Type KRP-C HI-CAP Fuses

................

181

8.

ASA Device numbers and functions . . . . . . . .

182

LIST OF FIGURES

2.1

Total short circuit current equals sum of sources 9

2.2

Symmetrical short circuit currents from . . . . . . . . . . 1 3


four surces

5.1

Typical time curves of CO-9 Relay . . . . . . . . . . . . . . . . 63

5.2

Portion of Belle plant relaying detailed diagram . 64

5.3

Portion of Belle plant co-ordination curves . . . . . . 65

A2-1

Block diagram of system setup . . . . . . . . . . . . . . . . . . . . 83

A2-2

Belle plant single line diagram . . . . . . . . . . . . . . . . . . 86

A2-3

Multiplying factors for three phase & line . . . . . . . 91


to ground faults

A2-4

Belle plant simplified impedance diagram . . . . . . . . . 92

A2-5

Equivalent circuit for fault

A2-6

Simplified equivalent circu'it for fault

"A"

(momentary) . . . . . 93

"A". . . . . .

94

"A". . . . . . . . . . .

94

"A" (interrupting) . .

95

Wye-Delta transformation for fault


Equivalent circuit for fault

Wye-Delta transformation for fault "A"(interrup.) 96


Typical time curves for the 10% sensitivity . . . . . . 100
type CA generator relay
Limits for application of the CWC time curves . . . . 102
Typical time curves of the type CWC relay . . . . . . . . 103
Generator over voltage curve . . . . . . . . . . . . . . . . . . . . . 108
Generator reactive capability curve . . . . . . . . . . . . . . 109
Machine capability curve . . . . . . . . . . . . . . . . . . . . . . . . . 110

A3-7

SDF-1 tripping relay under declining frequency . . . 113

A3-8

Operating time variations with changes in . . . . . . . . 114


time-dial setting

A3-9

KAB relay voltage unit setting . . . . . . . . . . . . . . . . . . . 118

A3-10

KAB relay current unit setting . . . . . . . . . . . . . . . . . . . 119

LIST OF TABLES
Machine reactance and multiplying factors . . . . . . .
Fuse classification. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current limiting characteristics of c-s one . . . . .
time fuse
Transformer ANSI data . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rating ratios for safe co-ordinations . . . . . . . . . . .
Power air circuit breaker minimum band . . . . . . . . . .

ANSI Standard reactance values . . . . . . . . . . . . . . . . . .


Transmission line impedances. . . . . . . . . . . . . . . . . . . .

15KV cable impedances. . . . . . . . . . . . . . . . . . . . . . . . . . .


5KV cable impedances. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Correction factors for non magnetic ducts . . . . . . . .

81

Result of Belle plant short circuit study . . . . . . .

97

Limits for application of CWC relay . . . . . . . . . . . . .

101

ABSTRACT

The
essential
devices

calculation

to

the

and

systems,
designer.
power,

ac

short-circuit

currents,

selection of adequately rated protective

equipment

is

of

in

becoming
Today,

industrial and commercial power

increasingly important to the system

power

systems

carry

larger blocks of

are more important to the operation of the plant and

building,

and

have

greater

safety

and

reliability

requirements.

Meeting these requirements necessitates the

fulfillment of

certain

criteria,

including

the

use

of

adequately rated equipment.


This
power

report

system

especially

others

who

engineering

valuable

electricians,

outlines state of-the-art industrial

to

industrial

are

involved

practices

industrial
power
with

which

plant

should

engineers

application

be
and

engineers and

the planning of electrical

facilities for industrial plants or commercial buildings.


The
has

been

circuit
were

of

short-circuit-current calculation

selected, so that adequate ratings of all the air

breakers

selected

throughout
set

method

were
to

obtained. Fault protective devices

maintain

the system.

proper

relay

coordination

These devices has been selected and

so that only the device nearest a fault opened to clear

the fault without affecting larger devices nearer the source


of power or causing a wider outage than the minimum.
-xii-

CHAPTER ONE

INTRODUCTION

All

power

systems, whether

industrial,

commercial,

purpose

providing

of

safely

or

residential,

electric
and

they

as

be

have

utility,
the common

energy

to the utilization

reliably

as is economically

equipment

as

feasible.

The relative importance of economic, reliability,

and safety considerations may vary somewhat with the type of


system,

but

all

three

elements

must

be

taken

into

consideration in any good system design, and certain minimum


safety and reliability requirements must be satisfied.

1.1 STATEMENT OF THE PROBLEM

Electric power system in today's industrial plants


and

large

quantities

commercial
of

energy.

energy

usage

in

energy

usage

has

such

establishments

continuity
costs

of

enormous

A review of the trend in electric


establishments

indicates that such

been doubling every seven to eight years

and shows little signs of leveling off [ I ] .


processes

handle

Many industrial

and commercial operations demand a high degree of


of

electric

production

considerations

in

power

supply because of the great

downtime.

One

of

the

major

the design of a power system is adequate

control

of

called.
outage

short circuits, or faults, as they are commonly


Uncontrolled

short

circuits

can

cause service

with accompanying production downtime and associated

inconvenience,
extensive

interruption

equipment

damage,

of

essential

facilities,

personnel injury or fatality,

and possible fire damage.


Clearly,
the

power

the

system,

and

fault

must be quickly removed from

this

is the job of the protective

device, the circuit breakers and fusible switches.


to

accomplish

this,

the

protective

In order

device must have the

ability to interrupt the maximum short-circuit current which


can

flow

value

for

a fault at the device location.

The maximum

of short-circuit current is frequently referred to as

the 'Iavailable'l short-circuit current.


The
reader

with

calculate
method

of

this

information

short-circuit

report

and

is

procedures

currents,

and

to provide the
necessary

to

also present a new

of coordination for protective relaying by using the

typical

time

short-circuit
relaying
of

purpose

curves
current

of

the

and

relay.

coordination

Calculation
of

of

protective

for the Belle plant, (one of the biochemical sites

E.I.dupont de Nemours & Company) is shown for the entire

system as an example for this report.


This
protection
affected

as

report
"the

portion

defines

detection

the

function

of

system

and prompt isolation of the

of the system whenever a short circuit or

other

abnormality

occurs

which

might cause damage to, or

adversely affect, the operation of any portion of the system


or the load which it supplies."
This

report

will

be

limited to short-circuit

coordination

of

protective

calculation

and

low-voltage

to medium-voltage industrial plants, commercial

and

institutional

devices

and

report,

which

buildings.

Bussmann

fuses

limits

our

relaying for

Westinghouse

protective

have been used throughout the

selection and information about

other protective devices.


Chapter
and

reviews

One

some

introduces an outline of this report

of

relative

methods

concerning short-

circuit calculation and coordination of protective relaying.


Chapter
their

Two

explains

waveforms.

short-

of

and

explains

for

this

single-line

which

protective
Five

will

includes

less than 50 hp by lumping them

as a single impedance.

in this report.

this report.

required
for

treated

which

calculation,

motors

Chapter

coordination

on

all

different

protection.

presented

Chapter Three explains longhand method of

circuit-current

impedances
together

.the major short circuit sources and

be

devices

Chapter Four

used

for

system

explains

several

method

of

compared

with the new method

Chapter Six gives the conclusion

Appendix 1 provides impedance data that is

the

Belle plant, which is used as an example

report.
diagram.

Appendix

provides

the Belle plant

Appendix 3 provides system generator

protection

for

the

plant.

Appendix

provides

protection of protective relaying for the Belle

transformer

Appendix 5 provides the complete set of coordination

plant.
curves

and

detailed

Appendix

provides

used

throughout

fuse

curves

provides
and

Belle

the

used

the

in

diagrams

for

the

entire

system.

Westinghouse overcurrent relay curves


Appendix 7 provides Bussmann

study.
this

report

and finally Appendix 8

American Standard Association devices numbers

(ASA)

functions

which

are

used

for

an

automatic

switching equipment.

1.2 LITERATURE SEARCH

There

are

short-circuit-current

several

texts

industrial and commercial power system.

is

the

Coordination

Power

of

[6].

provide
relaying

Industrial and Commertial Power Systems by


Other good books are The Art and Science of

Relaying by Russell C. Mason [ 3 ] , and Industrial

Systems

especially

Most noteworthy

IEEE Recommended Practice For Protection and

book

Protective

for

calculation and relaying coordination

of

D.Dalasta

available

Handbook by Donald Beeman [ 2 ] .

These texts,

The Art and Science of Protective Relaying, will

an

understanding

and

their

of

the

function

of protective

operation for protection of industrial

and commercial power systems.

1. 3

STATE OF THE ART

Protection

of power system involves short-circuit

calculation and relay coordination.


At the present there are several methods of shortcircuit-current
industries.
digital

calculation

Longhand

computer

available

throughout

calculation, Network

the

Analyzer and

techniques are the most-used methods.

presence

general,

the

network,

such as might be found in a large industrial plant

high-voltage
digital

of

closed

loops

In

in the impedance

system, will favor using a network analyzer or

computer technique from an economic and time-saving

standpoint[l].
low-voltage

Radial
and

systems,

such as those used in most

medium-voltage

systems,

can

be

easily

resolved by longhand calculations.


There
coordination
commercial
could

are

protective

power

systems

reasonably

Coordination
selectivity
currents
that

several

of

system operation.

1)

also

be

relaying

against

expected

to

for

available

for

industrial

and

any abnormalities which


occur

in the course of

These methods are as follows:


by

tables

assuming

flow

methods

are used as a simple check for

that

identical

or

reduced fault

through the circuits in descending order,

is, main-feeder-branch.

this method is recommended

only for low-voltage branch circuits [6].

2) Coordination by using the device characteristic curve can

be

used for any size system.

on

which the study is being made is placed on top of the

device

characteristic

selected

and

traced.

The sheet of log-log paper

curve.

Proper curve then can be

Human error is very high in this

method which makes it undesirable to use.


Coordination
method

by

using

presented

recommended,

since

in

the typical time curves is a new


this

relay

report.
curve

is

This
drawn

several points from typical time curve.


then

points

require

knowing

the

by

is

finding

These points are

ploted and traced on log-log paper.

these

method

calculation of

relay type, current

transformer (c.t.) ratio, available taps, ampere range of


the

relay,

short-circuit

circuit
current.

voltage

level

and

available

These requirements will ensure

correct data point transformation from typical time curve

of

the

relay

to

the

eleminates human error.

log-log paper, which practically

CHAPTER TWO

SOURCES OF SHORT CIRCUIT

If adequate protection

is

to be provided for a

plant electric system, the size of the electric power system


must

be

current

considered
it

will

to

determine

deliver.

This

how

much short-circuit

is done so that circuit

breakers or fuses may be selected with adequate interrupting


capacity.
to

open

power
a

This interrupting capacity should be high enough


safely the maximum short-circuit current which the

system can cause to flow through a circuit breaker if

short

circuit occurs in the feeder or equipment which it

protects.
When
currents,
short

it

determining
is

circuit

extremely
be

characteristics

the

of

magnitude of short-circuit

important

considered

and

that all sources of


that

these sources be known.

the

impedance

There are four

basic sources of short-circuit current:

1. Generators
2. Synchronous motors
3. Induction motors

4. Electric utility systems


All

these

can

feed short-circuit current into a

short circuit as shown in figure 2.1.

2.1

GENERATORS

Generators are driven by turbines, diesel engines,


water

wheels, or other types of prime movers.

circuit

occurs

generator

on

the

circuit

fed

to

produce

voltage because the field

continues

excitation

is

maintained

generator at normal speed.


short
the

circuit

the

a generator, the

prime mover drives the

The generated voltage produces a

current of a large magnitude that flows from

generator

circuit

and

by

When a short

to

current

the
is

short circuit.

limited

only

generator and the short circuit.

This flow of short-

by the impedance of the

For a .short circuit at the

-of the generator,. the current from the generat0.r

terminals

is limited only by its own impedance.

2.2 SYNCHRONOUS MOTORS

Synchronous
generators;
current
flows.

and

that
a

is,

motors
they

are

constructed

much

like

have a field excited by direct

stator winding in which alternating current

Normally,

synchronous motors draw A.C. power from

the line and convert electric energy to mechanical energy.


During
system

is

a system short circuit, the voltage on the

reduced

to a very low value.

Consequently, the

motor

stops

starts

delivering

slowing

generator,

down.

the

to the mechanical load and

However, as the prime mover drives a

inertia

the synchronous motor.

energy

of the load and motor rotor drives

The synchronous motor then becomes a

generator and delivers short-circuit current for many cycles


after

the short circuit has occurred.

circuit

current

impedance

of

produced

the

by

the

synchronous

The amount of short-

motor

motor

depends upon the

and impedance of the

system to the point of short circuit.


FROM E L ECTRIC

I
UTILITY SYSTEM

TURBINE GENERATOR

SHORT- CIRCUIT
CURRENT FROM
E L E C T R I C UTlUTT
SYSTEM

METAL CLAD
SWITCHGEAR

CURRENT
FROM
GENERATOR

SYNCHRONOUS
MOTOR

TOTAL SHORT
CIRCUIT
CURRENT
-?OM ALL
FGUR

1
SHORTURCUlT
SYN MOTOR

SHORT-CIRCUIT
CURRENT FROM
lNWCTlCE(

Figure

INDUCTION

/1 "

'

2.1 Total short-circuit current equals sum of source


contributions [I] .

2.3 INDUCTION MOTORS

The
motor

have

inertia of the load and rotor of an induction


the

synchronous

same

motor;

effect on an induction motor as on a

that is, they drive the motor after the

system short circuit occurs.

The

There is one major difference.

induction motor has no DC field winding, but there is a

flux

in

the induction motor during normal operation.

acts

like

flux

produced

by

the

This

dc field winding in the

synchronous motor.
The
induction
The
to

of

the induction motor is produced by

the stator rather than from the DC winding.

from

rotor flux remains normal as long as voltage is applied


the

stator

external
when

not

from

source

rotor

an

external source.

However, if the

of voltage were suddenly removed, as it is

short circuit occurs on the system, the flux in the


can not change instantly.

Because the rotor flux can

decay instantly and because the inertia of the rotating

parts
the

drives the induction motor, a voltage is generated in


stator winding.

flow

to

zero.
in

field

short

circuit until the rotor flux decays to

The short-circuit current vanishes almost completely

about

current

the

This causes a short-circuit current to

four
in

the

cycles,

since

there is no sustained field

rotor to provide flux, as in the case of a

synchronous machine.

11
The

flux

short-circuit
circuit

does last long enough to produce enough

current

breakers

to

affect

the

momentary

duty

and the interrupting duty on devices that

open within one or two cycles after a short circuit.


the

short

circuit

considered

in

short-circuit
depends
short
of

upon

short

by

current

produced

the

impedance

by

Hence,

motors must be

induction

calculations.

The magnitude of a
the

induction, motor

of the system to the point of

The machine impedance effective at the time

circuit

standstill.
circuit

produced

certain

circuit.

on

corresponds

closely to the impedance at

Consequently, the

current

inertia

value

of short-

is approximately equal to the locked rotor

starting current to the motor.

2.4 ELECTRIC UTILITY SYSTEMS

The
transformer
considered
speaking,

electric
from

the

sources

of

utility

electric

system

utility

short-circuit

or

the

system

current.

supply

are often
Strictly

this is not correct because the utility system or

supply transformer merely delivers the short-circuit current


from

the

change

utility

the

generate

system

neither.

transformer

is

system

generators.

voltage

and

Transformers merely

magnitude

of current but

The short-circuit current delivered by a

determined

by its secondary voltage rating

and impedance, the impedance of the generators and system to


the

terminals

of

the transformer and the impedance of the

circuit from the transformer to the short circuit.


As

illustrated

symmetrical
sources.
or

in

short

circuit

figure

current

2.2,

usually

the
has

total
several

The first includes generators either in the plant

the

utility

synchronous

motors.

which

are

these

currents

the

in

located

machine

current

system

or both.

The second comprises

The third source is induction motors,


in

every

plant and building.

Because

decay with time due to reduction of flux in

after

decays

short

with

circuit, the total short-circuit

time.

So

even

though

only

the

symmetrical part of the short-circuit current is considered,


the

magnitude of current-is highest at the first half cycle

after short circuit and is of lower value a few cycle later.


Note

that the induction motor component disappears entirely

after one or two cycles [ 2 ] .

2.5

ROTATING MACHINE REACTANCE

The
primarily
for

of

rotating

machine

consists

of reactance and is not one simple value as it is

transformer

variable
applied

impedance

with
to

or a piece of cable, but is complex and

time.

For

example, if a short circuit is

the terminals of a generator, the short-circuit

- T O T A L ASYMMETRICAL CURRENT

OC

COMPONENT
AC

(a) Symmetrical

COMPONEHT

(b) Asymmetrical

Figure 2.2 Symmetrical short-circuit currents from four


sources [ 2 ] .

14
current

behaves

as

current

starts

out

steady-state
inception
voltage
the

shown in figure 2.2a (generator).


at

high

value

and

decays

The
to

value after some time has elapsed from the

of the short circuit.

and

Since the field excitation

speed have remained relatively constant within

short interval of time considered, the reactance of the

machine

may be assumed-to explain the change in the current

value-to

have changed with time after the short circuit was

initiated.
Expression
instant
of

of

variable reactance at any

requires a comlicated formula involving time as one

the

variables.

Therefore,

simplification, three
generators

and

short-circuit
called

such

values

motors

for

for

the

sake

of

of reactance are assigned to


the

purpose

current at specified times.

of

calculating

These values are

the subtransient reactance, transient reactance, and

synchronous reactance and are described as follows:

>

Subtransient reactance

of

the

occurs,

stator
and

it

winding

(XI'd ) is the apparent reactance


at

the

instant short circuit

determines the current flow during the

first few cycles after short circuit.

2)

Transient
following

reactance

onehalf

determines

the

current

the period when subtransient reactance is the

controlling
to

(X'd)

value.

Transient reactance is effective up

second or longer, depending upon the design

of the machine.

3)

Synchronous
determines
is

reactance

that

the current flow when steady state condition

reached.

after

(Xd) is the

reactance

It is not effective until several seconds

the short circuit occurs; consequently, it is not

generally used in short-circuit calculations [ 2 ] .

A synchronous motor has the same kind of reactance


as

generator, but it is of a different value.

motors

have no field coils, but the rotor bars act like the

amortisseur
motors
to

Induction

winding

in

generator; therefore, induction

are said to have subtransient reactance only.

Appendix

reactances

(impedance

used

for

Refer

data) for the multiple value of

the

momentary

and

interrupting

short-circuit calculations for this study.

2.6 Symmetrical and Asymmetrical Currents

The
describe
the

words

"symmetrical"

"asymmetrical"

the shape of the ac waves about the zero axis.

envelopes

of

the

symmetrical

around

"symmetrical

current".

short-circuit

currents

total.

and

peaks

the

of

zero

the

current

axis,

they

waves
are

If
are

called

Figure 2.2a shows the symmetrical


from

four

sources

combined

into

If the envelopes are not symmetrical around the zero

16
axis,

they

shows

the

are called "asymmetrical current".


asymmetrical

Figure 2.2b

short-circuit currents plus the dc

component from all sources.


Most
asymmetrical
circuit

short-circuit
during

occurs.

the

currents

first

are

nearly

always

few cycles after the short

The asymmetrical current is at a maximum

during the first cycle after the short circuit occurs and in
a few cycles gradully becomes symmetrical as shown on figure
2.2b.
Asymmetrical currents are analyzed in terms of two
components,

shown

figure

on

symmetrical

symmetrical

current

As

2.2b.

component

is

and

a dc component as

previously

discussed

the

at a maximum at the inception of

the

short circuit and decays to a steady state value due to

the

apparent change in machine reactance.

circuits,

that

component

will also decay to zero as the energy represented

by

the

dc

resistance
component

is,

those

component
of
is

the circuit.

the

is

containing

In all practical

dissipated

circuit.

The

resistance,

as

rate

I2R
of

the dc

loss in the
decay

of dc

a function of the resistance and reactance of


In practical circuits, the dc component decays

to zero in from one to six cycles [ Z ] .

CHAPTER THREE

SHORT-CIRCUIT-CURRENT CALCULATIONS

The

maximum

magnitude

of

short-circuit current

must

be

known in order to coordinate protective devices as

well

as

to

mentioned

select

adequate

earlier,

there

interrupting
are

three

ratings.

basic

As

methods

of

calculating short-circuit current: network analyzer, digital


computer,
voltage
simple

and

longhand

system
to

use.

the

calculation. For a radial medium-

longhand method is feasible and fairly

Determination of short-circuit current for

the Belle plant, which is used as an example in this report,


is

done

by

this

longhand

calculation method.. Since the

system contains a three-winding transformer and other loops,


delta-wye

network

impedances.
Appendix

transformations

is

used

to

combine

Method of combining impedances are included in

2.

The

following

steps

identify

the

basic

considerations in making short circuit calculations.

>

Make

certain assumptions in a way that simplifies the

calculation

and

also maximum short-circuit current can

be calculated.

2)

Prepare

system

single-line

diagram

which

it

should

include all significant equipment and components.


3)

Prepare

system

impedance

diagram which should display

18
the

interconnected

circuit impedances that control the

magnitude of short-circuit currents.


4)

Identify

Type and location of faults required for the

system.
5

>

Calculate

symmetrical

short-circuit

current for the

system.
6

>

Calculate
currents

interrupting

for

all

and

momentary

short-circuit

identified locations, so that proper

protective devices can be selected for the system.

3.1 IMPORTANT ASSUMPTIONS

Certain
calculation.

simplifying assumptions are made for this

An important assumption is that the fault is

iibolted". That is, it has zero impedance.


not

only

factor

since

equipment
its

simplifies
the

full rating.

assumed,

because

caculation, but also applies a safety

calculated

selected

This assumption

values

are

maximum, and

on this basis is rarely stressed beyond

Furthermore a three-phase fault should be


maximum short-circuit current is required

for device selection.

3.2 SINGLE LINE DIAGRAM

The

system

one-line

diagram

is

fundamental to

19
short

circuit

analysis.

equipment

and

Refer

Appendix

to

It should include all significant

components

and show their interconnections.

2 (section 112.4) for the complete Belle

plant single-line diagram.

3.3 IMPEDANCE DIAGRAM

The
circuit

impedance diagram displays the interconnected

impedances

short-circuit
patterend
current
from
of

control

currents.

for

the

Impedance

momentary

calculations.

system

the

that

and

magnitude

diagrams

interrupting

of

should

be

short-circuit

These impedance diagrams are derived

single-line diagram, by replacing all elements

single-line

diagram with their calculated per-unit

reactances.

Specified reactances of a motor, generator, or

transformer

should

generators,
high-capacity
compared

be

used.

The

transformers,
buses

(above

resistance

reactors,
1000

of

motors,

rating)

is

so

all
and
low,

with their reactance, that their resistance is not

considered in impedance diagram.


Reactance

of

the

cables

600 volts

should be considered in impedance diagram.

and higher

Appendix 1 shows

the tables used for selecting a reactance of these cables


for the Belle plant impedance diagram.
After

it

has

been

decided what elements of the

single-line
diagram,
of

diagram

the

are

to be considered in the impedance

mechanics of making the impedance diagram and

determining

the short-circuit current magnitude used in

this report are as follows.

1)

The

first

cent

ohms,

circuit
not

step
or

is

to decide whether to use ohms, per

per-unit

impedances

ohms to represent the various

in the impedance diagram.

Ohms are

recommended because of the difficalty of converting

ohms

from

one

This

report

voltage

base to another without error.

is listing the impedance or reactance data

in per-unit.
2)

The

second

represent
by

step in making an impedance diagram is to

every

reactance

connected
bus" .

"infinit

so-called
internal

generator and motor and utility supply

voltage

of

to

a zero impedance bus or

This

bus

represents

the generators and motors.

the

These

reactances can be found as follows:


Utility

X= [MVAbaseI / [MVAUtilityI P e l l .

X=(XIfd%)[MVAbase/MVAgenerator1 P.U.
Motor X= (XI1d%)[MVAbase/KvAmo torI P.U.
Generator

Since
under

50

hp,

most

industrial plants contain many motors

Unlike other methods available for the short

circuit

study, this report recommends that induction motors

smaller

than 50 hp should be lumped together and treated as

single

impedance

on

the

secondary

side of the supply

21
transformer.
reactance
for

the

This

of

slightly

reduces the equivalent

the system, which means, the calculated value

momentary

slightly

will

and

higher.

interrupting short circuit will be

This will create a safety factor for the

system protection when selecting protective devices.


Table

Al-1

sequence

reactance

multiple

factors.

in

Appendix

shows

the positive-

of the short-circuit sources with their


These

multiple

factors are used when

determining momentary and interrupting short-circuit current


for

selecting

motor

in

factor

current,

For example, for a 600 hp

a branch circuit, the positive-sequence reactance

is

1.2

interrupting
current

circuit breakers.

for

case.

factor,
has

to

momentary
The

which
be

is

calculation

reciprocal

of

normally

six

multiplied

by

and

3.0 for

the locked rotor


times

full load

these factors for the

correct Thevinin reactance of the load as shown below.

Xth(momentary)=l.2 (1/6) (base KVA/ KVA load) p . u.


Xth(interrupting) =3.0(1/6) (base KVA/KVA load) p . u .
KVA(1oad) = (power factor) (motor hp)

3)

The third step is to add the reactance of cables, buses,


transformers, current transformers and circuit breakers,
in

their

digram.

proper

location

to

complete

the impedance

Appendix 2 (section A2.5) shows the calculation

of these reactances for the Belle plant.

TYPE AND LOCATION OF FAULTS REQUIRED

3.4

All

buses

should

be

identified.

The location

where short circuit studies are required should be selected.


In

many studies, all buses are faulted.

circuit

currents

rating
A2-1

we required is based on the short-circuit

of the equipment located at the faulted bus.

in

which

The type of short-

Figure

Appendix 2 shows the block diagram of system setup

includes the fault locations calculated for the Belle

plant.

Locations

were

mainly

picked

on main buses and

feeders .

3.5 SYMMETRICAL SHORT-CIRCUIT CURRENT CALCULATION

After

completing

the

impedance

diagram

and

inserting the values of reactance or impedance for each part


ot

the

one

diagram,

equivalent

reactances

is

it is necessary to reduce this network to


value.

used

in

Longhand
this

method

report.

If

of

combining

there are three

reactances in the system, the following shows how to combine


them.
a)

Combining series reactances:


X1+%+X3=X

=equivalent reactance
e

X1,%,X3=reactances

b)

of circuit components

Combining parallel reactances:

Xe=equivalent reactance
Some
by

merely

sytems

combining

are such that they cannot be reduced


series

and parallel reactances.

For

example, the equivalent impedance diagram of the Belle plant


is

shown

Appendix 2 (figure A2-5).

in

In order to reduce

this circuit to a single reactance, wye-delta transformation


is

used.

system

By these transformation any commonly encountered

impedance

diagram

can be reduced to one equivalent

reactance.
The

calculation

to

derive

the

symmetrical

short-circuit current is I=E/X where E is the system driving


voltage and X is the equivalent positive impedance.
When calculations are made in per-unit
four

base

impedance,

quantities :
and

base

base current.

KVA, base

there are

voltage,

When any two of the four are

assigned values, the other two values can be derived.


common

practice

voltage.

to

assign

study

base

Base current and base impedance are then derived

each of the voltage levels in the system.

the

KVA

the

base

It is

values to KVA and

for

nominal

base

base

assigned

line-to-line
voltages.

circuit calculations:

For example,

for the Belle plant is 5 MVA.

system

The

voltages are normally used as

Following

formulas

apply for short

Basic per-unit relationship:


Per-unit voltage=actual voltage/base voltage
Per-unit current=actual current/base current
Per-unit impedance=actual impedance/base impedance
Change

from

percent

on

an

old base to per unit on a new

base :
XpUNEW= (XpUOLD) (NEW

KVABASE/OLD KVABASE)
(OLD

KVBASE/NEW KVBASE

Symmetrical 3 phase short-circuit current in per unit (p.u.)

Ip.u.=Ep.u.jZp.u.

current in amperes, I=I(base)

phase

short-circuit

[ZP.U.I

Symmetrical 3 phase short circuit


were,

symmetrical

KVA, KVA=KVA(base) /Z (p .u . )

I(base) =KVAbase/\/S (KVLL,base 1


When

calculations

are

made in ohms, symmetrical

three-phase

short-circuit in amperes will be

EL-n =line to

neutral voltage and

I=E

L-n

/Z where

is the equivalent network

impedance in ohms per phase.


Calculation

points

at

different

Belle plant is done in Appendix 2,

level

section

A2.6. Calculation of fault duties is done for both

locations.

and

the

several

voltage

momentary

for

for

interrupting

current

for

different

fault

3.6 MOMENTARY SHORT CIRCUIT CALCULATION

The
with

time

fact

has

that

led

the

to

the

current changes in magnitude


establishment of two bases of

short-circuit-current ratings on power circuit breakers: (1)


the

momentary rating or its ability to withstand mechanical

stresses

due

to

interrupting

high

short-circuit

current

and (2) the

rating or its ability to interrupt the flow of

short-circuit current within its interrupting element.


Calculation
asymmetrical
short

current

circuit

factors

to

of

may

account

at

be

the

rms

value

of

an

any time after the inception of a

very

for

precise

involved.

the

Accurate decrument

dc component at any time are

required, as well as accurate factors for the rate of change


of

the

method
been

apparent reactance of the generators.


may

This precise

be used if desired, but simplified methods have

evolved

whereby

the dc component is accounted for by

simple multiplying factors.

The multiplying factor converts

the rms value of the symmetrical (interrupting) ac wave into


rms amperes of the asymmetrical (momentary) wave including a
dc component.
The magnitude of the dc component depends upon the
point on the voltage wave at which the short circuit occurs.
For

protective-device

component

is

application, only

the

maximum

dc

considered, since the circuit breaker must be

26
applied to handle the maximum short-circuit current that can
occur in a system.
In

general case for circuits rated above 600

the

volts, the multiplying factor to account for dc component is


1.6

times

the rms value of the ac symmetrical component at

the

first

cycle.

multiplying
first
the

For

factor

cycle

average

to

600 volts and less, the

circuits
calculate

the total current at the

is 1.25 when the circuit breaker is applied on


current

in

three

phases.

These factors are

listed in table 3.1 [2] .


Since

the short-circuit current is maximum at the

first-cycle, the short-circuit current must be determined at


the first-cycle to determine the maximum momentary duty on a
circuit
the

breaker.

To determine the short-circuit current at

first cycle, it is necessary to consider all sources of

short-circuit
motors,

current, that is, the generators, synchronous

induction

motors,

subtransient

reactances

motors,

induction

and

and

utility

(Xud) of
motors

are

connections.

The

generators, synchronous
used

in the impedance

diagram.
Procedure

for

consists of calculating
the

breaker

impedance
at

this

divided

determining

momentary

current

E/ZM ' the line to neutral voltage at

by

at that point.

the

equivalent

momentary system

Since the dc component is present

time, it is necessary to account for it by the use

of

multiplying factor as mentioned/ earlier, to find the

first-cycle

short-circuit-current

duty

per-unit

Breaker application (600 volts or above) will be

current.

if

proper

total

E/ZM

times

a factor of 1.6 does not exceed the

momentary current rating of the breaker.

Where

IIC is the

first-cycle

short-circuit asymmetrical

Refer to Appendix 2 (section A2.6) for the Belle

current.

plant momentary short-circuit current calculation.

3.7 INTERRUPTING SHORT CIRCUIT CALCULATION

To
breaker,
the

the

time

required

check the interrupting duty on a power circuit


short-circuit current should be determined at

that the circuit-breaker contacts part.

The time

for the circuit-breaker contacts to part will vary

over a considerable rang, because of variation in relay time


and

in

required

circuit-breaker
for

the
be

operating speed.

circuit-breaker

greater

will

maximum

interrupting

breaker

when

account

for

The fewer cycles

the current to interrupt.


duty

tripping
variation

is

to

contacts

imposed

part, the

Therefore, the

upon

the

circuit

relays operate instantaneously. To


in

the

circuit-breaker

operating

speed, power circuit breakers have been grouped into several


classes,

such

as

eight-cycle, five-cycle, and three-cycle

circuit breakers.
In industrial plants, eight-cycle circuit breakers
are

generally

contribution
motors

has

has

condition
part.

used.

disappeared,

changed

before

Normally,

induction-motor

and that of the synchronous

from the subtransient to the transient

the

Therefore,

the

contacts

of

these circuit breakers

in calculating the interrupting duty on

commonly used power circuit breakers, generator subtransient


reactance and synchronous-motor transient reactance are used
and

unlike

other

methods,

neglected,

induction

This

cause

will

current
safety

motor

which

induction

transient

motors

are

reactance are used.

the calculated interrupting short-circuit

to be higher than the actual value, which creates a


factor

for

selection

of

circuit breakers for the

entire system.
Instead
short-circuit
by

of

specifying

time

at

which

the

current is to be calculated, it is determined

specifying the generator and motors reactances and using

a multiplying factor.

These factors are listed in Table 3.1

The procedure for determining interrupting current


consists of calculating E / Z I ,
the

breaker

impedance
factors

at

to

divided
that

the line to neutral voltage at

by the equivalent interrupting system


point,

determine

and

then

applying multiplying

total current at the time of breaker

29
contact

parting.

This total current is compared with the

breaker total current interrupting rating.


Reactance
1969

for

motors,

values

used

with

ANSI standard C37.5

transformers, generators,

sources are listed in Appendix 1, table Al-1.

and

utility

Table 3.1 Machine Reactance and Multiplying Factors


Used in Simplified calculation of Short-circuit
Duty

[I1

Machine Reactances to Use


Equipmwtt

Type of Short-circuit
Rating

Synchronous
Motors

Induction
Motors

L-V Power Circuit Breakers


L-V Molded-core
Qr#kers

Synchronous
e a t o s

Multiplying Focmr
to be Applied
to Calculated
Syrnmehicoi
Value*

Circuit

L-V Motor Controllers (Incorporaiing Fusesor M o i d d rose Circuit Breakers)

Symmetrical Amperes
Available

Subtransient
(x7

Subtransient

(x?

Subtronsient
(x")

None

L-V Fuses
1-V Buswoy

k s &racing im
L-V Switchgear
1-V Switchboards
L-V Motor-controi Canters
L-V Panelboards

Power Circuif Ereakors


(above 600 volts)
with Rated Interrupting
Times of 8 cydes
(Refer to the Total
Current Rating k r i s ASA C37.6-1964)

Fuses and fused


Cutouts
( o b a e 1500 volts)

General
Caset

Interrupting--Symmetrical
+aperesor MVA
Available

Mocncntary-Asymmetrical
Amperes Available
Interrupting-Asymmetrical
Ampares Available

Subtransient

Transient

(xl)

1x1

Subtmnsient
(x")
Subtransient

(x?

Subtransient
(xl)
Subtransient

(x?

Sp&l
Caret

Noglut
1 .I
Subtmnsient

Subtransient

15$

1.27

CHAPTER FOUR

GENERAL EQUIPMENT USED

We
terms

of

usually

its

more

think

of an electric power system in

impressive

stations, transformers, high


these

are

FOR PROTECTION

parts,

voltage

the big generating


lines,

etc.

While

some of the basic elements, there are many other

necessary

and

fascinating components. Protective relaying

is one of these [ 3 ] .
The
protection
system

function

and

and

of

protective

coordination

its

components

is
and

relaying for system

to minimize damage to the


to

limit

the extent and

duration of service interruption whenever equipment failure,


human

error,

system.
circuit
faulty

or

The

"acts of GOD" occur on any portion of the

relaying

breakers
element

that

when

equipment is aided in this task by


are

they

capable

of

disconnecting the

are called upon to do so by the

relaying equipment.
Overcurrent
coordination

protection

device

selection

and

is an engineering decision that should be made

to protect the system from short-circuit or fault currents.


Protection
as

science

and

for electric systems is an art as well

should

objectives in mind:

be

designed

with

the

following

1) Prevent or minimize damage to equipment.

2) Minimize the effect of the disturbance on the


un-interrupted

portion of the system, both in its extent

and duration.

3) Minimize interruption of power.


4) minimize the effect on the utility system [4].

5) prevent injury to personnel.


The
application
abnormal
the

isolation

of

protective

current

system.

of

short

circuits

equipment

which

requires

the

will sense an

flow and remove the affected portion from

The sensing device and interrupting device may

be completely separate, interconnected only through external


control

wiring,

or they may be the same device or separate

devices mechanically coupled to function as a single device.


Equipments

used

for

protection

fuses, and circuit breakers.

are

overvurrent

relays,

The following sections explain

each of these devices in detail.

4.1

OVERCURRENT RELAYS

Overcurrent
must

be

relays

are

sensing devices only and

used in conjunction with some type of interrupting

device to interrupt a short circuit and isolate the affected


portion

of

the

system.

These

relays

may

directional or non directional in their action.

be

either

They may be

33
instantaneous
current
time,

or

time

delay

in

response.

Various time

characteristics, such as inverse time, very inverse

extremely inverse time, and definite minimum time are

available

over

overcurrent

wide

range

of

current

setting.

The

relays are generally available in the following

current ratings:
Range
0.5-2.5

0.5,0.6,0.8,1.2,1.5,2.0,2.0,2.5

1.5-6.0

1.5,2.0,2.5,3.0,3.5,4.0,6.0

4.0-16.0

4.0,5.0,6.0,7.0,8.0,10,12,16

The
or

Taps

double

relays can be specified to have either single

circuit closing contacts for tripping either one

or two circuit breakers.


Directional
overcurrent

relay

consists

of

two

element and a directional element.

units,

an

The contact

circuits are arranged insuch a way that tripping occurs only


when
power
of

current
flow

the

element,
current

has

proper

relationship to the voltage with

in the tripping direction.

circuit

is

done

The actual tripping

by. a contact on the overcurrent

the overcurrent element does not operate until the


is flowing in the proper direction and is above the

pickup setting.

The overcurrent element cannot operate on a

fault in the nontripping direction. For typical application


refer to Appendix 5 (section A5.3)
The

instantaneous

device No.67 (CWC type) .

element

is

set for a current

34
higher

than

element.
in

should

operate

the

time-delay

with the contacts of the time-delay element or

aconnected

mainly

which

The contacts ot this element are either connected

parallel

they

that

used

to

seperate

when

time

terminals.

interval

This element is

required

between

two

overcurrent relays can not be made in the short time region.


Refer

to

Appendix

(section

A5.12)

for

instantaneous

setting used in portion of the Belle plant.


The
relays

time-current characteristics for a variety of


in this report are shown in Appendix 6. These

used

characteristics
various
tap

time

give

the

contact

closing

times

for the

dial settings when the indicated multiples of

current are applied to the relay.

In Chapter 5 several

method .of coordination for these relays will be discussed.

4.2

FUSES

Fuses
protective

are

the

devices.

oldest

The

fuse

and

is

both

simplest

of

all

the sensing and

interrupting

device.

They are installed in series with the

circuit

operate

by

and

the

melting of a fusible link in

response to the current flow through them on an inverse time


current
fusible

basis.
elements

interrupting

the

They

are

are
current

one-shot

destroyed
flow.

devices
in

the

since their
process

of

Fuses may have only the

ability

to

maximum

rating

short

interrupt

circuit

or

short

the

current

circuit

ability
by

current

up to their

to limit the magnitude of

interrupting

the

current flow

before it reaches its maximum value.


As
compared.
example,

shown in table 4.1, several types of fuses are


Each

fuse has a different characteristic. For

code-type fuses are not recommended because of low

interrupting

and high melting current (70 times

capability

fuse rated current) at 0.01 second. Current limiting Amptrap


fuses have high interrupting capability and very low melting
current
These

(3.3

fuses

should

not

times

fuse

rated

current)

at 0.01 second.

are mainly recommended for branch circuits and


be

used for protection of transformers.

Since

transformers have an inrush current (sometimes 12 times full


load

current).

This

type

transformer is energized.
is

the

best

of fuses will melt before the

Chase Shawmut (C-S) one-time fuse

choice for most applications because of their

low cost and ratings.

Table 4 . 1

Fuse Classification

Melting current

Interrupting

Average multiples

capability

of rating amperes

Code fuse (NEC)

melt in

melt in

0.01 s

10 s

70

30

3.5

25

amperes

3,000

Semi lag fuse

Rowan AIR-SEAL

one time
dual element fuse

C-S new "trionicn

1 Current

50,000

50)000

30

20

45

5.5

10%
;;;

15

2.5

100, 000

13

2.5

100 ,000

12

100 000

3.3

100,000

1OO)OOO

limiting

"Amptrap 60011
"Limitron"
G.E. "CLF-J"

I
I

Solid state
current limitin

,
I
I

37
COST

OF FUSES [51
Approximate

costs

of

fuse

types,

for

given,

amperage, relative to NEC type are.

NEC fuse
C-S one time
Rowan air seal

C-S trionic
Fusetron
Lo-peak
Current Limiting

Semi

lag and dual element fuses of smaller size than NEC

size may be applicable, with proportionaly reduced cost.

On

this basis, the Chase-Sha~ut(C-S) one-time fuse appears the


optimum

for

all uses within its interrupting capability of

50,000 amperes.

CURRENT LIMITING CHARACTERISTICS OF C-S ONE TIME FUSES


(C-S)

Chase-Shawmut
limiting,
time

fuse

Amptrap.

but
is

not
about

Table

so

one-time

much as Amptraps.

as

current

fuses

are current

A 30-ampere one-

limiting

as a 60-ampere

4.4 shows the comparison of Chase-Shawmut

one-time fuses and Amptrap fuses.

Table 4 . 2 C-S one time fuses vs Amptrap fuses

Let- through current

Available current
(

RMS

(thousands of amperes peak AMPTRAP)

amperes

(Amptrap fuse rating)

7.8

50,000

11

---

--- -"- - - -

16
--

24

35

-- ----

(C-S) ONE-TIME fuse rating:

--

Fuses,

and

their characteristics which have been

used in this study is shown in Appendix 6.

4.3

CIRCUIT BREAKERS

Circuit breakers are interrupting devices only and


must
the

be used in conjunction with sensing devices to fulfill


detection

function.

In

the

case of medium-voltage

39
(1-72.5 KV)
separate

circuit

breakers,

protective

relays

the

sensing

devices

are

or combinations of relays.

In

the case of low voltage (under 1000 volts) circuit breakers,


sensing

devices

combination
either

of

may

external

breakers

protective

relays

or

In most low voltage application,

relays.

molded-case

circuit

be

circuit
having

breakers

or other low voltage

series sensing devices built into

the equipment are used.


The

ratings

which

apply to circuit breakers and

the actual assigned numerical values reflect the mechanical,


electrical,

and

thermal

capabilities

of

their

major

components. Basic ratings are

1)

Rared voltage

2)

Rated frequency

3)

Rated continuous current

4) Rated interrupting current


5)

Rated short-time current


The

basic

overcurrent trip device characteristic

used on molded-case circuit breakers and low voltage circuit


breakers

are

combination
tripping
that

long-time

of

for

these
those

persist,

and

delay

and

instantaneous.

characteristics
low-level

The

provides time delay

short circuits or overloads

instantaneous tripping for higher level

short circuits.
New molded-case circuit breakers are equipped with

40
a

short-time-delay

instantaneous

characteristic

characteristic.

long-time-delay

and

provides

tripping

delayed

maximum

allowable

in

place

of

the

The resulting combination of

short-time-delay

characteristics

for all levels of current up to

available short-circuit-current limit of

the circuit breaker without instantaneous trip element.


These
so

that

system

better

without

breakers are used for the Belle plant,

protection

can be obtained throughout the

using instantaneous trip element.

(section

which

shows

Appendix
curve,

new

A6.7)

for

Refer to

the device characteristic

available settings for long-time-delay

and short-time-delay pickup values.

4.4 GENERATOR PROTECTION

The

protection

of

generators

involves

the

consideration of more possible abnormal operating conditions


than

the

protection

unnecessary
not

try

of

any

other

system

element.

An

generator outage is undesirable, but one should

to avoid it by the omission of otherwise desirable

automatic protection.
The

practice

of

using

centralized

control

is

increasing, which requires more automatic equipment and less


manual

supervision.

Such practice requires more automatic

protective relaying equipment to provide the protection that

41
was formerly the responsibility of attendants [ 3 ] .
The
generator
settings

following

Refer to Appendix 3 for the type and

protection.
of

protective relays are used for the

protective

relays

used

for

the Belle plant

generator protection.

PERCENTAGE DIFFERENTIAL RELAYS


These

relays

KVA or higher [ 3 ] .
best

for

the

used for generators rated 1000

are

Percentage differential relaying is the

short-circuit protection of stator windings,

because of its high-speed instantaneous capability.


Generally,

the

practice

percentage-differential

relays

multicontact

relay.

,auxiliary

simultaneously

(2)

breaker,
mover

initiates
trip

field

(4) operate

and

the

is
trip
This

to

have

hand-reset

auxiliary

following:

(1)

trip

the

relay
main

breaker, (3) shut down the prime

an

alarm.

These will result in

minimizing damages to the generator.

SOLID STATE UNDER-FREQUENCY RELAYS


These relays are used for automatic load-shedding.
When

system overload occurs, under-frequency relays must

disconnect

load to arrest frequency decline.

generating

plants

may

be

impaired

below

The output of
57-57.5

Hz, so

shedding must be completed before this level is reached.

OVER-VOLTAGE

RELAYS

This type of relays are used for hydroelectric and


gas-turbine

generators.

additional
Then

if

It

operates

by

first

causing

resistance

into the generator or exciter field.

over-voltage

persists, the main generator breaker

trips.

OVER-TEMPERATURE RELAYS
Unbalanced

three-phase

double-system-frequency
iron.
cause

stator

currents

cause

currents to be induced in the rotor

These current quickly increase rotor temperature and


serious

operate

with

damage
such

to

the generator if it continues to

conditions.

These relays will prevent

generators from overheating.

LOSS-OF-EXCITATION
When
operates

as

synchronous

RELAYS

a synchronous generator loses excitation, it


an

induction

generator,

running

above

speed. Round-rotor generators are not suited to

such operation because they do not have amortisseur windings


that can carry the induced rotor currents.
Most
operation
the

of

systems
a

cannot

tolerate

the

generator without excitation.

continued

In fact, if

generator is not disconnected immediately when it loses

43
excitation, widespread instability may very quickly develop,
and

major

loses

system

excitation,

shutdown may occur.

When a generator

it draws reactive power from the system,

to as much as 4 times the generator's rated load.

amounting
This

will

cause

most

selective

extensive instability in the system.

type

of

loss

of

excitation

relay

The
is a

directional-distance type operating from the a-c current and


voltage at the main generator terminals [ 3 ] .

REVERSE POWER RELAYS


These

relays

are

used

to

detect

motoring.

Motoring protection is for the benefit of the prime mover or


the

system,

considered

and

here,

not

for

the

generator.

However, it is

because it is closely associated with the

generator.

FIELD GROUND-FAULT PROTECTION RELAYS


Because
single

field circuits are operated ungrounded, a

ground fault will not cause any damage or affect the

operation of a generator in any way.


of

However, the existence

single ground fault increases the stress to ground at

other

points in the field winding when voltages are induced

in the field by stator transients.

Thus, the probability of

a second ground occuring is increased.

44
Note: refer to Appendix 3 for the types and settings used
for protection of the Belle plant generator.

4.5 TRANSFORMER PROTECTION

The

function

of

protect the transformer.


to

automatically

transformer

protection

is

to

Transformer protection is required

disconnect

transformer from the power

system for any of the following reasons.

1)

To

prevent

developing
current

higher-than-rated

in

and,

insulation

the

transformer

thereby,

or

temperatures

causing

conductors.

from

excessive

from
load

rapid deterioration of

Protection

provided

to.

achieve this is known as overload protection.

2)

To

prevent

mechanical

and

thermal

effects

of large

"through" currents from causing permanent deformation or


other

damage

to

the

transformer.

Such protection is

known as short-circuit protection.

3)

To

minimize

transformer,

the
and

spread

of

minimize

damage

inside

power-system

a faulted

disturbance

resulting from transformer faults.

TRANSFORMER SHORT CIRCUIT CAPABILITIES


The
short-circuit

ability of a transformer to withstand through


current is defined as its "ANSI point".

This

45

point

specifies

the

magnitude

and

duration

of

maximum

permissable through current that a transformer can withstand


without sustaining damage.
Values
rated

full-load

of

ANSI point vary from 25 times the

the

current

for

2 seconds, for a transformer

with four percent or less impedance, to 1 4 . 3 times the rated


full load current for 5 seconds, for transformers with seven
percent

impedance

protect

the

as

shown

in

transformer, the

4.5.

table

primary

To properly

fuse must actually

clear

in the stated time at 87 percent of the current value

of

delta-delta

bank,

and

58 percent of the value of a

delta-wye bank.

Table 4.3 Transformer ANSI data


% Z

Irms (sym)

SYM.
rms

58% I

Fault PH-PH

FAULT

Delta-Delta

Delta-Wye

4% or

25 X Rated

22 X Rated

less

Current

Current

L-N

14 X Rated

11 X Rated

Current

Current

Current

16.6

X Rated

X Rated

Current

14

X Rated

9 X Rated

Current

12 X Rated
Current

TIME(s)
Allowable

Current

17 X Rated

7% or 1 4 . 3

more

SYM.
rms

20 X Rated

Current

87% I

Current
8

X Rated
Current

TRANSFORMER INRUSH CURRENT

A power transformer primary power fuse, as well as


any other protective device used in a transformer protection
scheme,

must

actuating

allow the transformer to be energized without

the

protective

device on the magnetizing inrush

current.
The
current

precise

vary

transformer,

Commonly

used

duration

of

inrush

can

only

be

determined

by

test.

estimates of magnetizing inrush currents for

and secondary substation transformers range from an

equivalent
duration
should

and

from one transformer to another, and, for any

specific

primary

magnitude

of

8 to 12 times full load rms current, with a

of 0.1 second.

The power or current-limiting fuse

be selected so to be capable of carrying at least 12

times the full-load rated primary current of the transformer


for

0.1 second, without damaging the fuse, in order to pass

safely

the

inrush

currents

which

occur during switching

operations.
Refer to Appendix 4 for tranformer protection used
throughout the Belle plant.

FIVE

CHAPTER

COORDINATION OF PROTECTIVE DEVICES

The coordination study of an electric power system


consists
in

of

series

study

an organized time-current study of all devices


from the utilization device to the source.

is

This

comparison of the time it takes the individual

devices to operate when certain levels of normal or abnormal


current pass through the protective devices.

A
study
are

coordination

should
added

replaced

be

to

study

or

revision of a provious

made for an existing plant when new loads

the

system

or

when

with higher rated equipment.

existing equipment is

A coordination study

should also be made when the available short-circuit current


of

the

source

determines

to

plant

settings

or

is

increased.

ratings

This

necessary

to

study
assure

coordination after system changes have been made.


The
determine

the

overcurrent

objective

of

coordination

characteristics, ratings,

protective

devices

is

to

settings of

which will ensure that the

minimum

unfaulted

devices

isolate a fault or overload anywhere in the system.

At

same

the

provide

load

and

study

time,

satisfactory

is interrupted when the protective

the devices and settings selected must


protection

against

overloads on the

48
equipment,

and

interrupt

short

circuits

as

rapidly

as

possible.

5.1

PRIMARY CONSIDERATIONS FOR COORDINATION

In
protective

order

to

obtain complete coordination of the

equipment applied, it is necessary to obtain all

of the following requirements.

SHORT-CIRCUIT CURRENTS
The

following

information

on

short-circuit

currents should be provided for every bus on the system.


(1)

Maximum and minimum 0 to 3 cycle (momentary) total


rms short-circuit current

(2)

and minimum 3 cycle to 1 s (interrupting duty)

Maximum

total rms short-circuit current


These short-circuit current values are obtained as
described in Chapter Three.
The

maximum

currents

are

used

currents

to

which

devices

respond,

to

and minimum 0 to 3 cycle (momentary)


determine

the

maximum and minimum

instantaneous

and

direct-acting

and

to

trip

verify the capability of circuit

breakers, fuses, switches, and bus bracings.


The
at

maximum

maximum 3 cycle to 1 s (interrupting) current

generation

will

verify the ratings of circuit

49
breakers,

fuses,

current

at

interval

is

which

cables.
the

current

This is also the value of

circuit

established.

(interruptig)
determine

and

The

at

protection
maximum

minimum

coordination
to 1 s

cycle

generation is needed to

whether the circuit-protection sensitivity of the

circuits is adequate.

TIME INTERVALS FOR COORDINATION


When
intervals

must

protective

of

coordination

curves, certain time

be maintained between the curves of various

devices

operation
because

plotting

the

relays

in

order

devices.
have

to ensure correct sequential


These intervals are required

overtravel,

fuses

have

damage

characteristics, and circuit breakers have certain speeds of


operation.

These intervals are often called margins.

When coordihating inverse-time overcurrent relays,


the

time

interval

interval
is

instantaneous

is

usually

0.3-0.4 seconds [ 6 ] .

This

considered between relay curves, either at the


setting

of

the

load

side

feeder

circuit

breaker relay, or at the maximum short circuit current which


can

flow

the

lower

through both devices simultaneously, whichever is


value

of current.

The interval consists of the

following components:
Circuit breaker opening time (5 cycles)

.08 seconds

Overtravel

.10 seconds

50

.12-.22

Safety factor
This
relays

and

is

with

inverse
somewhat

decrease

0.3

may

be

decreased if field tests of

circuit breakers indicate that the system still

coordinates
very

margin

seconds

in

the decreased margins.

The overtravel of

and extremely inverse time overcurrent relays


less

than

time

interval for carefully tested systems to

0.3

seconds.

for

Seconds

inverse

time

relays,

interval

allowing

is

used

for

coordination of the Belle plant overcurrent relays.


When
trip

units

circuit breakers equipped with direct-acting

are

coordinated with relayed circuit breakers,

the coordination time interval should be 0.3-.4 s.

HOW TO READ CURVES

basic

characteristic

is

considered

the

times

as

shown

on

understanding

essential

to

any

of
study.

time-current
Time

0 is

time at which the fault occurs, and all

the

curve

are the elapsed time from that

point.

The curves that are drawn are response times, since,

for

radial system, all the devices between the fault and

the

source

experience

the

same current until one of them

interrupts the circuit.

coordination

curve

is

arranged

so

that the

region below and to the left of the curve represents an area


of

no

operation.

The curves represent a locus of a family

UJ.

of

paired

coordinates

which indicate how long a period of

time is required for device operation at a selected value of


current.
Reading
range

of

times

corresponds
plotted.

to

current

along

the abscissa, the time or

in which any device is expected to operate


the

ordinate

or

ordinates

of

the curve

Relay curves begin at a point called "pickup" (the

minimum value of current which will cause the relay to close


its

contacts)

and end at the maximum short-circuit current

to which the device under consideration can be subjected.


single

curve

should

be

drawn

for

any

device

under

consideration.

5.2

DATA REQUIRED FOR A COORDINATION

The

first requisite for a coordination study is a

single-line diagram of the system.

This diagram should show

the following data.

11

Apparent

power

and

voltage

ratings

as well as the

impedance and connections of all transformers

2)

Nameplate

ratings

and

subtransient

reactance

of all

major motors and generators

3)

Conductor sizes, types, and configurations

4) Current transformer ratios


5)

Relay,

direct-acting

trip,

and

fuse

ratings,

52
characteristics, and ranges of adjustment
Refer
plant

to

Appendix 2 (section A2.4) for the Belle

single-line

diagram,

which

includes

the

above

information.
The

second

circuit-current

requirement

study

is

complete

short-

as described earlier in this Chapter

and also in Chapter Three.


The

third

characteristics
for

the

new

and

requirement

is

the

time-current

typical time curve (this curve is used

method of coordination in this report) of all

the devices under consideration.


The

forth

requirement

is

starting currents and

accelerating time of large motors.


.

Once

this

to

select

necessary
perform
pieces

their
of

information
the

assigned

equipment

is .assembled, it is then

protective
function

and

devices so that they

of protecting individual

operate so that only the minimum

amount of circuitry associated with the fault is isolated.

5.3 METHODS OF COORDINATION

There
coordination
system

are

several

available

abnormalities

utilization

to
on

methods

minimize
the

of overcurrent relay
the

system

effects

itself

equipment which it supplies.

or

of such
on

the

These methods are

as follows.

1)

Coordination by table

2)

Use of device characteristic curve

3)

Use

of

typical

time

curve

of

device

(new

method

presented in this report)


The following section will explain these method in
detail with some examples.

METHOD ONE COORDINATION BY TABLE


This

method

mainly

uses

fuse as the protective

device for the coordination of the system.


In
through
shows

fuse

the
a

use

applications,
of

typical

combinations

selectivity
selectivity

of fuses.
of

coordination

class

and

type

check

for

selectivity

is achieved

ratio tables.
schedule

for

Table 5.1
various

This schedule is limited to several

fuses.

This table is used as a simple

assuming

that identical or reduced

fault currents flow through the circuits in desending order,


that

is,

main-feeder-branch.

A coordination study may be

desired when the simple check as outlined is not sufficient,


and

can

be

accomplished

by

plotting

fuse

time-current

characteristic curves on log-log graph paper.


For

100 A

example,

current

when the largest branch device is a

limiting fuse, the main fuse may be a 200

Arnptrap or 100 A dual-element or one-time fuse.

54
5.2 shows

Table
branch

or

protective
in

main

or

coordination

device

and

main

between
or

the

supply

when a power air circuit breaker is used

supply

circuit.

For example, for a current

fuse used in branch or load circuit, a multiple of

times

percent
should

protective

device

limiting
2.5

load

the

ratio of 80 percent long time pickup to 500

the

short
be

time

used

1.25 when

pickup

of

power

air circuit breaker

for proper coordination.

the

ratio

This multiple is

of 160 percent long time pickup over

1000 percent short time pickup is used.


Some

of

the basic rules of coordination for this

method are [6]:

1) Branch fuse-clearing time must be less than the melt time


of

the

main

clearing
not

fuse.

That means under the total maximum

I2 t of the largest fuse on the load side should


90 percent of the melting I2 t of the supply

exceed

side fuse.

I2 t values must be used to check coordination

in the current-limiting range. Below the current-limiting


range

time/current

the

compared

as

follows:

(1)

add

curves

may

be

10 percent to the curve

for the downstream fuse, (2) subtract 10

current

values

percent

from

fuse.

The

percent

current

the

characteristic

the

curve current values for the upstream

resulting curves should allow at least a 10

downstream

margin between the two fuses based upon


fuse.

The result is a minimum fuse size

55

s p r e a d w h i c h s h o u l d c o o r d i n a t e w i t h o u t damage t o u p s t r e a m
fuse.

More s p r e a d w i l l o f c o u r s e i n c r e a s e a s s u r a n c e o f

coordination.
2)

Branch

device

clearing

sensing time of a breaker.

time

m u s t be u n d e r 80% o f t h e

Table 5.1 Rating Ratios for Safe Coordination

Branch or

load device

Main or supply device


(minimum multiple of branch device)

current limiting, dual element, semi lag,c-s


Amptrap,limitron, trionic and

one-time and

Table 5.2 Power air circuit breaker


Minimum band
Main or supply device

Branch or load

(minimum multiple of branch device)

device

80% long time pickup

160%long time pickup

500% short time pickup 1000% short time pickuq

b
.

-- --

ratio

-- -- -" --

--

----

--.-----

ratio

1b2r-

current lim.

2.5

dual element

5.0

C-S one time

5.0

2.5

10.0

5.0

NEC

Molded case
air circuit
breaker
50 A

4.0

2.0

100 A

5.0

2.5

100 A

7.0

3.5

225 A

4.0

2.0

600 A

3.0

1.5

(heavy duty)

58

METHOD TWO USING DEVICE CHARACTERISTIC CURVES


In
and

order to start drawing curves, a voltage level

multiple scale current in ampere should be selected and

marked

on

the

bottom

of

the log-log paper.

Then proper

multipliers for the various voltage levels considered in the


study

are

curves

calculated.

protective

device characteristic

are then placed on a smooth bright surface such as a

window pane, or a glassed-topped box with a lamp in it.


sheet

of

placed
current

log-log paper on which the study is being made is

on

top

of

the

device

characteristic

curve, the

scale of the study lined up with that of the device

characteristic.
ratings

The

of

The curves for all the various setting and

devices

being

studied

may

then be traced or

examined [4].

METHOD THREE USING DEVICE TYPICAL TIME CURVES


This

method

present

new

way

of

drawing

co-ordination curves which has been practiced throughout the


Belle
for
of

plant coordination study.

This method is recommended

more accurate protective relaying coordination. Instead


device

overcurrent
time

characteristic
relays

versus

curve,

Typical

used in this method.

multiples

overcurrent

relay

has

settings.

Knowing

the

of

tap

several
amount

of

curves of

These curves show

value

tap

time

value

current.
and

Each

time dial

maximum short circuit

59
current

and

dividing

current

several

transformer

values

ratio

is essential.

By

of short circuit currents to c.t.

ratio and the tap value, several multiples of tap values can
be found.

Refering to the curve time for these multiples of

tap value can be found depending upon what time dial setting
have

been selected.

At this time the short circuit current

and the time for several points are known.

These points are

then

ploted

Now let's assume

that

an overcurrent relay at a different voltage level must

and traced on log-log paper.

be

coordinated

of

0.3

with this relay.

The minimum interval time

seconds must be allowed between the two relays.

In

order to illustrate this method of coordination and decision


making,

portion of Belle plant detailed relaying diagram

is

shown as an example in figure 4.2 and the related curves

are

shown in figure 4.3. Figure 4.1 shows the typical time

curves

CO-9

of

overcurrent

relay.

The following example

illustrates this new method.

EXAMPLE :
Figure
overcurrent
relays
need

detailed

involved

in

coordination

overcurrent
the

4.2 shows

relay.

portion

drawing.

of the Belle plant

There are two overcurrent

this portion of the system, which will

with

the

incoming power company feeder

Let's assume that fault A happened on

syst'em. in order to isolate the fault from spreading to

other

portions

of the system, unit 2A breaker must operate

first

so

only

circuit
operate.

that

is

not

feeder

cleared

2A

yet,

shuts down.

If the short

then bank No.1 primary must

Finally if the short circuit is still not cleared,

then power company No.2 primary feeder must operate.


Figure

4.3 shows the CO-9 type overcurrent relay

curves that was selected and ploted for maximum protection


of

this portion of the system. Following data are required

for the selection of these curves.


No.2 primary feeder overcurrent relay data
Circuit: Bank No.1 primary
Relay type: Westinghouse CO-9
C.T. ratio: 200/5=40/1
Available Taps=1.0,1.2,1.5,2.0,2.5,3.0,3.5~4.0,5.0,6
7.0,8.0,10.0,12.0
Ampere range of relay=l-12
Circuit voltage: 46 kV level
Maximum

available

short

circuit

Unit 2A overcurrent relay data


Circuit: Unit 2A
Relay type: Westinghouse CO-9
C.T. ratio: 800/5=160/1
Available taps= same as relay No.1
Ampere range of relay=l-12
Circuit voltage: 12 kV level

at 46 kV level: 14,300 A

61
Maximum available short circuit at 12 kV level: 19,400 A
Since Bank No.1 is upstream in the system relative
to

Unit 2A, its overcurrent relay should be drawn first and

then unit 2A overcurrent curve should be drawn to coordinate


with that.
Relay No.1 settings
C.T.=200/5=40/1
Let's

select

the

following

setting

to

see

if

proper

coordination can be obtained.


Selected tap=12
Selected time lever=lO
Selected multiple current=lO
Selected voltage level=46kV
Multiple of tap value=(short-circuit
current) / (tap) (C.T.ratio)
Pickup* value= (tap) (C.T. ratio)
*Pickup

is

the minimum value of the current that can start

the relay to close its contact.


Point No. 1: 14,300 A /(12) (40)=29 off scale on figure 4.1
Point No.2 : 9,000A

/ (12) (40)=18.75

multiple of tap value

For this value and time lever of 10, time will


be equal to 1.2 seconds from figure 4.1.
Point No.3 : 7,000 A

/ (12) (40)=14.6 then time=l .3 seconds

Point No.4: 5,000 A

/ (12) (40)=10.4 then time=l .5 seconds

Pickup value= (12) (40)=480 A

62
These

points should be plotted and traced for the

relay curve as shown on figure 4.3 (curve number 1).


Relay No.2 settings
C.T.=800/5=160/1
Let's

select

the

following

setting,

so

that

proper

coordination can be obtained with the upstream relay.


Selected tap=7
Selected time lever=7
Selected multiple current=lO
Selected voltage level=12 kV
Maximum available short circuit at 12 kV=19,400 A
(19,400) (12 kV) / (46 kV) =5,060 A at 46 kV level
Point No. 1 : 5060/ (7)(160)=4.5 at 46 kV level
For this value and time lever of 7, time=2.1 s
Point No.2 : 4000/(7)(160) =3.57 then time=3.0 s
Point No.3: 3500/ (7)(160) =3.12 then time=3.9 s
Pickup value=(7) (160) (12 kV) / (46 kV)=292

A at 46 kV level

These points also should be plotted on figure 4.3.

As

shown

operate
before

unit

first
Bank

overcurrent relay (curve number 7) will

2A
in

case of a fault and will clear the fault

No.1. primary

relay

operates, since there is

about

0.6 second time interval allowed between the curves.

Both

relay

operation

were

based

tested
on

and

field

checked

for

proper

the method recommended on section 4.7.

OVER C U R R E Y T R E L A Y
5 0 - 6 0 tiERTZ

V)

a
2

S
W
Y,

MULTIPLES O F TAP VALUE CURREHT

F i g u r e 5 . 1 T y p i c a l t i m e c u r v e s of t y p e CO-9

Relay [7]

I2KV

B U S '0"

--

--*-a3;7
--

Figure 5.2 Portion of Belle plant Detailed Relaying Diagram

Figure 5.3 Portion of Belle plant Coordination curves

OF PROTECTIVE DEVICES

5.4 TESTING

This requires that the system or protective device


be

subjected

operation

to

of

abnormal
the

electrical

system

or

conditions

devices

and the

compared

to

manufacturers' specifications for these conditions.

MOLDED CASE CIRCUIT BREAKERS


In

testing a molded-case circuit breaker, several

points must be remembered.

1) Nameplate rated voltage must be available at the input


terminals throughout the test.

2)

The

values

therefore

of

it

current

are

high

and voltage is low,

is.advisable to use connections having the

shortest possible length and largest,.cross sectional area


between

test

unit

and circuit breaker..

In some cases,

pieces of bus bar may be used for these connectors.

3) The connection to the circuit breaker must be tight.


4) The circuit breaker tested one pole at a time.

5)

Trip

devices

must

be

allowed

to

fully reset before

performing a check test.


Molded-case

(1)

timing

values
trip

of
unit

and
test

circuit

breaker should be tested for

(2) instantaneous pickup.

The recommended

current is three times the circuit breaker

rating.

The tripping time must be measured and

compared to the manufacturer's specified values or curves.

Molded-case
precise;

however,

indicates

circuit

the

wide

breakers

may

be relatively

published time-delay characteristic

band

of operation.

The electrical test

will

reveal circuit breakers that will not trip, those that

take

abnormally

delay.

If

tripping

within

limits

of

affect

the

circuit

long

the

to trip, and those that have no time

test

reveals that the circuit breaker is

plus

or

minus

15 percent of the outside

its published curves and this tolerance does not


electric

system coordination or stability, the

breaker should be considered satisfactory otherwise

should be rejected.

An electrical test for pickup of the instantaneous


unit

should

tripping

be

will

to verify that the circuit breaker is

magnetically.

calibration
set

run

marks

is

Testing

at

satisfactory.

one

of

the

lower

The adjustment may be

to the lowest calibration point to verify that the unit


pick

If the instantaneous unit picks up at the

up.

minimum calibration point, then pickup will be assumed to be


within manufacturer's tolerances.

LOW-VOLTAGE

POWER CIRCUIT BREAKl3R [6]

Most
one

series

electrical
The

of

these circuit breakers are equipped with

overcurrent

trip

device

per

phase.

The

test must be run on each individual trip device.

operation

of

any

one

of these devices will trip all

68

poles of the circuit breaker.


The
circuit

recommended

for

low-voltage

power

are (1) timing (long-and short-time delay

breakers

units if the

test

circuit breaker has both type trip units), and

(2) instantaneous pickup.


The
time

delay

is

short-time
breaker

recommended
three

delay

operate

it

is one and one-half times the circuit


delay

pickup.

within

of test current for long

times the trip unit setting, and for

short-time

instantaneous

values

the

If

setting;
the

circuit

determine

the

breaker does not

tolerances shown by the manufacturers'

time current curves, then suitable adjustment should be made


as recommended by the manufacturer.

PROTECTIVE RELAYS
The

protective relay is the brain of the electric

protective circuit.

It is the relay that senses an abnormal

condition and then sends the message to other devices on the


system.

Therefore it is imperative that any relay work be

done in a very through manner.

timing

should

relay

closes

given

abnormal value of current.

with

the

its

check

relay

contacts

tap

in

be

within

its

made to see that the


a specified time for a

Normally this test is run

designated

position.

It is

suggested that a test current of four times pickup be used.

69
Based
equipment

on

used

above

in

the

methods

all

the

protective

Belle plant were field-checked and

tested for proper operation and coordination for the entire


system.

The 12 kV molded-case circuit breakers were tested

as follow:

Minimum pickup long time delay (LTD)


pickup was checked by applying 10 percent

Minimum
less

than

pickup

current for 10 minutes.

The breaker did

not trip.
Time delay (LTD)

100 Percent pickup value was selected and applied


to

the

relay.

tripped.

The

The

time

was measured until the breaker

time measured was within the shaded area of

the characteristic curve for the test current used.

Minimum pickup short time delay

LTD was

The
the

breaker.

operate

The

button

increased.

blocked to be sure it does not trip

breaker

was

(STD)

pushed

was closed and set to zero. The


and test current gradually was

The current at which the STD armature starts to

close is the minimum pickup.

All

the overcurrent protective relays were tested

for proper operation as follow:

Zero adjust test


This
close

when

test

the

is

dial

to

determine

that relay contacts

is set at zero.

With the continuity

light connected across the terminals, time dial was manually


turned

until

the

indicator

light on the test set glowed.

The reading was at zero.

Pickup test
This
current

test

needed

is

to

close

particular

tap setting.

test,

equal

was

alternately

to determine the minimum operating

tap

increase

the

relay

contacts

for

any

The pickup value selected for this

value

plus

or minus 5 percent.

By

and decrease current, the point where

continuity indicating light flickers was found and recorded.


This

flickering

making
were

and

higher

indicates

breaking.
than

that

the

contacts

are "just"

The recorded values in some relays

tap value, the spiral-spring tension was

too great and was adjusted for the correct tap value.

Time current characteristics

A
relay

timing

check

should

be

made to see that the

closes its contacts within a specified time for given

values
minimum

of

current.

Three times tap value was used as the

amount of test current for the timing check.

Timer

selector

switch

initiate

push

button

vernier

controls

current

through

was

changed

pointer
Then

the

button
coil

was

and

to
set

timer

was

was

put

in "N.O.MOMENTARYtt
position, the

was

jogged

by

using

the main and

and adjust the test unit to pass the test


the relay coil.

The timer selector switch

"N.O.MAINTAIN1'and the main ammeter preset


to
was

pressed.

value just under the test current.

reset

to

zero and the initiate push

This puts test current on the relay

starts the timer.

When relay contacts close, the

timer will stop and current will be removed from relay.


test

The

current and time were compared with 3 times tap value.

Some relay operating were too fast and the time dial setting
was increased up to 1/2 division.

CHAPTER S I X

CONCLUSIONS

This

report

has

short-circuit-current
coordination
relays

for

quick
and

isolation

recommended

for

many

computer

of

and

the

medium-voltage

systems.

contain

calculations

new

method

of

by using typical time curves of the protective

low-voltage
power

illustrated methods of longhand

affected

industrial

portion of

and commercial

The method of longhand calculation is not


large

closed

technique

power

loops.
is

systems,

since these plants

Network analyzer or digital

favorable from an economic and time

saving standpoint for these systems.

As

a result of the study done for the Belle plant

electrical

short-circuit-current

coordination

of

example

this

for

480-volt

protective

feeder

interrupting

devices

report;

show

breakers

ratings.

calculation
which

that

have

was used as an

, 12-kV, 2.4-kV, and

adequate

Short-circuit

and

momentary

duties

of

and

the air

circuit breakers installed at the purchased-power substation


should
ratings
the

be

reviewed again for proper operation and adequate

when

12-kV

transformer

significant

load is to be added, that time,

bus tie breakers could be opened.


would

supply

each

12-kV

Then only one

and

worst-case

73
symmetrical

interrupting
250-MVA.

approximately
to

the

system,

duty

would

be

reduced

to

This will minimize potential damage

its

components,

and

the

utilization

equipment it supplies.
Based
calculated
were

on the values of the short-circuit-currents

for

selected

isolation

of

the

Belle plant, proper protective devices

and coordinated for the detection and prompt


the affected portion of the system whenever a

short-circuit

occurs

in the system.

The recommended relay

settings associated with these devices were field-tested for


proper operation based on the method of testing mentioned in
section 4.7.
This
industrial

plant

application
planning

report

be a good reference manual for

engineers, electricians, industrial power

engineers
of

will

and others who are involved with the

electrical

facilities

for

low-voltage

medium-voltage industrial plants or commercial buildings.

and

BIBLIOGRAPHY

System
division.

engineering
"Short

industrial

and

apparatus

distribution

circuit

current

commercial

power

sales

calculations

system^,'^

for

General

Electric Co., September 1978.


Beeman.

Donald

"Industrial Power Systems Handbook,"

McGraw-Hill Book Company, Inc.

C. Mason. "The art and science of protective

Russell

3.

New York, N.Y. 1955.

relaying," Schenectady, N.Y.: John Wiley & Sons, Inc.,


1956.

4.

F.A.Leinberger. !!Relay co-ordination procedures for an


imaginary

medium

Electric Co.

5.

size

industrial

plant,"

General

Philadelphia, PA. 19102.

R.H.Lee.

"Methods and materials for co-ordination of

fault Memo 12-43," E.I.Dupont Co. Wilmington, Delaware.


6.

D.Dalasta, Norman peach, R.H.Kaufman and W.A.Weddendorf.


It

IEEE

recommended

co-ordination
system,"

of

practice

for

industrial

and

protection
commercial

and
power

IEEE John Wiley and Sons, 1975.

- )

7. Relay instrument division.

If

Type CO (Hi Lo) overcurrent

relay," Westinghouse 1.L.41-100D.Westinghouse Electric


Co., Coral Springs,
8.

Relay

FL. December 1976.

instrument

Differential

Relay

division.
for

"Type

Generator

CA

Percentage

Protection,If

Westinghouse

1.L.41-331.2D,

Westinghouse

Electric

Co.,Coral Springs, FL. February 1975.


Relay

9.

instrument

Directional

Ground

division.

Relays

"Type

CWC

and

CWP

instruction," Westinghouse

1.L.41-242.4F, Westinghouse

Electric Co., Newark, N.J.

Oct. 1975.
10. Relay instrument division. "Type SDF-1 solid state under
frequency relay instruction," Westinghouse 1.L.41-504.1,
Westinghouse Electric Co., Newark
11.

Relay
relay

department.

"Type DT-3

N.J. August 1975.

temperature and micron

Westinghouse

instruction,"

1.L.41-552.1D,

Westinghouse Electric Co., Newark, N.J. 1975.


12.

Relay

instrument

Synchro-Verifire

division.

relays

"Type

CVE-1

instruction,"

and

CVE

Westinghouse

1.L.41-681.1N) Westinghouse Electric Co, Coral Springs,


FL .
13. Relay-instrument division. "Type KAB high impedance bus
differential

relay,"

Westinghouse

1.L.41-337.4F.

Westinghouse Electric Co., Coral Springs, FL. May 1981.


14. Relay instrument division. "Type HU and HU-1 transformer
differential

relays

instruction,

1.L.41-347.1M, Westinghouse Electric Co.


15.

Westinghouse

, Newark, N.J.

Relay

instrument division. "Type SC, SC-1, SV and SV-1

relays

instruction," Westinghouse Electric Co. Newark,

N.J. July 1978.

16. Relay

instrument

Westinghouse

division.

"Type

CV voltage relay,"

1.L.41-201K. Westinghouse

Electric

Co.

Coral Springs, FL. December 1979.


17.

Relay

instrument

division.

relay," Westinghous

'I

Type

COM

overcurrent

1.L.41-102E.Westinghouse Electric

Co. Coral Springs, FL. June 1979.

18. Relay
type

instrument

DS

Application

and

division. "Characteristic curves for

DSL

circuit

breaker,"Westinghouse

Data 32-860. Westinghouse Electric Co. East

Pittsburg, Pa. 15112, November 1978.

APPENDIX 1 - IMPEDANCE DATA


Al.l ANSI standard reactance values calculation
Table Al-1 ANSI Standard Reactance Values

--

Positive-Sequence

First-Cycle (Momentary)
Calculation for

H.V. Breaker

Reactance

Utility Supply

XS

Plant Generators

X"

Synchronous Motors

XIf

Induction Motors
(Above 1000 hp >I200 rpm)

x1 r

(Above 250 hp >I800 rpm)

(All other motors 50-1000 hp)

.I' r
1.2Xlr

(Less than 50 hp)

.25X"

Non-rotating equipment

Interrupting Calculations for H.V. Breakers


Utility supply

Plant Generators

XIf
1 . 5X"

Synchronous Motors
Induction Motors
(Above 1000 hp >I200 rpm)

1.5Xlr

(Above 250 hp >I800 rpm)

1.5Xlr

(All other motors 50 - 1000 hp)

3.OXlr

(Less than 50 hp)

Infinity

Non-rotating Equipment
lr = Locked Rotor, %=utility

reactance

A1.2 Transmission line impedances


Table A1-2

V)
c

u
C

Transmission Line Impedances

I . . . . . . . . . . . . . . . . . . . . .

~ , 0 0 0 0 C 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ~

$ ' N * 6 m W O m N m m * P O r n v N P P W
9
o
~ l I c om ~n -, o~ e . c ~: ~* m
m q - n e~ ~q o~ w* - no ~
m ~
c *y m~ v m c u @ ~ . m m
i * ~ * ~ ~ m m m m m m q q q q v q o n o o o

......................

X O C O O C O O O O O O O Q O C O O O O O O O

A1.3 15-kV cable impedances


Table A1-3

6 AhG
3 AhO

U O

ALtG

3/0 AkG
410 AkG
2 5 0 MC!A
300 MCM
3 5 0 !.CCU
400 YC!I
5 0 0 IACM

6a0 MCM
753 MC!A
1000 A!CN
12>0 ).{C!.i
15CC UCM
1750 MCX
2 0 0 0 MCM

15-kV Cable Impedances

A1.4 5-kV cable impedances

5-kV Cable Impedances

Table A1-4

Approximate Resistance, Reactance, and Impedance of


M00.volt Cables in Magnetic Ducts per 100 H
Throe singlo-conduda cabiu p u duct,
ohm p u 100

Woo-eonductor cablo induding Intorlocked onnor coblo, ohms p u 100 f l

Coblo ria.

Ma 14 Awq..

. 0.3135

WalOAwq..
No.8Awg

0.1240
0.0779

0.W969
0.00150
0.CG781

0.313s
0.1210
0.0781

0.3133
0.1240
0.0779

0.006664
0.005745
0.005308

0.3291
0.1241
0.07808

0.0U741
0.00681
0.00623

0.0503
0.0325
0.0212

0.0493
0.0112
0.0197

0.004941
0.004619
0.004366

0.04944
0.03154
0.02017

No.Z/OAwq..

0.0163
0.0131
0.0106

0.00566
0.00567
0.00545

0.0173
0.0143
0.0119

0.0157
0.0125
0.0100

0.003961
0.003792
0.003677

0.01619
0.01304
0.01061

Wo.l/OAwg..
4
0A
.
2SO M C M . .

0.00860
0.0070a
0.00609

0.00535
0.00529
0.0056

0.0101
0.00817
0.00102

0.00800
0.00640
0.W7

0.003631
0.003313
0.003362

0.008785
0.007335
0.006527

0:00520
0.00461
0.00119

0.00519
0.00314
0.00506

0.00733
0.00690
0.00657

0.00460
0.00400
0.00354

0.003311
0.003U7
0.a3436

0.003791
0.005299
0.001923

0.0.00219

0.W95
0.W4

0.0061 1
0.00U1

0.00292
0.0010(

o.oo3wr
0.001018

0 . ~
0.003723

...

lb. 6 AwQ..
4A

.
.

Mo. 1 A
.
Mo. 1/0 Awq.

..

100 M C M .

...
..

350 M C M . .
400 M U . .

..
s
o ma.. ..
750MCM ....

0.0491
0.0118
0.0203

.-

A1.5 Correction factors for non-magnetic ducts


Table A1-5

Correction Factors for Non-Magnetle Ducts


b b k

s+k.an.lw)cr

t
foefar kv concctinq
mctoncm, 011 S U ~ S
of cabk

No. 6 to

No. 0 A r g

No. 8 A r g

0.8

Fa wrr.cclng r e d e a r n

fadom

0.96

No.0010
250 MCM

300 to
500 MCM

0.93

0.83

0.72

Correction Factors for Nonmagnetic Ducts.


Thr-ductor
Cables
Dotormino correct Z from corrected voluu of X and r0. No comedim is required for intedocked

armor.
f o c t m for correcting ruistoncm
f o a a for ronocting
rooctoncm, all rizm
of coblo

No. 14 to No. 00 A r g N a 0000 A r g to 750 MCM

0.17

1 .O

0.98

Per Cmt Reactonce of Typical Three-phase Cable Circuits


1000-tw lose

Per Cont Rooctonc. of 1000 Crcuit F W ~on o

I / 1 / / /
230

System rdtogo

Coblo h e ,

throo ringltcamdw9or coblw in


iron conduit................
Thrononducror coblo m iron conduit or in#-d
0rolor.d l
cable..
kao-conductor enblo in m a g neticduct..................

91.3

................... 71.8
511.5

575

2,400

4,160

6,900

13,100

No. 4 to 1 Awg

24.6

15-14

1.075

0,351

18

11.5

0.669

0.222

0.11

9.4

0.581

0.194

0.0955

14.7

Cablo siro..No.

1 /0

0.0276

0.024

No. 4/0 Awg

hrw nnglccarc)uctor

cobla in
ironconduit
n*eo-conducta cublo in imn conduit or i n t . r k c t d o-ad
coblo..
ecconductor cable in nommogwnetic+&

................

92.5

................... 68
.................. 34.8

23.2

14.83

0.953

0.318

17.1

10.9

0.6

0.2

13.72

1.1

Cable Six.,

re* singlrconductu cablu m


iron condvtt..
recconductor coblo in irom condwt or interlocked armored
coblo.
he.-conductor
coble in -magd c d w

$:
I

.............

.................... 61.4
.................. 51

0.0237

0.52 ~0.17310.01111 0.0101

250 lo 750 MCM

11.3

13-63 0.868

0.219

0.179

0.0796

0.01

0.139

O.W

0.0176

9.85

0.331

11.8

1.19

0.477

I I/
0.0943

For a~nglc-phwcueuru mult~plyvduea by 2-

APPENDIX 2

BELLE PLANT SHORT CIRCUIT STUDY

A2.1

DESCRIPTION

This
coordination

OF THE WORK

work shows the short-circuit study and relay


for

distribution

the

system

entire

for

the

power-house

Belle

plant,

electrical
(one

of

biochemical sites of E.I.dupont de Nemours & Company).

the
This

plant is required to modernize power house coal handling and


electrical distribution reliability for the entire system so
that
can

greater load capacity, improved reliability and safety


be achieved for the entire sytem.

power-house

electrical

facilities

Modernization of the
will

improve

the

electrical reliability of the power house by installation of


a

46-kV feeder from the existing structure between the

new

"A1' and

"B" switch house

transformer

with

12-kV

feeder

power

house

breaker

in

will

new

7.5MVA, 46/12-kV

primary circuit switcher.

A secondary

be provided from the transformer to the

complete
the

to

with

new

!'A" switch house

secondary

air circuit

and a new incoming air

circuit breaker located in the turbine area switchgear room.


The

new

incoming

switchgear
the

circuit

breaker

in

the

turbine

area

room will be connected to, and become a part of,

12-kV switchgear. Figure A2.1 shows the system setup as

83
a block diagram.

T h i s s t u d y w i l l i n s u r e a d e q u a t e r a t i n g s of a l l t h e
air

circuit

breakers

and

proper

relay

coordination

throughout t h e system.

Utility
. W 9 9/1
,

t N t '0" 46Kv
n

Bus

B n k tb.7, IWcl

F i g u r e A2-1 Block d i a g r a m of s y s t e m s e t u p

A2.2

12-kV

AIR CIRCUIT BREAKER RATING

Westinghouse
air

circuit

substation

breakers

as

12-kV

electric magnetic blast eight cycles


are installed at the purchased power
incoming

supply and feeder breakers.

Breaker specifications are as follows:


1.

Symmetrical three-phase rating = 500MVA

2. Continuous current rating = 1200 amperes


3.

Maximum voltage = 12-kV rms

4. Momentary rating = 37-kA rms asymmetrical,


momentary 2 s.

5. Minimum contact-parting time = 3 cycles


5. Rated interrupting time = 5 cycles

A2.3

SYSTEM ASSUMPTIONS

ANSI
calculation
voltage
The

of

circuit

procedures

Standard
fault

contains a guide

for

currents for application of AC high-

breakers
used

37.5-1969

in

rated
this

on a total current basis.


study are the same as those

suggested in ANSI standard by using

jX impedance only.

Certain simplifying assumptions were made for this


calculation which are as follows.

1.

Base MVA is 5MVA

2. Three-phase symmetrical fault

3. Line resistance is neglected

4. Fault is "bolted", that is, it has zero impedance


5. Tie breaker in 2.4kV switchgear is open,
Refer

to figure A2-2 in section A2.4 for the system single-

line diagram.

A2.4 BELLE PLANT SINGLE LINE DIAGRAU

The
used

as

line

diagram.

This diagram shows the normal distribution

represents

the best available definition of the system

and

electrical distribution switching diagram was


starting point in developing the system single-

for fault studies.


For purposes of this study, the system was defined
to
and

start at the 46-kV bus at the purchased power substation


continue through the 12-kV overhead distribution system

to transformers supplying secondary loads at 12-kV,2.4-kV or

480 volt.

Motors smaller than 50 hP were lumped together

and

as a single impedance on the secondary side of

treated

the supply transformer.


Data
conductor

on transformer impedances, transmission line

sizes

and

lengths

and bus duct capacity at the

purchased power substation were obtained from drawings.


The

single-line

diagram

used

shown in its final form in figure A2-2.

for this study is

Figure A2-2

Belle Plant Single Line Diagram

A2.5

BELLE PLANT IMPEDANCE DIAGRAMS

few

impedance diagrams are patterned after the

one line diagram.

The arrangement of elements should aid in

easy

identification of any given component in the two types

of

diagrams

(one-line

identification
circuits
into

itself

may

of

vs

impedance)

even

though

components and significant points in the

become

impossible

as the network is reduced

single-value

impedance.

The per-unit system lends

to

analysis

of

this system because of the several

voltage

levels.

A base MVA of 5MVA is assigned.

voltage

will

be

46-kV, 12-kV, 2.4-kV, and 480 volt.

current

and

base

can

then

diagrams

be

Base

impedance for each of the voltage levels

derived

for

The base

the

as

shown

in Appendix 3. Impedance

one-line diagram shown in figure A2-2 in

Appendix 2, which contains the subtransient reactance of the


system generator, the utility system reactance, and the perunit

value

of

all the transformers, feeder cables and the

motor loads is shown in figure A2-4, Appendix 2.


The
impedance

per-unit

diagram

values

(figure

for

all

components

A2-4) are derived and listed as

follows.
Utility:

X=5MVA/1020MVA=.0049 P.U.

Transformer (TI) :

on

X= (6.46%)(5MVA/lOMVA) = .0323 P .U.

Transformer(T2):

three winding transformer

Zp=1/2(ZpS+ZpT-ZST)
=1/2 (5MVA/15MVA) (19.66%+7.91%-18.83%)
=
.0146 P.U.
Zs=1/2(2PS+ Z ST-Z PT)=1/2 (5MVA/15MVA) (19.66%+18.83%-7.91%)
=
.0509 P.U.
ZT=1/2 (ZPT+ZST-ZPS)=1/2 (5MVA/15MVA) (7.91%+18.83%-19.66%)
=
,0118 P.U.
Transformer (T3) :

X= (5.09%)(5MVA/2.8MVA)= .0909 P . U.

Transformer (T4) :

X= (5.32%)(5MVA/3.75MVA)= . 0709 P.U.

Transformer (T5) :

X= (5.39%)(5MVA/3.75MVA)= .0719 P .U.

Transformer(T6) :

X=(5.09%)(5MVA/2.8MVA)= .0909 P .U.

Transformer(T7):

X=(5.55%) (5MVA/2.OMVA)=.139 P.U.

Generator : X1'=5MVA/102MVA=.
049 P . U.
Motors :
Typical
follows.

calculation
Appendix

for
1

Xth momentary short circuit is as

will

show the multiple factors for

different size of motors.

I. Xth(momentary)=l .2(1/6) (base kVA/load kVA)

1/6 is the lock rotor current.

2.

Induction motors 50-1000 hp,

3X1r

Xth (interrupting) =3 (1/6) (base kva/load kVA)


3.

Full load current=largest motor (~vA)


/fl(kVLL)
Lock rotor current=5(full

load current)+-total load

Cables :
The

per-unit

determined

by

values

of

all

the

cable impedances can be

referring to Appendix 1 , which will show the

approximate reactances of cables for various voltage levels


These
the

values
feeders.

will

be the actual impedance (ohm) values of

The per-unit values then can be calculated by

using the following equations.


Base impedance=(base

voltage,kVLL) /base

MVA3phase

Per unit impedance=actual impedance/base impedance


Examples :
1.

12-kV feeder, 1-3/C-500MCM (50ft)


2

Base impedance= (kVLL ' base) /baseMVA3phase


Base impedance=(12kV)
Appendix
15-kV

copper

magnetic

and

/5MVA=28.8 ohms

1 section A1.3 shows the ohmic values of


aluminum

conduit per 1000ft.

cables

in

magnetic

For 1-3/C-500MCM copper cable

non-magnetic conduit, R=.0279ohms/1000ft and


X=.0317ohms/1000ft

therefore:

and non-

Z=( R ~ + x ~'I2=
) [ ( .0279)2+ ( .0317)2] I/'=.

0422ohms/1000f t

For 50ft cable;

50ft(.0422/1000ft)=.0021ohms/50ft
Per-unit impedance=.0021/28.8=.0001 P.U.

2.

2.4-kV feeder, 3-3/C-750MCM/phase, 130ft long


2
Base impedance= (2.4kV) /5MVA=1.152
Appendix 1 Section A1.4, shows the ohmic values of

5-kV cables in magnetic ducts per 100ft.


the

correction

factors

for

Section A1.5 shows

non-magnetic

1-3/C-750MCM copper cable magnetic duct,

ducts.

For

R=.00208ohms/100ft

and X=.003088ohms/100ft then Z=.003723ohms/100ft


For 3-3/C-750MCM, Z=1/3(.003723ohms/10Oft)=.0013/100ft
For 130ft, Z=130ft(.0013ohms/10Oft)=.0017 ohms
From section A1.5 correction factor for 750MCM cable in nonmagnetic ducts is 0.72, so 2=.0017(.72)=.0012 ohms
Per unit impedance=.0012/1.152=.0011 P.U.
Table
short-circuit

A2-1 in Appendix 2 shows the results of the


calculations

for

momentary and interrupting

case at different locations of the system.


will

be

used

for

This information

specifying the 12-kV switchgear, 2.4-kV

switchgear and 480-volt switchgear.

91
Multiplying

factors

for three-phase and line-to-

ground faults.

,MULTIPLYINGFACTORS FOR E / X AMPERES

Figure A 2 - 3 multiplying factors [2]

Figure A2-4

Belle P . l a n t Simplified Impedance Diagram

A2.6

BELLE PLANT SHORT CIRCUIT CALCULATION

CASE 1: Momentary short-circuit calculation for fault "A"at


12-kV bus as shown in figure A2-1 and A2-5.

The
system

simplified

impedance

is shown on figure A2-4.

diagram for the entire

The equivalent circuit for

the impedance diagram is shown on figure A2-5 and A2-6.

Figure A2-5 The equivalent circuit for the impedance diagram

The

Wye-Delta

transformation

for

fault

"A" is

shown on figure A2-7.


MVASC=BASE MVA/XthP.U.=5MVA/.0188=416MVA
-BASE MVA/
(kVLL BASE) 103=5 (lo6) /12 (lo3) ~ = 2 4 A
0
IBASEISC'IBASE /XthP.U.=240/.0188=20,000.00A

'Tp,u,
1
Infinite Ru

Infinite Bus

mgQTA

,kw
P.u.

0 P*u*

,85337

D.il7*i/Zb+iizcrJ82.e C
Za&DZ~W(,W9)(.OiG)=,8216p,u.
&DZbfc=382(.81G)(.83397)=.
1487 p.u.

Z;lcrDZdc=W(.W9)(.83397)=.8583 p.u.

Inf initr Bus


I

Infinite Bus
I

Figure A2-6 Simplified equivalent circuit

By siylifing thr &ow circuit w get:


Infinite Bus
ee49

.P.U.

5263
P.U.

,8146
p*u.

8123
p.u.

*em
P*U.

"
"

Fault 'A'
To s i y l i Q this portin of t h c i r r i t . W-DELTA trrrrfmtim
is brar wrd.

Figure A2-7 The WYE-DELTA transformation

95

CASE 2: Interrupting short-circuit calculation for fault


I 1 All

The
system

simplified

impedance

is shown on figure A2-4.

diagram for the entire

The equivalent circuit for

the impedance diagram is shown on figure A2-8.

Infinitr RJS

Figure A2-8 The equivalent circuit (interrupting case)

The

Wye-Delta

transformation

for

fault

"A" is

shown on figure A2-9.

-BASE M V A / (kYLL
~
BASE) 103=5 ( l o 6 ) / 1 2 (103)\/T = 2 4 0 A

IBASE-

IS C=IBASE /XthP . U . = 2 4 0 / . 0 1 3 2 = 1 8 , 2 0 0 . 0 0 A

The
used

for

same

other

calculations

for

method
locations

other

of short circuit calculation is


of

the

points

in

system.

Result

the system is shown in

table A2-1.

Infinite Bus

Infinite Bus
UYE

Infinite Bus

-> DELTA

Infinite Wu

I
T

Figure A2-9 The

of

WYE-DELTA transformation

T a b l e A2-1 R e s u l t of B e l l e P l a n t S h o r t - C i r c u i t S t u d y
----.
F a u l t Location
Momentary S h o r t C i r c u i t C u r r e n t ;i

B a s e 5 MVA

Amperes

MVP.s~
I
--

.-----

.--

..-----

F a u l t "B" 46 KV

Fault

l f ~ l l

46 KV

14,326

F a u l t "A" 1 2 KV

19,400

F a u l t "D" 2 . 4 KV

17,480

F a u l t "El1 2 . 4 KV

27,097

F a u l t "F" 2 . 4 KV

F a u l t "MIf 2 . 4 KV

10,400

Ii

F a u l t "I" 4 8 0 V
F a u l t "K" 480 V

..

---

40,880
63,123

64,317

F a u l t Location

1140

17,660

F a u l t " N " 2 . 4 KV

1140

L
53

-.....-..

Interrupting Short Circuit

B a s e 5 MVA

Amperes

F a u l t "B" 4 6 KV

14,036

F a u l t "C" 46 KV

14,036

F a u l t "A" 1 2 KV

18,178

378

F a u l t "Dlf 2 . 4 KV

13,136

52

F a u l t "Elf 2 . 4 KV

22,396

89

F a u l t "F" 2 . 4 KV

12,923

51

F a u l t "MI1 2 . 4 KV

8,010

32

F a u l t "N" 2 . 4 KV

37,240

148

F a u l t "1"480 V

48,440

40

1 F a u l t "K" 480 V

48,600

40

MvAsc

1121
1121

APPENDIX 3
BELLE PLANT GENERATOR AND BUS PROTECTION

A3.1

BELLE PLANT GENERATOR PROTECTION

TYPE CA PERCENTAGE DIFFERENTIAL RELAY 10% (WESTINGHOUSE) [8]


The

type

CA

generator relay is available in two

designs: one for 10 percent sensitivity and the other for 25


percent sensitivity. Figure A3-1 shows the operating curves
for

10

percent

sensitivity. That means 10 percent of the

smaller restraint current must flow in the operating coil to


cause tripping when the restraining currents are in phase.
One

setting

is required for this relay, that is,

the setting of the time dial.

This setting should be on the

number one position as manufacturer recommended


The

only

setting

required

on

the

indicating

contactor switch (ICS) unit is the selection of the 0.2 A or


2.0

volt

tap

setting.

Since this relay is energizing a 125

d-c relay switch in this system, the 0.2

instead of 2.0 A tap.


set time dial 1, figure A3-1.
ICS (indicating contactor switch) . 2 amps

A tap is used

CWC GENERATOR GROUND A-C DIRECTIONAL OV3RCURRENT RELAY [9]


The

following information is required to set this

relay:

1) The

maximum

fualts

at

and
the

minimum
relay

ground

and

fault

current for

at the remote bus.

These

values should be residual current which is three times


the zero sequence current.

2) The

maximum

voltage
should

and

values
be

minimum
for

residual

the

polarizing current
faults above.

(IU) or

These values

current which is three times the

zero sequence values.

Cuur 5.rr-

H;

La t .

#&.A
rc%v e u i

ZOO/*

SFF
YRCT

Ull.Z,'l4

uua-

occa3Sq

3) The

current transformer ratios (C.T.) of the main and

polarizing current transformer.

CASE 1: Tie breaker is closed and generator is down.


Since

generator

is

down,

either

fault

F1 or F2 can see

current I1

R=M (I1/IU),for the 0.25 to 4.0 product range


Iprimary (polarizing)=50 A, C.T. ratio=50/5=10/1
Isecondary (polarizing)=50 A, C.T. ratio=50/5=10/1
Secondary current

(Iu)=Iprimary /C.T. ratio=50/10=5

Secondary current

(I1)=Isecondary/C.T. ratio=50/10=5

Product of

(IUXT1)
=25 and IU/I1=l.0

With tap product=25,

R limit constant should be 4.0or 5.0.

OCCRATINO C O K A Y C C R C S

Figure A3-1

Typical time curves for the 10% sensitivity type

CA generator relay [8]

R=M

( 1 I u ) select

upper tap=l.O and lower tap=0.25 from

table A3-1, then M=4.0 from the table A3-1.

Multiple of tap product=I1.Iu/(upper tap)(lower

tap)

=25/1( .25)=I00

from
dial=2

figure

A3-3

at multiples of tap product=100 and time

then operating time=.09 s .

Note :
The

typical

time

curves

for the type CWC relay

apply i f the values of (R) falls within the shaded area of


the

curve

shown

on

current is greater than

figure

A3-3,

and if neither relay

(K) in amperes.

Figure A.3-2 limits for application of the CWC time curve[9]

WLTlPLU OC TAP CIOOYCT

Figure

A3-3

typical

time

curves

of

- -

the

current coils in series [ 9 ] .

type CWC relay

Total time = operating time

+ relay time + breaker time

Total time = 0.09 s + 2(0.0167) + S(0.0167) = .21 s


The

relay 50/GN has 0.5 s delay, this allows 0.29 s

ground

for resetting of the 50/GN relay.

CASE 2: Tie breaker is closed and the generator is on.


IU(polarizing)
Since
By

= 50amps.

is on, fault F1 and F2 see 11+12=100 A, so

generator

using

figure

A3-2

and table A3-1, for the 0.25 to 4.0

product range M=4.0


I,=lOO A

I1/IU=lOO A/50 A=2, R=M(I1/IU)

Multiple of tap product


from

figure

= (10) (5) /1(

R=4 (100/50) =8

.25)=200

A3-3 at multiple of tap product= 200, and time

dial=2, operating time will be .065 s


Total time= .065 + 2(.0167)

+ 5(.0167)=. 18 s

Time to reset 50/GN relay=.5-.18=.32 s

Since

the calculated value of delay time for this

relay

is

proper

delta

wye ground transformer, then relay setting will be as

follows:
Set: Upper tap=l
Lower tap=.25
Time dial=2

for coordination with the ground relay on

ITH generator ground relay (westinghouse)


This

relay

is

factory set for minimum pickup of

0.25 amperes, no setting was required for this relay.


Set: All ITH relays on minimum pickup .25amps.

Device 59G generator over voltage relay


The

P.T.=

transformer,
permitted

relay

is

energized

12000/120=100

from

volts,

maximum

potential
voltage

on generator continuously is about 105 percent or

1.05(120)=126

volts.

120 volts relay set at tap=5 designed

to operate at 122 volts, then 122/120 = 1.016 percent, Relay


is

factory set for

tap = 5 and lever = 10, field to adjust

per curve shown on figure A3-4.

104 percent continuous over

voltage limit is desired.

Device 53G volts per hertz relay


SVF

Type
volt/hertz

for

.lvolt/hertz
maximum.

form

2E1, hitachi, maximum permissable

generator

increment.

is

1 . 2 per-unit.

Relay setable

Relay setting of 1.9 volt/hertz is

This relay was set at factory for 1.2 volt/hertz.

Device 60G voltage balance relay


Type SDV3 form W-3E2, hitachi, these voltages will
normally be balanced.
be selected.

Therefore most sensitive setting will

This relay was set at factory for 1 0 volts.

Device 64F field ground relay


Relay
used,

because

single
of

field

form C-Dl, hitachi, this relay is

circuits

are operated ungrounded.

ground fault will not damage or affect the operation


generator

single

SG

type

in

any

way.

However, the existence of a

ground fault increases the stress to ground at other

points in the field winding when voltages are induced in the


field by stator

transients [ 4 ] .

This relay is factory set,

therefore no setting is required for this relay.

Device 27G high speed under-voltage relay


Type
agiven
at

W3-UT21-21

E2,

value of under-voltage,

this

relay

functions

The dropout is normally set

80 to 90 percent of normal voltage.

approximately

on

This

relay is factory set for maximum value of voltage 95 volt.

KLF loss of excitation relay (Westinghouse)


Refer
capability

to

figure

curve.

A3-5

to see generator reactive

The machine capability curve on figure

A3-6, was generated from figure A3-5.


been

drawn

on

an

A reactive circle has

R-X diagram. The equivalent generator

impedance traces a path from first quadrant into a region of


the

fourth quadrant that is entered only when excitation is

severely

reduced

or

lost.

By

encompassing this region

107
within the relay characteristic, the relay will operate when
the

generator

field

breaker

first starts to slip poles and will trip the


and disconnect the generator from the system

before either the generator or the system can be harmed.

As

shown on figure A3-6 ZA-1.98 and R=1.03.


= [ (KV)2 / ~ [ ~
(RC/RV)
~ ] ]=12'/14.564
'base
ZA=l.98(19.776)=39.16 ohms.

(200/100) =19.776 ohms

Zc=.08(19.776)=1.58 ohms.
(SA) must be greater than or equal Z
'base
A' therefore:
19.7(SA)>
39.16, then SA must be atleast 3.0, so set S
A

TA=ZA/SA=39.16/3=13.05, set TA on tap=11.5

MA= [TA SA/ZA] -I= [ll.5 (3)/39.16] - ( 9 ), set MA =-0.12


This requires: L, lead on .03 and R, lead on upper .06
Actual Z=TA SA/(1-MA)=11.5(3)/(1-.12)=39.2
39.16/39.2=99.88% of
SC

for 6(Sc)>1.58.

setting required.

Set ZC=1,58, set

SC=l minimum tap so set S C = l

tap closest to Zc/Sc=1.58/1=1.58.

Set TC tap=1.84

Mc= [(TCXSC) /ZC]-I= [I.84(1) /I.581 -I=.165


Set MC for 0.15, L(1ead upper)=.06 and R(lead)=O.O
ZC=1.84(1)/(1+.15)=1.6
1.58/1.6=98.75% of required setting.
Set under voltage unit at 77% (factory set check).

Set TC

Figure A3-4 Generator Overvoltage Curve.

Figure A3-5 Generator .Reactive Capability Curve.

Figure A 3 - 6

Generator Capability Curve,

CRN-1 Reverse power relay (Westinghouse)


Set
seconds.

relay

detect monitoring in approximate 6

to

time dial of 2 for 120 volts.

Using

Set timing

relay at 30 seconds (Agastat) to trip the generator.

COQ Generator negative sequence relay (westinghouse)


hitachi generator data C.T.ratio = 1000/5 or

From

-701
Ifullload--

200/1 and

amperes. 701/200 = 3.505

Set relay: Tap=3.5 A


Time dial = 4.0 and ICS = .2 A

SDF-1 Under frequency relay (westinghouse) r101


Figure
actual

A3-7 shows the effect of time delay on the

frequency

at

which

tripping

declining

frequency

conditions.

frequency

continues

to

for

the

relay

takes

placeunder

The curves show how the

drop in the time interval required

to operate after its frequency set point is

crossed.
For
constant

example, suppose that for a system of inertia

H=2,

it

is

required

for any overload upto 46 percent.

below

57.5Hz

relay

is set to trip at 59.2Hz.

figure
6Hz/s

A3-7
rate

that the frequency not dip

indicates
of

that

decline.

Assume the

The scale at the bottom of

46 % overload will cause a

The SDF-1 relay with 15 cycles of

delay setting will close its trip contact when the frequency

112
has

dropped

overload

1.7Hz below the set point, or 57.5Hz, for this

condition.

acceptable

time

Thus

delay

15

setting

cycles
to

is

the

maximum

obtain

the

desired

protection.
In this system the relay is set to trip at 57.5Hz,
30

cycles

frequency

delay
relay

provided.

Breaker No.1 and No.10 under

are set to trip at 58.5 Hz(3 cycle delay).

Refer to figure A3-7.

DT-3 Generator temperature relay (westinghouse) rll]


Normal

setting

for

this

type

of

relay is 120

degree centigrade. Since this relay alarms high temperature


only,

set

relay

at

115

degrees

C to provide operator a

pre-warning to increase cooling water supply.

RATE OF FREQUENCY

H-2

H=4

10

20

10

20

30

40

50

30

D E C L I N E . HZ / SEC.

40

60

70

80

1
90

60

100

120

140

APPROX. PERCENT SYSTEM OVERLOAD


CONSTANT WITH FREQUENCY AND PF
H = SYSTEM INERTIA CONSTANT, KW-SECMVA

(ASSUME LOAD

70

50

.as)

Fig k3-7 SDF-1 Relay Tripping Delay Under Declining


Fig
A3-7
SDF-1 Relay Tripping Delay Under Declining
Frequency Conditions [lo]

CVE-1 Syncheck relays (Westinghouse) [ I 2 1


For
as

follows:

breaker No.10 (in unit No.4) CVE-1 setting is


The time dial should be set so that the relay

will not operate when the system are swinging too fast. From
figure

A3-8

(Westinghouse)

for

a 20 degree circle as the

relay calibrated from factory, set the time dial setting =1,
then the operating time will be about 2.8 seconds.
It
time

dial

is
equal

recommended by the manufacturer to set the


11, when 60 degree circle setting is used

and time dial of 4 when 40 degree circle is used.

Figure 113-8 Operating time variations with changes in


time-dial settings.

Rated in phase voltage on

both circuits, 20, 40 and 60 degrees circle


setting

[I21

Automatic synchronizer W
The
to

be

U (Westinghouse)

following are suggested settings and may have

altered

in field due to various voltage differences

that occur.
Voltage acceptor: Lower limit 110 volts
Upper limit 120 volts
Difference limit 5 volts
Voltage matcher 2 volts times 3 second
Pulse duration time .25 second
Field

check closing times of all synchronizing breaker and

set EQ breaker closing equalizer.

A3.2 BUS DIFFERENTIAL PROTECTION [13]

KAB
relay

of

bus

the

differential

is an instantaneous

high impedance type used for bus protection.

The

following

type

KAB relay application.

1)

relay

points

should be considered on any proposed

All ct's in the bus differential circuit should have the


same ratio and should be operated on their full tap.

2) The leakage impedance of the ct's should be low.


3)

To

insure a substantial margin of operation on internal

faults,
than

the

knee

voltage

voltage

unit

should not be set any higher

Vk, value

of

poorest

ct which is

connected to the relay.

4)

To

insure a substantial margin for preventing the relay

from operation on external faults, the knee voltage value


of

the best ct which is connected to the relay should be

used to determine value of (RS+RL)IF/NVK

The

knee

extention
saturation

in figure A3-9.

voltage

is defined as the intersection of the

of

two

the

curve,

straight

ordinate

line

and

portions

abscissa

of the

must be same

scale for each decade.


5)

The maximum number of circuits which can be connected to


the
to

relay or the minimum internal fault current required


operate the relay can be estimated from the following

equation

Imin=(XI,+IR+IV)N

Imin=minimum

,where

current,

RMS. Ie=ct

secondary

voltage.

equal

,the

IR--Current
in

in

varistor

value

of

to

internal

excitation current at a

setting

value

V-unit.

at
N=ct

of

V-unit.

VR. I ~ C u r r e n t

V-unit at setting voltage

circuit

fault

a voltage equal to the setting

turn's

ratio and X=Number of

circuits connected to the bus.

Device

maximum

ground

fault

is

the

transformer ground and the generator ground.


Maximum ground fault=50A+50A=100 Amps
Switchgear short circuit available=500
3 Phase symmetrical f ault=500
1200/5 CT,

MVA

M V A / (~1 2 ~ =24
~ ) KA

VK, voltage Knee=160 volt, N=1200/5=240

sum

of

Current Transformer resistance= R

=.471 ohms

One way lead resistance 80ft of #14 wire=RL=.156

Voltage unit setting (3 phase fault)


C.T. Saturation Factor=(RS+RL)IF/N.VK=.392
Margin Factor, K=1.32, found from figure A 3 - 9 .
Relay voltage, VR=K(R S+RL)IF/N, then VR=82 volt,
so pick the relay voltage, VR=90 volts.

Current unit setting

( R +R
~ L)IF/N=63 From figure A3-10
Unit setting=3 A (rms)

2.4KV

Bus

differential

type KAB relay, Westinghouse style

NO. 6668D37A12 87 device.

Switchgear rating = 200 MVA


Maximum fault = 48,000 A
Minimum fault = 24,000 A
Maximum ground fault = 340 A
C.T. 2000/5 = 400/1 =

Knee voltage = 240 volts = VK


C.T. DC Resistance = .858ohms = RS
One way lead resistance = .032 (50ft of # 8) = RL

R S+RL- . 8 9 ohms

Current unit setting (instantaneous 3-48 amps)

( R +R
~ L) IF/N= ( .89) (48,000amps/400) =106.8
From figure A3-10

Figure A3-9

setting is 3 amperes.

KAB Relay Voltage Unit Setting[l3].

Voltage unit setting (75-300 VAC)


C

.T .

Saturation Factor = (RS+RL) I F / N . VK

C . T. Saturation Factor

= .89(48,000amps) /400(240)= .445

From figure A3-9, margin factor, K> .95


VR=K (RS+RL) IF/N=.95 ( .89 ohms) (48,000amps) /400

101.5

Pick relay voltage, VR = 120 volts


Check minimum fault current required to operate the relay.

= 6 circuits

IE = .015 A

VR=120 volts

1 . 0A

Figure A3-10 KAB Relay Current Unit Setting[l3]

APPENDIX 4
BELLE PLANT TRAiiSFORMER PROTECTION

A4.1

TYPE HU-1 TRANSFORMER DIFFERENTIAL RELAY r14]

(Westinghouse)
In
and

check

order

current

to

calculate the required tap settings

transformer

performance

the following

information is required.

1) Maximum transformer power rating (KVA)M


2) Maximum external fault currents

3) Voltage ratings of power transformer (VH,VI,VL)

4) One

way current transformer lead resistance at 25 degree

ormer copnections (wye or delta)


5) Current tr-ansf

6) ct secondary winding resistance, RS

Definition of terms

IP-Primary current at (KVA)M


IR=Relay input current at (KVA)M
IRH IRL IRI are
)

same

as

IR except for high, low and

intermediate voltage sides respectively.


IS=CT secondary current at (KVA)
T=Relay tap setting.

TH ,TL ,TI-T except for high, low and intermediate voltage


winding, respectively.

N=Number of current transformer turns that are in use.

NP-N/N T (Proportion of turns in use)


NT=Current transformer ratio, full tap
ZA-Burden impedance of any devices other than HU-1 relay
Iext .

=Maximum

symmetrical

external

fault

current

in

secondary RMS amperes.


ZT=Total

secondary

burden

in

ohms

(excluding

transformer winding resistance.)

Calculation procedure
Three-winding transformer bank N0.7

High

Intermediate

(KVA)M= 15MVA

(KVA)M= 15MVA

Low

(KVA)M= 15MVA

current

1)

Selection of C.T. ratio

I, (high)=15,OOOKYA/: 5' (46KV)=I88 A

300/5 C . T. ratio

1 ~ ( i n t e r m . ) = 1 5 , 0 0 0 ~ ~ (12KV)=721
~/'~~
A 1200/5 C .T. ratio

I (low) =l5,OOOKVA/'F
(2.4KV)=3600 A 5000/5 C.T. ratio
P

2)

Selection of relay taps

Is(high) =Ip/N=188/60=3. 13 A

IS(interm.) =Ip/N=721/240=3.0 A
IS(low)=I,/N=3600/1121=3.22

IR(high) =Is(high) =3.13 A


IR(interm.)=IS (interm.)=3.0 A

IR(low) =IS(low)=3.22 A
TAPhigh=TH=3.
2 (3.13/3.22)=3.11

TAPinterm.=TI-3.2 (3.0/3.22)=2.98
TAPlOw=TL=3.2

3)

Mismatch calculation
High side
%Mismatch=100 [(IRhigh/IRinterm. ) - (TH/TI) ] /S
S=The smaller of IRhigh/IRinterm. or TH/TI
TH/TI=3.2/2.9=1.10 and IRhigh/IRinterm.=3.13/3.0=1.043
Then S=1.043
%Mismatch=100(1.043-1.103)/1.043=-5.79

Intermediate side
%M=lOO [ (1,intex-m. /IRlow) - (TI/TL) 1 / S
T /T -2.9/3.2=.906 and I interm./I low=3.0/3.22=.932
I LR
R
Then S=.906
%M=100(.932-.906)/.906=2.87%

Low side
%M=lOO [ (IRlow/IRhigh) - (TL/TH) ] /S

IR low/IRhigh=3.22/3.13=1.0288 and TL/TH=3.2/3.2=1.0


Then S=1.0
%M=lOO(l.O288-l.O)/l.O=2.88

4)

Check C.T. performance for WYE connection


High side
ZT=1.13RL+0.15/T +Z ohms, where R =.I63 Q 75 degree

H A

ZT=1.13(.5)+0.15/3.2=.61 ohms

Np=N/NT=60/60=1
NP(VCL/lOO)>ZT,

since 1(100/100)>.61, then it is 0.k.

Intermediate side
C.T.=1200/5
RL=.471 Q 75 degree=.396 Q 25 degree
ZT=1.13RL+.15/TI=1.13(.396)+.15/2.9

ZT-.499 ohms, Np=N/NT=240/240=1, VCL=200


Np(VCL/lOO)>ZT,

since 1(200/100)>.499,

then it is 0.k.

Low side

HU-1 style 290B346A10 setting are as follows.


Instantaneous = 3 times of tap setting
Pickup = . 3 times of tap setting
Taps available = 2.9, 3.2, 3.5, 3.8, 4.2, 4.6, 5.0, 8.7
Setting used, (Thigh'3.2,

Tintermz3

'

T ~ o=3.2)
w

Type SC circuit switcher relay (Westinghouse) r151


The
Wide
the

type

SC

current

relay is adjustable over a

range

of voltage or current and can be calibrated for

proper

pickup setting. The type that is used here is a

d-c, 25 to 60hz frequency with a current adjustable range of

40

to

160 A, with a maximum continuous current equal 40 A.

Dropout ratio for a-c is between 90-98% and for d-c would be
65-80%.
The proper adjustments to insure correct operation
of this relay have been made at the factory.
Range=40-160 amps.
Circuit switcher interrupting rating =8,000A
for primary faults. Primary C.T. ratio=200/5=40/1

125
160(40/1)=6400

amps, maximum current which will operate

the

Since circuit switcher has to clear the fault

relay.

before

No.2

primary feeder and coordinate with overcurrent

relay on bank No.1 then, the instantaneous setting =I60 A as


shown in Appendix 5 section A5.1.

126

APPENDIX 5

- BELLE PLANT OVERCURRENT PROTECTION DETAILED

DRAWINGS
A 5 . 1 "A" s w i t c h h o u s e , Bank N o . 1 and 1 2 k V B u s " D M

A5.1 continued
Refer

to Appendix 6 section A6.2 for selection of type CO-9

relay curves.

A 5 . 2 ECR No.6, 12kV Bus "A"

FROM IZKV
2

UNIT

SWGR

A5.2 continued
Refer

to Appendix 6 sections A 6 . 1 and A 6 . 2 for selection of

type CO-7 and CO-9 relay curves respectively.

r u 4 i~L

clALn/Fz43n
c m ~ mrm
r
Ln

A 5 . 3 ECR No.6 , 12kV Bus "B"

A5.3 continued
Refer

to Appendix 6 section A6.2 for selection of type CO-9

relay curves.

A5.4 Co-generation generator

ZEPO SEQUENCE

!'

NOTE: REFER TO W615413 FOR hE TAl LED


G E N E R A T O R RELAY SINGLE LINE
DIAGRAM.

A 5 . 4 continued

A 5 . 5 Bank No.7 feeder No.18

A5.5 continued
Refer

to Appendix 6 section A6.2 for selection of type CO-9

relay curves.

A 5 . 6 2.4kV 600hp motor river pump house

A 5 . 6 continued

A 5 . 7 2.4kV 4 5 0 h p motor boiler feeder pump No.5

CuQRErJT
RELAY

# 5 B ~ I C E RFEEDWATER
PUMP

A5.7 continued
Refer to Appendix 6 section A6.9 for selection of type AA12P
overload relay curves. Fuse curves are shown in Appendix 7.

-------- -.--

- - -,,*--

.----..--.-.

--:
------.
-----.-A

I
.-,--...-.----

---

.
1
.

.,.*-

. . L

... .
..

-..-..

. - - - ----,
U v L r m r ruu cunxrwr IN A

n s x a X & A T ~xv.
A

- -- - . -

- -

A 5 . 8 2.4kV 7 5 h p m o t o r a s h pump

Z 4 K V UNIT 3 A

p;RuADa

(3
50/5

L.R.
OVER
CURREUT

RELAY

A5.8 continued
Refer to Appendix 6 section A6.9 for selection of type AA12P
overload relay curves. Fuse curves are shown in Appendix 7.

N A I L CI
/%-A

--

mmarrcrIS_n
a l m H

cr

&

m rm r r r rn

nnmnro-H

1 U I L -

Cf -,%-A

cmlr miu

Imr mu *

n
u
l

m u R - X

A5.9 2.4kV 200hp motor recirculating pump

A 5 . 9 continued

A5.10 2.4kV 200hp motor F . D . fan boilers No.6 & 9

UNIT

F.D. FACJ

68

A5.10 continued
Refer to Appendix 6 section A6.4 for selection of type CON-5
overcurrent

relay curves.

are shown in section A6.9.

Type AA12P overload relay curves

A 5 . 1 1 2.4kV f e e d e r s , s h e e t No.1 & Bank No.60

.AN<
'60
5250 KVA
I2KV /2.4KV

&,

A5.11 continued
Refer

to Appendix 6 section A6.2 for selection of type CO-9

relay curves.

MULTIPLY $CALL C U R R E N T IN A M P E R E S

X =AT-?&

KV

A5.12 2.4kV f e e d e r s , s h e e t No.2 & Bank No.59

SECIPC,
PUMP

A 5 . 1 2 continued
Refer

to Appendix 6 section A 6 . 2 for selection of type CO-9

relay curves.

A5.13 2.4kV f e e d e r s , ECR No.5

A.f? CO. %KV

BANK
4GKV

4CKY

*7

1 5M V A

IZKV
IZKY

A 5 . 1 3 continued

Refer

to

selection

Appendix
of

respectively.

type

sections A 6 . 1 , A 6 . 2 and A 6 . 3 for the

CO-7,

CO-9

and

CO-11

relay

curves

A5.14 2.4kV 15Ohp motor boiler No.10 mills

A5.14 continued
Refer
type

to Appendix 6 sections A6.4 and A6.9 for selection of

COM-5 overcurrent relay curves and type AA12P overload

relay curves.

A 5 . 1 5 2.4kV 550hp motor I . D . f a n boilers No.14 & 15

UNIT 4 A

UNIT 4 6

A 5 . 1 5 continued

Refer
type

to Appendix 6 sections A6.4 and A 6 . 9 for selection of


COM-5

overcurrent relay curves and type AA12P overload

relay curves.

-+-nn

TY__ IL

er

nanmrrcr>

al

mlDAsl

mr-m-I2

--

1
U
1
1
-

' 5 - n
c w n mrrcr
n

CT

.n ma-um
ur-m-x

'

CI

'OAT=
KV.

-,
/

U IL
L-/I
n

mm3usMUL'flPLT Sa2AI.X CU8EXNT IN A Y P I I C I

A 5 . 1 6 2.4kV 4 0 0 h p motor I . D . f a n boilers No.6 & 9

UNIT 4A

UNIT 4 8

A5.16 continued
Refer
type

to

Appendix 6 section A6.4 and A6.9 for selection of

COM-5 overcurrent relay curves and type AA12P overload

relay curves.

(n

roowe

4-

cr. -R--n
NLllRUM&#V

mr m m w R

cr. a ,%>/I

m ~ mrm
r Ll

LV

N%TLL_!
Lr-,%
c:m11 YalW

NI-;anvrunr
m1'mb
an
BLLI

rm-

L I

cm
i 11Y a r m

-<'

A5.17 4 8 0 V feeders, ECR No.8 sheet 1

A5.17 continued
Refer
type

to Appendix 6 sections A6.7 and A6.8 for selection of


Amptector

11-A and type DSL-206 Limiters. Appendix 7

shows the selection of type LPS-RK Buss fuses.

A 5 . 1 8 4 8 0 V f e e d e r s , ECR No.8 s h e e t 2

BLR* 9 MCC

=Rat4

MCC

BLR'ISUCC

AS.18 continued
Refer
type

to Appendix 6 sections A6.7 and A6.8 for selection of


Amptector

11-A and type DSL-206 Limiters. Appendix 7

shows the selection of type LPS-RK Buss fuses.

A 5 . 1 9 480V feeders, ECR No.8 sheet 3

AS.19 continued
Refer
type

to Appendix 6 sections A6.7 and A 6 . 8 for selection of


Arnptector

11-A and DSL-206 limiters. Appendix 7 shows

the selection of type LPS-RK Buss fuses.

A 5 . 2 0 2.4kV 5 5 0 h p motors

I.D. f a n boiler No.10

A5.20 continued
Refer

to Appendix 6 sections A6.4 and A6.9 for selection of

type

COM-5 overcurrent relay curves and type AA12P overload

relay curves.

APPENDIX

WESTINGHOUSE

OVER VOLTAGE AND

OVERCURRENT,

UNDER VOLTAGE RELAY CURVES [ 7 ] , [16]


A 6 . 1 T y p e CO-7

Over C u r r e n t R e l a y [ 7 ]

V)

Q
2

0
U
W

M U L T I P L E S OF TAP VALUE CURRENT


Typical Time C u r v e o i t h e T y p e C O - 7

Relay

9 10

12 14 16 18 20

A6.2 Type CO-9 Over Current Relay[7]

'TYP T C:V,'T Ty1E C U R V E S


'1,Y 1' 1: LO- $1
OVER CURRENT RELAY

M U L T i P L E S OF T A P V A L U E C U R R E H T
T,r

cul T

C , r v e q i thr T v o e

CO 9

RCIO~

A 6 . 3 Type

TIME D I A L
SETTING

HULTIPLES OF TAP VALUE CURRENT

T y p , c o l Trme C u r v e o i the T y p e

C O -l i Relay

A6.4 Type COM-5 Over Current R e l a y [ l ? ]


I

'

I , ,

,.*

TYPICAL T I M E CURVES

OVER CURRENT R E L A Y

M U L T I P L E S OF TAP VALUE CURRENT

8 910

AB.5 T y p e CV-2 U n d e r Voltage Relay[lG]


32
TYPICAL T I M E CURVES
UNDER VOLTAGE RELAY

30
28

26

24
22

20
18
v)

16

0
U
W

v)

14

12
10

1)

1C

2C

30

40

50

60

7G

80

90

0
1OC

P E A C E N T TAP V A L U E V O L T A G E
TIP,cal60-crcle T ~ , ~ W C U ~
or* tho
O S t y p o C V 2 S h o e T ; m * Undorvoltope R e l o r .

A 6 . 6 Type CV-7

Over a n d Under V o l t a g e R e l a y [ l G ]

T r P . < a l Y 1 - c y c ~ +t ~ m rc v r e x o f t h e t y p e C V 7 I h r r T . 0 . Ow..

o l d Umd.rroltap*

R.iey,

A6.7 Type Amptector II-A Time-Current Characteristics[l8]

CURRENT IN MULTIPLES OF SENSOR RATING

CURRENT IN MULTIPLES OF SENSOR R l T l N G

A 6 . 8 Type DSL-206 L i m i t e r s [ 1 8 ]

A 6 . 9 Two p o l e t y p e AA12P Overload Relay

"

- M

"

IN SECONDS

"

'

---"I

I
---.--. . .--

nME

- n - - - -

,.__,
LIW'

TRIP

--

- - A--L,
&-I

.-.-.-

L+--J--&+
-.+-,-_LJ--.

--..-,.z

I
-

II

_ . . - ' . n . . o

TRIP T \ M E 'N .(SFCONDS

I.

L.

,#

G.

. .

" "
"
"
c,

.
)
U

..--;
-.

"- -

.(

-3

. ..
- .- .. .
---&i

i..---Lm - T f --I7
3
f $ 'i~bl'tj

A 6 . 9 Continued

- -

- - - - o

TRIP TlPAE IN SECONDS


- . - - I .

I.

...........
-- - --

." . . . . . ... . . .

'"
-

+:-

'
., ,.o - .-

0
0

,_ _.
---,

--

-----

---.

...?
. . . . . . . . . . . . . -. .,. . .,.
,

> - .

--+
4

1,.

-0

. ! *

'.-. . . . . . . .

.
.

., & , , . .

--

"

. . . . . . . .
.

. . < . .

'r)

. .

. . . . . . . . .

.
.I

-c

7 . y

L l n O i - . - & - -

uo---

..........

--.--..

- 1 ,
-,..-..-+-8

---- -,. +Ail). .-----.


I--;

- - - ------

-_-A

TRtP T I H E

---i-.-

--,-.----

3-t

. .' - r
I

..........,..................

...

I.:
;-.,
: - , .
--,
....
_ . _ _ - - .. . . . . . . . .

-.-2 Zd:6i

SECO&JDf

f IIS6,jf

1.-

.,A.

b:

A 6 . 9 Continued
f R I P TIME IN SECONDS

4hl, ----

.- .

...

xw
.m

.
-. .-

.l

I . .

- - --.

...-

,i-.-

+
~ --,.- + - k. t f "----i-C
- l.--. - ----- r
.
i+*

..

L.-.

-----..
--I

-..

. - ",
"

4.-

..

-..

. . . . .

-. . . . . . . . . . .

. - - - i d .

6.--

.
I:
I . -.
. ! :... .--r.-. :

. .

. .

L I-

::

.
.

3m

...

. .
........
.-----.
-T7
., - 4 -.w

7:-=-

r r g r z x i

T R I P TIWE IN S E C O N D S .

"
2

522i!?f

1rZa

A 6 . 9 Continued
IN SECONDS

TRlP TtME

LX:,

- l .

----------. .

...

. r

-----i . ? .

..-.--.---...A-

L...

--..

.-..

L..

-.,
-.

-.---.

. , #
, ,.

i--1--7-

ta

-.

.-

- -. - -..--

..
I

.
.

-.-,
,

--*

<,.*.

rur
-0

.-------.-,--.-..
: .,- --.--.---: -..-. :--!A_
--;..-____
,-,-r*+-,l---.--*
__;
--, .
-----..
- ..
-..-1 . L - I
-.--..
- . . --.. ...-..-- --. . - .
._A

'

"

- - - a -

L
U

. ..-----

_ _ #

TRlP T I W E IN S E C O N D S

'

.-.

-1

8Z.i:

f 5 3

1M

\..-

A 6 . 9 Continued

T R I P TIME IN SECONDS

A 6 . 9 Continued.

APPENDIX 7 - BUSS FUSES CURVES


A7.1 Type LPS-RK(R.Kl) LOW
- PEAK Dual-Element Fuses (600v) [I91

Minimum Melting Tlme-Current Characteristic Curves

L47.2 Type

KRP-C H I - C A P F u s e s ( 6 0 0 ~[I91
)

Total Clearing Tlme-Current Characteristic Curves

APPENDIX 8

AND FUNCTIONS

ASA DEVICE NUMBERS

A8.1 ASA DEVICE NUMBERS

AND FUNCTIONS

Each device in an automatic switching equipment has


a

device

within

function
the

device

number

which

symbol

on

is placed adjacent to or
all

wiring

diagrams

and

arrangement

drawings so that its function and operation may

be

identified. These numbers are based on a system

readily

which
the

was

adopted

American

The

as standard for Automatic Switchgear by

Standards

following

Association

is

list

and

of

appear

FUNCTION

ASA

device numbers and

functions as taken from this standard.


DEVICE No.

in

AND DEFINITION

.1

Master Element

Time delay Starting or Closing Relay

Checking or Interlocking relay


Master Contactor
Stopping Device
Starting Circuit Breaker
Anode Circuit Breaker
Control Power Disconnecting Device
Reversing Device
Unit Sequence Device
Reversed for future application

Overspeed Device
Synchronous speed Device
Underspeed Device
Speed or Frequency Matching Device
Reversed for future application
Shunting or Discharge Switch
Accelarating or Decelerating Device
Starting to Run Transition Contactor
Electrically Operated Valve
Distance Relay
Equalizer Circuit Breaker
Temperature Control Device
Reversed for future application
Synchronizing or synchronism Check Device
Apparatus Thermal Device
Undervoltage Relay
Reserved for future application
Isolating Contactor
Annunciator Relay
Separate Excitation Device
Direction power Relay
Position Switch
Motor Operated Sequence Switch
Brush operating or Slip ring Short cir. Device
Polarity Device

Undercurrent or Under power Relay


Bearing Protective Device
Reversed for future application
Field Relay
Field Circuit Breaker
Running Circuit Breaker
Manual Transfer or Selector Device
Unit Sequence Starting Relay
Reversed for future application
Reversed Phase or Phase Balanced Relay
Phase Sequence Voltage Relay
Incomplete Sequence Relay
Machine or Transformer Thermal Relay
Instantaneous Overcurrent or Rate of rise
A-C Time Overcurrent Relay
A-C Circuit Breaker
Exciter or DC Generator
High speed D-C Circuit Breaker
Power Factor Relay
Field Application Relay
Short Circuit or Grounding Device
Power Rectifier Misfire Relay
Overvoltage Relay
Voltage Balance Relay
Current Balance Relay

185
Time delay Stopping or Opening Relay
Liquid or Gas Pressure, Level, or Flow Relay
Ground Protection Relay
Governor
Notching or Jogging Device
A-C Directional Overcurrent Relay
Blocking Relay
Permissive Control Device
Electrically Operated Rheostat
Reserved for future application
D-C Circuit Breaker
Load Resistor Contactor
Alarm Relay
Position Changing Mechanism
D-C Overcurrent Relay
Pulse Transmitter
Phase Angle Measuring
A-C Reclosing Relay
Reserved for future application
Frequency Relay
D-C Reclosing Relay
Automatic Selective Control or Transfer Relay
Operating Mechanism
Carrier or pilot wire Receiver Relay
Locking out Relay

Differential Protective Relay


Auxiliary Motor or Motor Generator
Line Switch
Regulating Device
Voltage Directional Relay
Voltage and Power Directional Relay
Field Changing Contactor
Tripping or Trip Free Relay

You might also like