Professional Documents
Culture Documents
Short Circuit Calculation PDF
Short Circuit Calculation PDF
..
CALCULATIONS
A Thesis Presented to
The Faculty of the College of Engineering and Technology
Ohio University
In Partial Fulfillment
of the Requirements for the Degree
Master of Science
Houshang C. Mohammadi
s
August, 1986
OHIO UNIVERSITY
LIBRARY
ACKNOWLEDGEMENTS
I would
to
Dr.
their
Albert
thesis.
I owe
company
who
gave
education while
my
thanks
to
great
me
deal to my employer,
this
opportunity
to
E.I. Dupont
continue
my
TABLE OF CONTENTS
CHAPTER
CHAPTER
CHAPTER
ABSTRACT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xii
1.
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1
1.2
Literature search . . . . . . . . . . . . . . . . . . . . . . .
1.3
2.
2.1
Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2
Synchronous motors . . . . . . . . . . . . . . . . . . . . . . . 8
2.3
Induction motors . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4
2.5
2.6
3.
Short-circuit-current calculation . . . . . . . . 17
3.1
Important assumptions . . . . . . . . . . . . . . . . . . . . 18
3.2
3.3
Impedance diagram . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4
3.5
3.6
3.7
CHAPTER
4.
4.1
Overcurrent relays . . . . . . . . . . . . . . . . .
CHAPTER
31
4.3
....... 32
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.4
Generator protection
4.5
Transformer protection . . . . . . . . . . . . . . . . . .
5.
5.1
5.2
5.3
Methods of coordination. . . . . . . . . . . . . . . . . . 52
5.4
6.
Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2
CHAPTER
...
....................
40
44
72
BIBLIOGRAPHY
....................
APPENDIX 1 .
Impedance data . . . . . . . . . . . . . . . . . . . . . . . . . .
77
Al.l
77
A1.2
78
A1.3
1 5 K V cable impedances . . . . . . . . . . . . . . . . . . .
79
A1.4
80
A1.5
APPENDIX
APPENDIX
APPENDIX
APPENDIX
2.
82
A2.1
82
A2.2
84
A2.3
System assumptions . . . . . . . . . . . . . . . . . . . . . .
84
A2.4
85
A2.5
87
A2.6
93
3.
98
A3.1
98
A3.2
115
4.
120
A4.1
120
5.
126
126
128
130
Cogeneration generator . . . . . . . . . . . . . . . . . .
132
134
136
A5.8
140
A5.9
142
.....
144
146
..
148
150
152
154
No.6 & 9
No . 14 & 15
A5.16 2.4KV 400HP motor 1 . D fan boilers . . . . . . .
156
No.6 & 9
A5.17 480V feeders ECR No.8 sheet 1 . . . . . . . . . . .
158
160
162
APPENDIX
6.
166
A6.1
166
167
168
169
A6.3
A6.5
A6.6
171
172
APPENDIX
APPENDIX
A6.8
173
A6.9
......
174
7.
180
A7.1
Type
180
A7.2
................
181
8.
182
LIST OF FIGURES
2.1
2.2
5.1
5.2
5.3
A2-1
A2-2
A2-3
A2-4
A2-5
A2-6
"A"
(momentary) . . . . . 93
"A". . . . . .
94
"A". . . . . . . . . . .
94
"A" (interrupting) . .
95
A3-7
A3-8
A3-9
A3-10
LIST OF TABLES
Machine reactance and multiplying factors . . . . . . .
Fuse classification. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current limiting characteristics of c-s one . . . . .
time fuse
Transformer ANSI data . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rating ratios for safe co-ordinations . . . . . . . . . . .
Power air circuit breaker minimum band . . . . . . . . . .
81
97
101
ABSTRACT
The
essential
devices
calculation
to
the
and
systems,
designer.
power,
ac
short-circuit
currents,
equipment
is
of
in
becoming
Today,
power
systems
carry
larger blocks of
building,
and
have
greater
safety
and
reliability
requirements.
fulfillment of
certain
criteria,
including
the
use
of
report
system
especially
others
who
engineering
valuable
electricians,
to
industrial
are
involved
practices
industrial
power
with
which
plant
should
engineers
application
be
and
engineers and
been
circuit
were
of
short-circuit-current calculation
breakers
selected
throughout
set
method
were
to
maintain
the system.
proper
relay
coordination
CHAPTER ONE
INTRODUCTION
All
power
systems, whether
industrial,
commercial,
purpose
providing
of
safely
or
residential,
electric
and
they
as
be
have
utility,
the common
energy
to the utilization
reliably
as is economically
equipment
as
feasible.
but
all
three
elements
must
be
taken
into
large
quantities
commercial
of
energy.
energy
usage
in
energy
usage
has
such
establishments
continuity
costs
of
enormous
handle
Many industrial
electric
production
considerations
in
power
downtime.
One
of
the
major
control
of
called.
outage
short
circuits
can
cause service
inconvenience,
extensive
interruption
equipment
damage,
of
essential
facilities,
power
the
system,
and
fault
this
accomplish
this,
the
protective
In order
flow
value
for
The maximum
with
calculate
method
of
this
information
short-circuit
report
and
is
procedures
currents,
and
to provide the
necessary
to
typical
time
short-circuit
relaying
of
purpose
curves
current
of
the
and
relay.
coordination
Calculation
of
of
protective
as
report
"the
portion
defines
detection
the
function
of
system
other
abnormality
occurs
which
report
will
be
limited to short-circuit
coordination
of
protective
calculation
and
low-voltage
and
institutional
devices
and
report,
which
buildings.
Bussmann
fuses
limits
our
relaying for
Westinghouse
protective
reviews
One
some
of
relative
methods
concerning short-
Two
explains
waveforms.
short-
of
and
explains
for
this
single-line
which
protective
Five
will
includes
as a single impedance.
in this report.
this report.
required
for
treated
which
calculation,
motors
Chapter
coordination
on
all
different
protection.
presented
circuit-current
impedances
together
be
devices
Chapter Four
used
for
system
explains
several
method
of
compared
the
report.
diagram.
Appendix
provides
protection
for
the
plant.
Appendix
provides
transformer
plant.
curves
and
detailed
Appendix
provides
used
throughout
fuse
curves
provides
and
Belle
the
used
the
in
diagrams
for
the
entire
system.
study.
this
report
(ASA)
functions
which
are
used
for
an
automatic
switching equipment.
There
are
short-circuit-current
several
texts
is
the
Coordination
Power
of
[6].
provide
relaying
Systems
especially
Most noteworthy
book
Protective
for
of
D.Dalasta
available
These texts,
an
understanding
and
their
of
the
function
of protective
1. 3
Protection
calculation
Longhand
computer
available
throughout
calculation, Network
the
Analyzer and
presence
general,
the
network,
high-voltage
digital
of
closed
loops
In
in the impedance
standpoint[l].
low-voltage
Radial
and
systems,
medium-voltage
systems,
can
be
easily
are
protective
power
systems
reasonably
Coordination
selectivity
currents
that
several
of
system operation.
1)
also
be
relaying
against
expected
to
for
available
for
industrial
and
in the course of
tables
assuming
flow
methods
that
identical
or
reduced fault
is, main-feeder-branch.
be
on
device
characteristic
selected
and
traced.
curve.
by
using
presented
recommended,
since
in
relay
report.
curve
is
This
drawn
points
require
knowing
the
by
is
finding
these
method
calculation of
relay,
short-circuit
circuit
current.
voltage
level
and
available
of
the
relay
to
the
CHAPTER TWO
If adequate protection
is
to be provided for a
be
current
considered
it
will
to
determine
deliver.
This
how
much short-circuit
open
power
a
short
protects.
When
currents,
short
it
determining
is
circuit
extremely
be
characteristics
the
of
magnitude of short-circuit
important
considered
and
the
impedance
1. Generators
2. Synchronous motors
3. Induction motors
these
can
2.1
GENERATORS
circuit
occurs
generator
on
the
circuit
fed
to
produce
continues
excitation
is
maintained
circuit
the
a generator, the
generator
circuit
and
by
When a short
to
current
the
is
short circuit.
limited
only
terminals
Synchronous
generators;
current
flows.
and
that
a
is,
motors
they
are
constructed
much
like
Normally,
is
reduced
Consequently, the
motor
stops
starts
delivering
slowing
generator,
down.
the
inertia
energy
circuit
current
impedance
of
produced
the
by
the
synchronous
motor
motor
I
UTILITY SYSTEM
TURBINE GENERATOR
SHORT- CIRCUIT
CURRENT FROM
E L E C T R I C UTlUTT
SYSTEM
METAL CLAD
SWITCHGEAR
CURRENT
FROM
GENERATOR
SYNCHRONOUS
MOTOR
TOTAL SHORT
CIRCUIT
CURRENT
-?OM ALL
FGUR
1
SHORTURCUlT
SYN MOTOR
SHORT-CIRCUIT
CURRENT FROM
lNWCTlCE(
Figure
INDUCTION
/1 "
'
The
motor
have
synchronous
same
motor;
The
flux
in
acts
like
flux
produced
by
the
This
synchronous motor.
The
induction
The
to
of
from
stator
external
when
not
from
source
rotor
an
external source.
However, if the
parts
the
flow
to
zero.
in
field
short
about
current
the
four
in
the
cycles,
since
synchronous machine.
11
The
flux
short-circuit
circuit
current
breakers
to
affect
the
momentary
duty
short
circuit
considered
in
short-circuit
depends
short
of
upon
short
by
current
produced
the
impedance
by
Hence,
motors must be
induction
calculations.
The magnitude of a
the
induction, motor
circuit
standstill.
circuit
produced
certain
circuit.
on
corresponds
Consequently, the
current
inertia
value
of short-
The
transformer
considered
speaking,
electric
from
the
sources
of
utility
electric
system
utility
short-circuit
or
the
system
current.
supply
are often
Strictly
the
change
utility
the
generate
system
neither.
transformer
is
system
generators.
voltage
and
Transformers merely
magnitude
of current but
determined
terminals
of
illustrated
symmetrical
sources.
or
in
short
circuit
figure
current
2.2,
usually
the
has
total
several
the
utility
synchronous
motors.
which
are
these
currents
the
in
located
machine
current
system
or both.
every
Because
after
decays
short
with
time.
So
even
though
only
the
2.5
The
primarily
for
of
rotating
machine
consists
transformer
variable
applied
impedance
with
to
time.
For
- T O T A L ASYMMETRICAL CURRENT
OC
COMPONENT
AC
(a) Symmetrical
COMPONEHT
(b) Asymmetrical
14
current
behaves
as
current
starts
out
steady-state
inception
voltage
the
high
value
and
decays
The
to
and
machine
value-to
initiated.
Expression
instant
of
of
the
variables.
Therefore,
simplification, three
generators
and
short-circuit
called
such
values
motors
for
for
the
sake
of
purpose
of
calculating
>
Subtransient reactance
of
the
occurs,
stator
and
it
winding
the
2)
Transient
following
reactance
onehalf
determines
the
current
controlling
to
(X'd)
value.
of the machine.
3)
Synchronous
determines
is
reactance
that
reached.
after
(Xd) is the
reactance
motors
have no field coils, but the rotor bars act like the
amortisseur
motors
to
Induction
winding
in
Appendix
reactances
(impedance
used
for
Refer
the
momentary
and
interrupting
The
describe
the
words
"symmetrical"
"asymmetrical"
envelopes
of
the
symmetrical
around
"symmetrical
current".
short-circuit
currents
total.
and
peaks
the
of
zero
the
current
axis,
they
waves
are
If
are
called
four
sources
combined
into
16
axis,
they
shows
the
Figure 2.2b
short-circuit
during
occurs.
the
currents
first
are
nearly
always
during the first cycle after the short circuit occurs and in
a few cycles gradully becomes symmetrical as shown on figure
2.2b.
Asymmetrical currents are analyzed in terms of two
components,
shown
figure
on
symmetrical
symmetrical
current
As
2.2b.
component
is
and
a dc component as
previously
discussed
the
the
the
circuits,
that
component
by
the
dc
resistance
component
is,
those
component
of
is
the circuit.
the
is
containing
In all practical
dissipated
circuit.
The
resistance,
as
rate
I2R
of
the dc
loss in the
decay
of dc
CHAPTER THREE
SHORT-CIRCUIT-CURRENT CALCULATIONS
The
maximum
magnitude
of
short-circuit current
must
be
well
as
to
mentioned
select
adequate
earlier,
there
interrupting
are
three
ratings.
basic
As
methods
of
and
longhand
system
to
use.
the
done
by
this
longhand
network
impedances.
Appendix
transformations
is
used
to
combine
2.
The
following
steps
identify
the
basic
>
Make
calculation
and
be calculated.
2)
Prepare
system
single-line
diagram
which
it
should
Prepare
system
impedance
18
the
interconnected
Identify
system.
5
>
Calculate
symmetrical
short-circuit
system.
6
>
Calculate
currents
interrupting
for
all
and
momentary
short-circuit
Certain
calculation.
only
factor
since
equipment
its
simplifies
the
full rating.
assumed,
because
calculated
selected
This assumption
values
are
maximum, and
The
system
one-line
diagram
is
fundamental to
19
short
circuit
analysis.
equipment
and
Refer
Appendix
to
components
The
circuit
impedances
short-circuit
patterend
current
from
of
control
currents.
for
the
Impedance
momentary
calculations.
system
the
that
and
magnitude
diagrams
interrupting
of
should
be
short-circuit
single-line
reactances.
transformer
should
generators,
high-capacity
compared
be
used.
The
transformers,
buses
(above
resistance
reactors,
1000
of
motors,
rating)
is
so
all
and
low,
of
the
cables
600 volts
and higher
Appendix 1 shows
it
has
been
single-line
diagram,
of
diagram
the
are
determining
1)
The
first
cent
ohms,
circuit
not
step
or
is
per-unit
impedances
Ohms are
ohms
from
one
This
report
voltage
in per-unit.
2)
The
second
represent
by
every
reactance
connected
bus" .
"infinit
so-called
internal
voltage
of
to
This
bus
represents
the
These
X= [MVAbaseI / [MVAUtilityI P e l l .
X=(XIfd%)[MVAbase/MVAgenerator1 P.U.
Motor X= (XI1d%)[MVAbase/KvAmo torI P.U.
Generator
Since
under
50
hp,
most
circuit
smaller
single
impedance
on
the
secondary
21
transformer.
reactance
for
the
This
of
slightly
momentary
slightly
will
and
higher.
Al-1
sequence
reactance
multiple
factors.
in
Appendix
shows
the positive-
multiple
selecting
motor
in
factor
current,
is
1.2
interrupting
current
circuit breakers.
for
case.
factor,
has
to
momentary
The
which
be
is
calculation
reciprocal
of
normally
six
multiplied
by
and
3.0 for
full load
3)
their
digram.
proper
location
to
complete
the impedance
3.4
All
buses
should
be
identified.
The location
circuit
currents
rating
A2-1
in
which
Figure
plant.
Locations
were
mainly
picked
feeders .
After
completing
the
impedance
diagram
and
the
one
diagram,
equivalent
reactances
is
used
in
Longhand
this
method
report.
If
of
combining
=equivalent reactance
e
X1,%,X3=reactances
b)
of circuit components
Xe=equivalent reactance
Some
by
merely
sytems
combining
For
shown
in
In order to reduce
used.
system
impedance
diagram
reactance.
The
calculation
to
derive
the
symmetrical
base
impedance,
quantities :
and
base
base current.
KVA, base
there are
voltage,
practice
voltage.
to
assign
study
base
the
KVA
the
base
It is
for
nominal
base
base
assigned
line-to-line
voltages.
circuit calculations:
For example,
system
The
Following
formulas
from
percent
on
an
base :
XpUNEW= (XpUOLD) (NEW
KVABASE/OLD KVABASE)
(OLD
KVBASE/NEW KVBASE
Ip.u.=Ep.u.jZp.u.
phase
short-circuit
[ZP.U.I
symmetrical
KVA, KVA=KVA(base) /Z (p .u . )
calculations
are
three-phase
EL-n =line to
I=E
L-n
/Z where
points
at
different
level
section
locations.
and
the
several
voltage
momentary
for
for
interrupting
current
for
different
fault
The
with
time
fact
has
that
led
the
to
the
stresses
due
to
interrupting
high
short-circuit
current
current
circuit
factors
to
of
may
account
at
be
the
rms
value
of
an
very
for
precise
involved.
the
Accurate decrument
the
method
been
This precise
evolved
whereby
protective-device
component
is
application, only
the
maximum
dc
26
applied to handle the maximum short-circuit current that can
occur in a system.
In
the
times
the
first
cycle.
multiplying
first
the
For
factor
cycle
average
to
circuits
calculate
in
three
phases.
breaker.
short-circuit
motors,
induction
motors,
subtransient
reactances
motors,
induction
and
and
utility
(Xud) of
motors
are
connections.
The
generators, synchronous
used
in the impedance
diagram.
Procedure
for
consists of calculating
the
breaker
impedance
at
this
divided
determining
momentary
current
by
at that point.
the
equivalent
momentary system
of
first-cycle
short-circuit-current
duty
per-unit
current.
if
proper
total
E/ZM
times
Where
IIC is the
first-cycle
short-circuit asymmetrical
current.
To
breaker,
the
the
time
required
The time
in
required
circuit-breaker
for
the
be
operating speed.
circuit-breaker
greater
will
maximum
interrupting
breaker
when
account
for
tripping
variation
is
to
contacts
imposed
part, the
Therefore, the
upon
the
circuit
the
circuit-breaker
operating
such
as
circuit breakers.
In industrial plants, eight-cycle circuit breakers
are
generally
contribution
motors
has
has
condition
part.
used.
disappeared,
changed
before
Normally,
induction-motor
the
Therefore,
the
contacts
of
unlike
other
methods,
neglected,
induction
This
cause
will
current
safety
motor
which
induction
transient
motors
are
for
selection
of
entire system.
Instead
short-circuit
by
of
specifying
time
at
which
the
a multiplying factor.
breaker
impedance
factors
at
to
divided
that
determine
and
then
applying multiplying
29
contact
parting.
for
motors,
values
used
with
transformers, generators,
and
utility
[I1
Type of Short-circuit
Rating
Synchronous
Motors
Induction
Motors
Synchronous
e a t o s
Multiplying Focmr
to be Applied
to Calculated
Syrnmehicoi
Value*
Circuit
Symmetrical Amperes
Available
Subtransient
(x7
Subtransient
(x?
Subtronsient
(x")
None
L-V Fuses
1-V Buswoy
k s &racing im
L-V Switchgear
1-V Switchboards
L-V Motor-controi Canters
L-V Panelboards
General
Caset
Interrupting--Symmetrical
+aperesor MVA
Available
Mocncntary-Asymmetrical
Amperes Available
Interrupting-Asymmetrical
Ampares Available
Subtransient
Transient
(xl)
1x1
Subtmnsient
(x")
Subtransient
(x?
Subtransient
(xl)
Subtransient
(x?
Sp&l
Caret
Noglut
1 .I
Subtmnsient
Subtransient
15$
1.27
CHAPTER FOUR
We
terms
of
usually
its
more
think
impressive
are
FOR PROTECTION
parts,
voltage
etc.
While
necessary
and
is one of these [ 3 ] .
The
protection
system
function
and
and
of
protective
coordination
its
components
is
and
limit
error,
system.
circuit
faulty
or
The
relaying
breakers
element
that
when
they
capable
of
disconnecting the
relaying equipment.
Overcurrent
coordination
protection
device
selection
and
science
and
should
objectives in mind:
be
designed
with
the
following
and duration.
isolation
of
protective
current
system.
of
short
circuits
equipment
which
requires
the
will sense an
wiring,
used
for
protection
are
overvurrent
relays,
4.1
OVERCURRENT RELAYS
Overcurrent
must
be
relays
are
of
the
system.
These
relays
may
be
either
They may be
33
instantaneous
current
time,
or
time
delay
in
response.
Various time
available
over
overcurrent
wide
range
of
current
setting.
The
current ratings:
Range
0.5-2.5
0.5,0.6,0.8,1.2,1.5,2.0,2.0,2.5
1.5-6.0
1.5,2.0,2.5,3.0,3.5,4.0,6.0
4.0-16.0
4.0,5.0,6.0,7.0,8.0,10,12,16
The
or
Taps
double
relay
consists
of
two
units,
an
The contact
current
flow
the
element,
current
has
proper
circuit
is
done
pickup setting.
instantaneous
element
is
34
higher
than
element.
in
should
operate
the
time-delay
aconnected
mainly
which
parallel
they
that
used
to
seperate
when
time
terminals.
interval
This element is
required
between
two
to
Appendix
(section
A5.12)
for
instantaneous
used
characteristics
various
tap
time
give
the
contact
closing
times
for the
In Chapter 5 several
4.2
FUSES
Fuses
protective
are
the
devices.
oldest
The
fuse
and
is
both
simplest
of
all
interrupting
device.
circuit
operate
by
and
the
basis.
elements
interrupting
the
They
are
are
current
one-shot
destroyed
flow.
devices
in
the
since their
process
of
ability
to
maximum
rating
short
interrupt
circuit
or
short
the
current
circuit
ability
by
current
up to their
interrupting
the
current flow
interrupting
capability
(3.3
fuses
should
not
times
fuse
rated
current)
at 0.01 second.
Since
current).
This
type
transformer is energized.
is
the
best
Table 4 . 1
Fuse Classification
Melting current
Interrupting
Average multiples
capability
of rating amperes
melt in
melt in
0.01 s
10 s
70
30
3.5
25
amperes
3,000
Rowan AIR-SEAL
one time
dual element fuse
1 Current
50,000
50)000
30
20
45
5.5
10%
;;;
15
2.5
100, 000
13
2.5
100 ,000
12
100 000
3.3
100,000
1OO)OOO
limiting
"Amptrap 60011
"Limitron"
G.E. "CLF-J"
I
I
Solid state
current limitin
,
I
I
37
COST
OF FUSES [51
Approximate
costs
of
fuse
types,
for
given,
NEC fuse
C-S one time
Rowan air seal
C-S trionic
Fusetron
Lo-peak
Current Limiting
Semi
On
for
50,000 amperes.
Chase-Shawmut
limiting,
time
fuse
Amptrap.
but
is
not
about
Table
so
one-time
much as Amptraps.
as
current
fuses
are current
A 30-ampere one-
limiting
as a 60-ampere
Available current
(
RMS
amperes
7.8
50,000
11
---
--- -"- - - -
16
--
24
35
-- ----
--
Fuses,
and
4.3
CIRCUIT BREAKERS
function.
In
the
case of medium-voltage
39
(1-72.5 KV)
separate
circuit
breakers,
protective
relays
the
sensing
devices
are
or combinations of relays.
In
devices
combination
either
of
may
external
breakers
protective
relays
or
relays.
molded-case
circuit
be
circuit
having
breakers
ratings
which
and
thermal
capabilities
of
their
major
1)
Rared voltage
2)
Rated frequency
3)
basic
are
combination
tripping
that
long-time
of
for
these
those
persist,
and
delay
and
instantaneous.
characteristics
low-level
The
short circuits.
New molded-case circuit breakers are equipped with
40
a
short-time-delay
instantaneous
characteristic
characteristic.
long-time-delay
and
provides
tripping
delayed
maximum
allowable
in
place
of
the
short-time-delay
characteristics
that
system
better
without
protection
(section
which
shows
Appendix
curve,
new
A6.7)
for
Refer to
The
protection
of
generators
involves
the
the
protection
unnecessary
not
try
of
any
other
system
element.
An
automatic protection.
The
practice
of
using
centralized
control
is
supervision.
41
was formerly the responsibility of attendants [ 3 ] .
The
generator
settings
following
protection.
of
protective
relays
used
for
generator protection.
relays
KVA or higher [ 3 ] .
best
for
the
are
the
practice
percentage-differential
relays
multicontact
relay.
,auxiliary
simultaneously
(2)
breaker,
mover
initiates
trip
field
(4) operate
and
the
is
trip
This
to
have
hand-reset
auxiliary
following:
(1)
trip
the
relay
main
an
alarm.
disconnect
generating
plants
may
be
impaired
below
The output of
57-57.5
Hz, so
OVER-VOLTAGE
RELAYS
generators.
additional
Then
if
It
operates
by
first
causing
resistance
over-voltage
trips.
OVER-TEMPERATURE RELAYS
Unbalanced
three-phase
double-system-frequency
iron.
cause
stator
currents
cause
operate
with
damage
such
to
conditions.
LOSS-OF-EXCITATION
When
operates
as
synchronous
RELAYS
induction
generator,
running
above
of
systems
a
cannot
tolerate
the
continued
In fact, if
43
excitation, widespread instability may very quickly develop,
and
major
loses
system
excitation,
When a generator
amounting
This
will
cause
most
selective
type
of
loss
of
excitation
relay
The
is a
relays
are
used
to
detect
motoring.
system,
considered
and
here,
not
for
the
generator.
However, it is
generator.
other
44
Note: refer to Appendix 3 for the types and settings used
for protection of the Belle plant generator.
The
function
of
automatically
transformer
protection
is
to
disconnect
1)
To
prevent
developing
current
higher-than-rated
in
and,
insulation
the
transformer
thereby,
or
temperatures
causing
conductors.
from
excessive
from
load
rapid deterioration of
Protection
provided
to.
2)
To
prevent
mechanical
and
thermal
effects
of large
damage
to
the
transformer.
Such protection is
3)
To
minimize
transformer,
the
and
spread
of
minimize
damage
inside
power-system
a faulted
disturbance
This
45
point
specifies
the
magnitude
and
duration
of
maximum
full-load
of
the
current
for
impedance
protect
the
as
shown
in
transformer, the
4.5.
table
primary
To properly
clear
of
delta-delta
bank,
and
delta-wye bank.
Irms (sym)
SYM.
rms
58% I
Fault PH-PH
FAULT
Delta-Delta
Delta-Wye
4% or
25 X Rated
22 X Rated
less
Current
Current
L-N
14 X Rated
11 X Rated
Current
Current
Current
16.6
X Rated
X Rated
Current
14
X Rated
9 X Rated
Current
12 X Rated
Current
TIME(s)
Allowable
Current
17 X Rated
7% or 1 4 . 3
more
SYM.
rms
20 X Rated
Current
87% I
Current
8
X Rated
Current
must
actuating
the
protective
current.
The
current
precise
vary
transformer,
Commonly
used
duration
of
inrush
can
only
be
determined
by
test.
equivalent
duration
should
and
specific
primary
magnitude
of
of 0.1 second.
safely
the
inrush
currents
which
operations.
Refer to Appendix 4 for tranformer protection used
throughout the Belle plant.
FIVE
CHAPTER
of
series
study
is
This
A
study
are
coordination
should
added
replaced
be
to
study
or
revision of a provious
the
system
or
when
existing equipment is
A coordination study
the
source
determines
to
plant
settings
or
is
increased.
ratings
This
necessary
to
study
assure
the
overcurrent
objective
of
coordination
characteristics, ratings,
protective
devices
is
to
settings of
minimum
unfaulted
devices
At
same
the
provide
load
and
study
time,
satisfactory
against
overloads on the
48
equipment,
and
interrupt
short
circuits
as
rapidly
as
possible.
5.1
In
protective
order
to
SHORT-CIRCUIT CURRENTS
The
following
information
on
short-circuit
(2)
Maximum
maximum
currents
are
used
currents
to
which
devices
respond,
to
the
instantaneous
and
direct-acting
and
to
trip
maximum
generation
will
49
breakers,
fuses,
current
at
interval
is
which
cables.
the
current
circuit
established.
(interruptig)
determine
and
The
at
protection
maximum
minimum
coordination
to 1 s
cycle
generation is needed to
circuits is adequate.
must
protective
of
coordination
devices
operation
because
plotting
the
relays
in
order
devices.
have
overtravel,
fuses
have
damage
time
interval
interval
is
instantaneous
is
usually
0.3-0.4 seconds [ 6 ] .
This
of
the
load
side
feeder
circuit
flow
the
lower
of current.
following components:
Circuit breaker opening time (5 cycles)
.08 seconds
Overtravel
.10 seconds
50
.12-.22
Safety factor
This
relays
and
is
with
inverse
somewhat
decrease
0.3
may
be
coordinates
very
margin
seconds
in
The overtravel of
than
time
0.3
seconds.
for
Seconds
inverse
time
relays,
interval
allowing
is
used
for
units
are
basic
characteristic
is
considered
the
times
as
shown
on
understanding
essential
to
any
of
study.
time-current
Time
0 is
the
curve
point.
for
the
source
experience
the
coordination
curve
is
arranged
so
that the
no
operation.
UJ.
of
paired
coordinates
of
times
corresponds
plotted.
to
current
along
ordinate
or
ordinates
of
the curve
contacts)
curve
should
be
drawn
for
any
device
under
consideration.
5.2
The
11
Apparent
power
and
voltage
ratings
as well as the
2)
Nameplate
ratings
and
subtransient
reactance
of all
3)
Relay,
direct-acting
trip,
and
fuse
ratings,
52
characteristics, and ranges of adjustment
Refer
plant
to
single-line
diagram,
which
includes
the
above
information.
The
second
circuit-current
requirement
study
is
complete
short-
third
characteristics
for
the
new
and
requirement
is
the
time-current
forth
requirement
is
Once
this
to
select
necessary
perform
pieces
their
of
information
the
assigned
equipment
is .assembled, it is then
protective
function
and
of protecting individual
There
coordination
system
are
several
available
abnormalities
utilization
to
on
methods
minimize
the
of overcurrent relay
the
system
effects
itself
or
of such
on
the
as follows.
1)
Coordination by table
2)
3)
Use
of
typical
time
curve
of
device
(new
method
method
mainly
uses
fuse
the
a
use
applications,
of
typical
combinations
selectivity
selectivity
of fuses.
of
coordination
class
and
type
check
for
selectivity
is achieved
ratio tables.
schedule
for
Table 5.1
various
fuses.
assuming
is,
main-feeder-branch.
can
be
accomplished
by
plotting
fuse
time-current
100 A
example,
current
54
5.2 shows
Table
branch
or
protective
in
main
or
coordination
device
and
main
between
or
the
supply
supply
circuit.
times
percent
should
protective
device
limiting
2.5
load
the
the
short
be
time
used
1.25 when
pickup
of
power
the
ratio
This multiple is
of
the
main
clearing
not
fuse.
exceed
side fuse.
time/current
the
compared
as
follows:
(1)
add
curves
may
be
current
values
percent
from
fuse.
The
percent
current
the
characteristic
the
downstream
55
s p r e a d w h i c h s h o u l d c o o r d i n a t e w i t h o u t damage t o u p s t r e a m
fuse.
More s p r e a d w i l l o f c o u r s e i n c r e a s e a s s u r a n c e o f
coordination.
2)
Branch
device
clearing
time
m u s t be u n d e r 80% o f t h e
Branch or
load device
one-time and
Branch or load
device
b
.
-- --
ratio
-- -- -" --
--
----
--.-----
ratio
1b2r-
current lim.
2.5
dual element
5.0
5.0
2.5
10.0
5.0
NEC
Molded case
air circuit
breaker
50 A
4.0
2.0
100 A
5.0
2.5
100 A
7.0
3.5
225 A
4.0
2.0
600 A
3.0
1.5
(heavy duty)
58
marked
on
the
bottom
of
Then proper
are
curves
calculated.
protective
device characteristic
of
placed
current
on
top
of
the
device
characteristic
curve, the
characteristic.
ratings
The
of
devices
being
studied
may
then be traced or
examined [4].
method
present
new
way
of
drawing
overcurrent
time
characteristic
relays
versus
curve,
Typical
multiples
overcurrent
relay
has
settings.
Knowing
the
of
tap
several
amount
of
curves of
value
tap
time
value
current.
and
Each
time dial
59
current
and
dividing
current
several
transformer
values
ratio
is essential.
By
ratio and the tap value, several multiples of tap values can
be found.
tap value can be found depending upon what time dial setting
have
been selected.
then
ploted
that
be
coordinated
of
0.3
In
is
are
curves
CO-9
of
overcurrent
relay.
EXAMPLE :
Figure
overcurrent
relays
need
detailed
involved
in
coordination
overcurrent
the
4.2 shows
relay.
portion
drawing.
with
the
other
portions
first
so
only
circuit
operate.
that
is
not
feeder
cleared
2A
yet,
shuts down.
If the short
available
short
circuit
at 46 kV level: 14,300 A
61
Maximum available short circuit at 12 kV level: 19,400 A
Since Bank No.1 is upstream in the system relative
to
select
the
following
setting
to
see
if
proper
is
/ (12) (40)=18.75
62
These
select
the
following
setting,
so
that
proper
A at 46 kV level
As
shown
operate
before
unit
first
Bank
2A
in
No.1. primary
relay
about
Both
relay
operation
were
based
tested
on
and
field
checked
for
proper
OVER C U R R E Y T R E L A Y
5 0 - 6 0 tiERTZ
V)
a
2
S
W
Y,
F i g u r e 5 . 1 T y p i c a l t i m e c u r v e s of t y p e CO-9
Relay [7]
I2KV
B U S '0"
--
--*-a3;7
--
OF PROTECTIVE DEVICES
5.4 TESTING
subjected
operation
to
of
abnormal
the
electrical
system
or
conditions
devices
and the
compared
to
2)
The
values
therefore
of
it
current
are
high
test
unit
In some cases,
5)
Trip
devices
must
be
allowed
to
(1)
timing
values
trip
of
unit
and
test
circuit
The recommended
rating.
Molded-case
precise;
however,
indicates
circuit
the
wide
breakers
may
be relatively
band
of operation.
will
take
abnormally
delay.
If
tripping
within
limits
of
affect
the
circuit
long
the
test
plus
or
minus
should be rejected.
should
tripping
be
will
magnetically.
calibration
set
run
marks
is
Testing
at
satisfactory.
one
of
the
lower
up.
LOW-VOLTAGE
Most
one
series
electrical
The
of
overcurrent
trip
device
per
phase.
The
operation
of
any
one
68
recommended
for
low-voltage
power
breakers
units if the
test
delay
is
short-time
breaker
recommended
three
delay
operate
it
pickup.
within
short-time
instantaneous
values
the
If
setting;
the
circuit
determine
the
PROTECTIVE RELAYS
The
protective circuit.
timing
should
relay
closes
given
with
the
its
check
relay
contacts
tap
in
be
within
its
designated
position.
It is
69
Based
equipment
on
used
above
in
the
methods
all
the
protective
as follow:
Minimum
less
than
pickup
not trip.
Time delay (LTD)
the
relay.
tripped.
The
The
time
LTD was
The
the
breaker.
operate
The
button
increased.
breaker
was
(STD)
pushed
All
when
test
the
is
dial
to
determine
is set at zero.
until
the
indicator
Pickup test
This
current
test
needed
is
to
close
particular
tap setting.
test,
equal
was
alternately
tap
increase
the
relay
contacts
for
any
value
plus
or minus 5 percent.
By
flickering
making
were
and
higher
indicates
breaking.
than
that
the
contacts
are "just"
too great and was adjusted for the correct tap value.
A
relay
timing
check
should
be
values
minimum
of
current.
Timer
selector
switch
initiate
push
button
vernier
controls
current
through
was
changed
pointer
Then
the
button
coil
was
and
to
set
timer
was
was
put
in "N.O.MOMENTARYtt
position, the
was
jogged
by
using
pressed.
reset
to
The
Some relay operating were too fast and the time dial setting
was increased up to 1/2 division.
CHAPTER S I X
CONCLUSIONS
This
report
has
short-circuit-current
coordination
relays
for
quick
and
isolation
recommended
for
many
computer
of
and
the
medium-voltage
systems.
contain
calculations
new
method
of
low-voltage
power
affected
industrial
portion of
and commercial
closed
technique
power
loops.
is
systems,
As
electrical
short-circuit-current
coordination
of
example
this
for
480-volt
protective
feeder
interrupting
devices
report;
show
breakers
ratings.
calculation
which
that
have
was used as an
adequate
Short-circuit
and
momentary
duties
of
and
the air
be
when
12-kV
transformer
significant
supply
each
12-kV
and
worst-case
73
symmetrical
interrupting
250-MVA.
approximately
to
the
system,
duty
would
be
reduced
to
its
components,
and
the
utilization
equipment it supplies.
Based
calculated
were
for
selected
isolation
of
the
short-circuit
occurs
in the system.
plant
application
planning
report
engineers
of
will
electrical
facilities
for
low-voltage
and
BIBLIOGRAPHY
System
division.
engineering
"Short
industrial
and
apparatus
distribution
circuit
current
commercial
power
sales
calculations
system^,'^
for
General
Donald
Russell
3.
4.
medium
Electric Co.
5.
size
industrial
plant,"
General
R.H.Lee.
IEEE
recommended
co-ordination
system,"
of
practice
for
industrial
and
protection
commercial
and
power
- )
If
Relay
instrument
Differential
Relay
division.
for
"Type
Generator
CA
Percentage
Protection,If
Westinghouse
1.L.41-331.2D,
Westinghouse
Electric
9.
instrument
Directional
Ground
division.
Relays
"Type
CWC
and
CWP
instruction," Westinghouse
1.L.41-242.4F, Westinghouse
Oct. 1975.
10. Relay instrument division. "Type SDF-1 solid state under
frequency relay instruction," Westinghouse 1.L.41-504.1,
Westinghouse Electric Co., Newark
11.
Relay
relay
department.
"Type DT-3
Westinghouse
instruction,"
1.L.41-552.1D,
Relay
instrument
Synchro-Verifire
division.
relays
"Type
CVE-1
instruction,"
and
CVE
Westinghouse
relay,"
Westinghouse
1.L.41-337.4F.
relays
instruction,
Westinghouse
, Newark, N.J.
Relay
relays
16. Relay
instrument
Westinghouse
division.
"Type
CV voltage relay,"
1.L.41-201K. Westinghouse
Electric
Co.
Relay
instrument
division.
relay," Westinghous
'I
Type
COM
overcurrent
1.L.41-102E.Westinghouse Electric
18. Relay
type
instrument
DS
Application
and
DSL
circuit
breaker,"Westinghouse
--
Positive-Sequence
First-Cycle (Momentary)
Calculation for
H.V. Breaker
Reactance
Utility Supply
XS
Plant Generators
X"
Synchronous Motors
XIf
Induction Motors
(Above 1000 hp >I200 rpm)
x1 r
.I' r
1.2Xlr
.25X"
Non-rotating equipment
Plant Generators
XIf
1 . 5X"
Synchronous Motors
Induction Motors
(Above 1000 hp >I200 rpm)
1.5Xlr
1.5Xlr
3.OXlr
Infinity
Non-rotating Equipment
lr = Locked Rotor, %=utility
reactance
V)
c
u
C
I . . . . . . . . . . . . . . . . . . . . .
~ , 0 0 0 0 C 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ~
$ ' N * 6 m W O m N m m * P O r n v N P P W
9
o
~ l I c om ~n -, o~ e . c ~: ~* m
m q - n e~ ~q o~ w* - no ~
m ~
c *y m~ v m c u @ ~ . m m
i * ~ * ~ ~ m m m m m m q q q q v q o n o o o
......................
X O C O O C O O O O O O O Q O C O O O O O O O
6 AhG
3 AhO
U O
ALtG
3/0 AkG
410 AkG
2 5 0 MC!A
300 MCM
3 5 0 !.CCU
400 YC!I
5 0 0 IACM
6a0 MCM
753 MC!A
1000 A!CN
12>0 ).{C!.i
15CC UCM
1750 MCX
2 0 0 0 MCM
Table A1-4
Coblo ria.
Ma 14 Awq..
. 0.3135
WalOAwq..
No.8Awg
0.1240
0.0779
0.W969
0.00150
0.CG781
0.313s
0.1210
0.0781
0.3133
0.1240
0.0779
0.006664
0.005745
0.005308
0.3291
0.1241
0.07808
0.0U741
0.00681
0.00623
0.0503
0.0325
0.0212
0.0493
0.0112
0.0197
0.004941
0.004619
0.004366
0.04944
0.03154
0.02017
No.Z/OAwq..
0.0163
0.0131
0.0106
0.00566
0.00567
0.00545
0.0173
0.0143
0.0119
0.0157
0.0125
0.0100
0.003961
0.003792
0.003677
0.01619
0.01304
0.01061
Wo.l/OAwg..
4
0A
.
2SO M C M . .
0.00860
0.0070a
0.00609
0.00535
0.00529
0.0056
0.0101
0.00817
0.00102
0.00800
0.00640
0.W7
0.003631
0.003313
0.003362
0.008785
0.007335
0.006527
0:00520
0.00461
0.00119
0.00519
0.00314
0.00506
0.00733
0.00690
0.00657
0.00460
0.00400
0.00354
0.003311
0.003U7
0.a3436
0.003791
0.005299
0.001923
0.0.00219
0.W95
0.W4
0.0061 1
0.00U1
0.00292
0.0010(
o.oo3wr
0.001018
0 . ~
0.003723
...
lb. 6 AwQ..
4A
.
.
Mo. 1 A
.
Mo. 1/0 Awq.
..
100 M C M .
...
..
350 M C M . .
400 M U . .
..
s
o ma.. ..
750MCM ....
0.0491
0.0118
0.0203
.-
s+k.an.lw)cr
t
foefar kv concctinq
mctoncm, 011 S U ~ S
of cabk
No. 6 to
No. 0 A r g
No. 8 A r g
0.8
Fa wrr.cclng r e d e a r n
fadom
0.96
No.0010
250 MCM
300 to
500 MCM
0.93
0.83
0.72
armor.
f o c t m for correcting ruistoncm
f o a a for ronocting
rooctoncm, all rizm
of coblo
0.17
1 .O
0.98
I / 1 / / /
230
System rdtogo
Coblo h e ,
91.3
................... 71.8
511.5
575
2,400
4,160
6,900
13,100
No. 4 to 1 Awg
24.6
15-14
1.075
0,351
18
11.5
0.669
0.222
0.11
9.4
0.581
0.194
0.0955
14.7
Cablo siro..No.
1 /0
0.0276
0.024
hrw nnglccarc)uctor
cobla in
ironconduit
n*eo-conducta cublo in imn conduit or i n t . r k c t d o-ad
coblo..
ecconductor cable in nommogwnetic+&
................
92.5
................... 68
.................. 34.8
23.2
14.83
0.953
0.318
17.1
10.9
0.6
0.2
13.72
1.1
Cable Six.,
$:
I
.............
.................... 61.4
.................. 51
0.0237
11.3
13-63 0.868
0.219
0.179
0.0796
0.01
0.139
O.W
0.0176
9.85
0.331
11.8
1.19
0.477
I I/
0.0943
APPENDIX 2
A2.1
DESCRIPTION
This
coordination
OF THE WORK
distribution
the
system
entire
for
the
power-house
Belle
plant,
electrical
(one
of
the
This
power-house
electrical
facilities
Modernization of the
will
improve
the
new
"A1' and
transformer
with
12-kV
feeder
power
house
breaker
in
will
new
7.5MVA, 46/12-kV
A secondary
complete
the
to
with
new
secondary
air circuit
new
incoming
switchgear
the
circuit
breaker
in
the
turbine
area
83
a block diagram.
T h i s s t u d y w i l l i n s u r e a d e q u a t e r a t i n g s of a l l t h e
air
circuit
breakers
and
proper
relay
coordination
throughout t h e system.
Utility
. W 9 9/1
,
t N t '0" 46Kv
n
Bus
B n k tb.7, IWcl
F i g u r e A2-1 Block d i a g r a m of s y s t e m s e t u p
A2.2
12-kV
Westinghouse
air
circuit
substation
breakers
as
12-kV
A2.3
SYSTEM ASSUMPTIONS
ANSI
calculation
voltage
The
of
circuit
procedures
Standard
fault
contains a guide
for
breakers
used
37.5-1969
in
rated
this
jX impedance only.
1.
line diagram.
The
used
as
line
diagram.
represents
and
480 volt.
and
treated
sizes
and
lengths
single-line
diagram
used
Figure A2-2
A2.5
few
easy
of
diagrams
(one-line
identification
circuits
into
itself
may
of
vs
impedance)
even
though
become
impossible
single-value
impedance.
to
analysis
of
voltage
levels.
voltage
will
be
current
and
base
can
then
diagrams
be
Base
derived
for
The base
the
as
shown
in Appendix 3. Impedance
value
of
per-unit
diagram
values
(figure
for
all
components
follows.
Utility:
X=5MVA/1020MVA=.0049 P.U.
Transformer (TI) :
on
Transformer(T2):
Zp=1/2(ZpS+ZpT-ZST)
=1/2 (5MVA/15MVA) (19.66%+7.91%-18.83%)
=
.0146 P.U.
Zs=1/2(2PS+ Z ST-Z PT)=1/2 (5MVA/15MVA) (19.66%+18.83%-7.91%)
=
.0509 P.U.
ZT=1/2 (ZPT+ZST-ZPS)=1/2 (5MVA/15MVA) (7.91%+18.83%-19.66%)
=
,0118 P.U.
Transformer (T3) :
X= (5.09%)(5MVA/2.8MVA)= .0909 P . U.
Transformer (T4) :
Transformer (T5) :
Transformer(T6) :
Transformer(T7):
Generator : X1'=5MVA/102MVA=.
049 P . U.
Motors :
Typical
follows.
calculation
Appendix
for
1
will
2.
3X1r
Cables :
The
per-unit
determined
by
values
of
all
the
values
feeders.
will
voltage,kVLL) /base
MVA3phase
copper
magnetic
and
/5MVA=28.8 ohms
cables
in
magnetic
therefore:
and non-
Z=( R ~ + x ~'I2=
) [ ( .0279)2+ ( .0317)2] I/'=.
0422ohms/1000f t
50ft(.0422/1000ft)=.0021ohms/50ft
Per-unit impedance=.0021/28.8=.0001 P.U.
2.
correction
factors
for
non-magnetic
ducts.
For
R=.00208ohms/100ft
for
be
used
for
This information
91
Multiplying
factors
ground faults.
Figure A2-4
A2.6
The
system
simplified
impedance
The
Wye-Delta
transformation
for
fault
"A" is
'Tp,u,
1
Infinite Ru
Infinite Bus
mgQTA
,kw
P.u.
0 P*u*
,85337
D.il7*i/Zb+iizcrJ82.e C
Za&DZ~W(,W9)(.OiG)=,8216p,u.
&DZbfc=382(.81G)(.83397)=.
1487 p.u.
Z;lcrDZdc=W(.W9)(.83397)=.8583 p.u.
Infinite Bus
I
.P.U.
5263
P.U.
,8146
p*u.
8123
p.u.
*em
P*U.
"
"
Fault 'A'
To s i y l i Q this portin of t h c i r r i t . W-DELTA trrrrfmtim
is brar wrd.
95
The
system
simplified
impedance
Infinitr RJS
The
Wye-Delta
transformation
for
fault
"A" is
-BASE M V A / (kYLL
~
BASE) 103=5 ( l o 6 ) / 1 2 (103)\/T = 2 4 0 A
IBASE-
IS C=IBASE /XthP . U . = 2 4 0 / . 0 1 3 2 = 1 8 , 2 0 0 . 0 0 A
The
used
for
same
other
calculations
for
method
locations
other
the
points
in
system.
Result
table A2-1.
Infinite Bus
Infinite Bus
UYE
Infinite Bus
-> DELTA
Infinite Wu
I
T
of
WYE-DELTA transformation
T a b l e A2-1 R e s u l t of B e l l e P l a n t S h o r t - C i r c u i t S t u d y
----.
F a u l t Location
Momentary S h o r t C i r c u i t C u r r e n t ;i
B a s e 5 MVA
Amperes
MVP.s~
I
--
.-----
.--
..-----
F a u l t "B" 46 KV
Fault
l f ~ l l
46 KV
14,326
F a u l t "A" 1 2 KV
19,400
F a u l t "D" 2 . 4 KV
17,480
F a u l t "El1 2 . 4 KV
27,097
F a u l t "F" 2 . 4 KV
F a u l t "MIf 2 . 4 KV
10,400
Ii
F a u l t "I" 4 8 0 V
F a u l t "K" 480 V
..
---
40,880
63,123
64,317
F a u l t Location
1140
17,660
F a u l t " N " 2 . 4 KV
1140
L
53
-.....-..
B a s e 5 MVA
Amperes
F a u l t "B" 4 6 KV
14,036
F a u l t "C" 46 KV
14,036
F a u l t "A" 1 2 KV
18,178
378
F a u l t "Dlf 2 . 4 KV
13,136
52
F a u l t "Elf 2 . 4 KV
22,396
89
F a u l t "F" 2 . 4 KV
12,923
51
F a u l t "MI1 2 . 4 KV
8,010
32
F a u l t "N" 2 . 4 KV
37,240
148
F a u l t "1"480 V
48,440
40
1 F a u l t "K" 480 V
48,600
40
MvAsc
1121
1121
APPENDIX 3
BELLE PLANT GENERATOR AND BUS PROTECTION
A3.1
type
CA
10
percent
setting
only
setting
required
on
the
indicating
volt
tap
setting.
A tap is used
relay:
1) The
maximum
fualts
at
and
the
minimum
relay
ground
and
fault
current for
These
2) The
maximum
voltage
should
and
values
be
minimum
for
residual
the
polarizing current
faults above.
(IU) or
These values
Cuur 5.rr-
H;
La t .
#&.A
rc%v e u i
ZOO/*
SFF
YRCT
Ull.Z,'l4
uua-
occa3Sq
3) The
generator
is
down,
either
fault
F1 or F2 can see
current I1
Secondary current
(I1)=Isecondary/C.T. ratio=50/10=5
Product of
(IUXT1)
=25 and IU/I1=l.0
OCCRATINO C O K A Y C C R C S
Figure A3-1
R=M
( 1 I u ) select
tap)
=25/1( .25)=I00
from
dial=2
figure
A3-3
Note :
The
typical
time
curves
curve
shown
on
figure
A3-3,
(K) in amperes.
Figure
A3-3
typical
time
curves
of
- -
the
ground
= 50amps.
generator
using
figure
A3-2
figure
R=4 (100/50) =8
.25)=200
+ 5(.0167)=. 18 s
Since
relay
is
proper
delta
follows:
Set: Upper tap=l
Lower tap=.25
Time dial=2
relay
is
P.T.=
transformer,
permitted
relay
is
energized
12000/120=100
from
volts,
maximum
potential
voltage
1.05(120)=126
volts.
Type
volt/hertz
for
.lvolt/hertz
maximum.
form
generator
increment.
is
1 . 2 per-unit.
Relay setable
because
single
of
field
circuits
single
SG
type
in
any
way.
transients [ 4 ] .
W3-UT21-21
E2,
value of under-voltage,
this
relay
functions
approximately
on
This
to
figure
curve.
A3-5
drawn
on
an
severely
reduced
or
lost.
By
107
within the relay characteristic, the relay will operate when
the
generator
field
breaker
As
Zc=.08(19.776)=1.58 ohms.
(SA) must be greater than or equal Z
'base
A' therefore:
19.7(SA)>
39.16, then SA must be atleast 3.0, so set S
A
for 6(Sc)>1.58.
setting required.
Set TC tap=1.84
Set TC
Figure A 3 - 6
relay
to
Using
Set timing
From
-701
Ifullload--
200/1 and
frequency
at
which
tripping
declining
frequency
conditions.
frequency
continues
to
for
the
relay
takes
placeunder
crossed.
For
constant
H=2,
it
is
required
below
57.5Hz
relay
figure
6Hz/s
A3-7
rate
indicates
of
that
decline.
Assume the
delay setting will close its trip contact when the frequency
112
has
dropped
overload
condition.
acceptable
time
Thus
delay
15
setting
cycles
to
is
the
maximum
obtain
the
desired
protection.
In this system the relay is set to trip at 57.5Hz,
30
cycles
frequency
delay
relay
provided.
setting
for
this
type
of
relay is 120
set
relay
at
115
degrees
C to provide operator a
RATE OF FREQUENCY
H-2
H=4
10
20
10
20
30
40
50
30
D E C L I N E . HZ / SEC.
40
60
70
80
1
90
60
100
120
140
(ASSUME LOAD
70
50
.as)
follows:
will not operate when the system are swinging too fast. From
figure
A3-8
(Westinghouse)
for
relay calibrated from factory, set the time dial setting =1,
then the operating time will be about 2.8 seconds.
It
time
dial
is
equal
[I21
Automatic synchronizer W
The
to
be
U (Westinghouse)
altered
that occur.
Voltage acceptor: Lower limit 110 volts
Upper limit 120 volts
Difference limit 5 volts
Voltage matcher 2 volts times 3 second
Pulse duration time .25 second
Field
KAB
relay
of
bus
the
differential
is an instantaneous
The
following
type
1)
relay
points
To
faults,
than
the
knee
voltage
voltage
unit
Vk, value
of
poorest
ct which is
4)
To
The
knee
extention
saturation
in figure A3-9.
voltage
of
two
the
curve,
straight
ordinate
line
and
portions
abscissa
of the
must be same
equation
Imin=(XI,+IR+IV)N
Imin=minimum
,where
current,
RMS. Ie=ct
secondary
voltage.
equal
,the
IR--Current
in
in
varistor
value
of
to
internal
excitation current at a
setting
value
V-unit.
at
N=ct
of
V-unit.
VR. I ~ C u r r e n t
circuit
fault
turn's
Device
maximum
ground
fault
is
the
MVA
M V A / (~1 2 ~ =24
~ ) KA
sum
of
=.471 ohms
( R +R
~ L)IF/N=63 From figure A3-10
Unit setting=3 A (rms)
2.4KV
Bus
differential
R S+RL- . 8 9 ohms
( R +R
~ L) IF/N= ( .89) (48,000amps/400) =106.8
From figure A3-10
Figure A3-9
setting is 3 amperes.
.T .
C . T. Saturation Factor
101.5
= 6 circuits
IE = .015 A
VR=120 volts
1 . 0A
APPENDIX 4
BELLE PLANT TRAiiSFORMER PROTECTION
A4.1
(Westinghouse)
In
and
check
order
current
to
transformer
performance
the following
information is required.
4) One
Definition of terms
same
as
=Maximum
symmetrical
external
fault
current
in
secondary
burden
in
ohms
(excluding
Calculation procedure
Three-winding transformer bank N0.7
High
Intermediate
(KVA)M= 15MVA
(KVA)M= 15MVA
Low
(KVA)M= 15MVA
current
1)
300/5 C . T. ratio
1 ~ ( i n t e r m . ) = 1 5 , 0 0 0 ~ ~ (12KV)=721
~/'~~
A 1200/5 C .T. ratio
I (low) =l5,OOOKVA/'F
(2.4KV)=3600 A 5000/5 C.T. ratio
P
2)
Is(high) =Ip/N=188/60=3. 13 A
IS(interm.) =Ip/N=721/240=3.0 A
IS(low)=I,/N=3600/1121=3.22
IR(low) =IS(low)=3.22 A
TAPhigh=TH=3.
2 (3.13/3.22)=3.11
TAPinterm.=TI-3.2 (3.0/3.22)=2.98
TAPlOw=TL=3.2
3)
Mismatch calculation
High side
%Mismatch=100 [(IRhigh/IRinterm. ) - (TH/TI) ] /S
S=The smaller of IRhigh/IRinterm. or TH/TI
TH/TI=3.2/2.9=1.10 and IRhigh/IRinterm.=3.13/3.0=1.043
Then S=1.043
%Mismatch=100(1.043-1.103)/1.043=-5.79
Intermediate side
%M=lOO [ (1,intex-m. /IRlow) - (TI/TL) 1 / S
T /T -2.9/3.2=.906 and I interm./I low=3.0/3.22=.932
I LR
R
Then S=.906
%M=100(.932-.906)/.906=2.87%
Low side
%M=lOO [ (IRlow/IRhigh) - (TL/TH) ] /S
4)
H A
ZT=1.13(.5)+0.15/3.2=.61 ohms
Np=N/NT=60/60=1
NP(VCL/lOO)>ZT,
Intermediate side
C.T.=1200/5
RL=.471 Q 75 degree=.396 Q 25 degree
ZT=1.13RL+.15/TI=1.13(.396)+.15/2.9
since 1(200/100)>.499,
then it is 0.k.
Low side
Tintermz3
'
T ~ o=3.2)
w
type
SC
current
range
proper
40
to
Dropout ratio for a-c is between 90-98% and for d-c would be
65-80%.
The proper adjustments to insure correct operation
of this relay have been made at the factory.
Range=40-160 amps.
Circuit switcher interrupting rating =8,000A
for primary faults. Primary C.T. ratio=200/5=40/1
125
160(40/1)=6400
the
relay.
before
No.2
126
APPENDIX 5
DRAWINGS
A 5 . 1 "A" s w i t c h h o u s e , Bank N o . 1 and 1 2 k V B u s " D M
A5.1 continued
Refer
relay curves.
FROM IZKV
2
UNIT
SWGR
A5.2 continued
Refer
r u 4 i~L
clALn/Fz43n
c m ~ mrm
r
Ln
A5.3 continued
Refer
relay curves.
ZEPO SEQUENCE
!'
A 5 . 4 continued
A5.5 continued
Refer
relay curves.
A 5 . 6 continued
CuQRErJT
RELAY
# 5 B ~ I C E RFEEDWATER
PUMP
A5.7 continued
Refer to Appendix 6 section A6.9 for selection of type AA12P
overload relay curves. Fuse curves are shown in Appendix 7.
-------- -.--
- - -,,*--
.----..--.-.
--:
------.
-----.-A
I
.-,--...-.----
---
.
1
.
.,.*-
. . L
... .
..
-..-..
. - - - ----,
U v L r m r ruu cunxrwr IN A
n s x a X & A T ~xv.
A
- -- - . -
- -
A 5 . 8 2.4kV 7 5 h p m o t o r a s h pump
Z 4 K V UNIT 3 A
p;RuADa
(3
50/5
L.R.
OVER
CURREUT
RELAY
A5.8 continued
Refer to Appendix 6 section A6.9 for selection of type AA12P
overload relay curves. Fuse curves are shown in Appendix 7.
N A I L CI
/%-A
--
mmarrcrIS_n
a l m H
cr
&
m rm r r r rn
nnmnro-H
1 U I L -
Cf -,%-A
cmlr miu
Imr mu *
n
u
l
m u R - X
A 5 . 9 continued
UNIT
F.D. FACJ
68
A5.10 continued
Refer to Appendix 6 section A6.4 for selection of type CON-5
overcurrent
relay curves.
.AN<
'60
5250 KVA
I2KV /2.4KV
&,
A5.11 continued
Refer
relay curves.
MULTIPLY $CALL C U R R E N T IN A M P E R E S
X =AT-?&
KV
SECIPC,
PUMP
A 5 . 1 2 continued
Refer
relay curves.
BANK
4GKV
4CKY
*7
1 5M V A
IZKV
IZKY
A 5 . 1 3 continued
Refer
to
selection
Appendix
of
respectively.
type
CO-7,
CO-9
and
CO-11
relay
curves
A5.14 continued
Refer
type
relay curves.
UNIT 4 A
UNIT 4 6
A 5 . 1 5 continued
Refer
type
relay curves.
-+-nn
TY__ IL
er
nanmrrcr>
al
mlDAsl
mr-m-I2
--
1
U
1
1
-
' 5 - n
c w n mrrcr
n
CT
.n ma-um
ur-m-x
'
CI
'OAT=
KV.
-,
/
U IL
L-/I
n
UNIT 4A
UNIT 4 8
A5.16 continued
Refer
type
to
relay curves.
(n
roowe
4-
cr. -R--n
NLllRUM&#V
mr m m w R
cr. a ,%>/I
m ~ mrm
r Ll
LV
N%TLL_!
Lr-,%
c:m11 YalW
NI-;anvrunr
m1'mb
an
BLLI
rm-
L I
cm
i 11Y a r m
-<'
A5.17 continued
Refer
type
A 5 . 1 8 4 8 0 V f e e d e r s , ECR No.8 s h e e t 2
BLR* 9 MCC
=Rat4
MCC
BLR'ISUCC
AS.18 continued
Refer
type
AS.19 continued
Refer
type
A 5 . 2 0 2.4kV 5 5 0 h p motors
A5.20 continued
Refer
type
relay curves.
APPENDIX
WESTINGHOUSE
OVERCURRENT,
Over C u r r e n t R e l a y [ 7 ]
V)
Q
2
0
U
W
Relay
9 10
12 14 16 18 20
M U L T i P L E S OF T A P V A L U E C U R R E H T
T,r
cul T
C , r v e q i thr T v o e
CO 9
RCIO~
A 6 . 3 Type
TIME D I A L
SETTING
T y p , c o l Trme C u r v e o i the T y p e
C O -l i Relay
'
I , ,
,.*
TYPICAL T I M E CURVES
OVER CURRENT R E L A Y
8 910
30
28
26
24
22
20
18
v)
16
0
U
W
v)
14
12
10
1)
1C
2C
30
40
50
60
7G
80
90
0
1OC
P E A C E N T TAP V A L U E V O L T A G E
TIP,cal60-crcle T ~ , ~ W C U ~
or* tho
O S t y p o C V 2 S h o e T ; m * Undorvoltope R e l o r .
A 6 . 6 Type CV-7
Over a n d Under V o l t a g e R e l a y [ l G ]
T r P . < a l Y 1 - c y c ~ +t ~ m rc v r e x o f t h e t y p e C V 7 I h r r T . 0 . Ow..
o l d Umd.rroltap*
R.iey,
A 6 . 8 Type DSL-206 L i m i t e r s [ 1 8 ]
"
- M
"
IN SECONDS
"
'
---"I
I
---.--. . .--
nME
- n - - - -
,.__,
LIW'
TRIP
--
- - A--L,
&-I
.-.-.-
L+--J--&+
-.+-,-_LJ--.
--..-,.z
I
-
II
_ . . - ' . n . . o
I.
L.
,#
G.
. .
" "
"
"
c,
.
)
U
..--;
-.
"- -
.(
-3
. ..
- .- .. .
---&i
i..---Lm - T f --I7
3
f $ 'i~bl'tj
A 6 . 9 Continued
- -
- - - - o
I.
...........
-- - --
." . . . . . ... . . .
'"
-
+:-
'
., ,.o - .-
0
0
,_ _.
---,
--
-----
---.
...?
. . . . . . . . . . . . . -. .,. . .,.
,
> - .
--+
4
1,.
-0
. ! *
'.-. . . . . . . .
.
.
., & , , . .
--
"
. . . . . . . .
.
. . < . .
'r)
. .
. . . . . . . . .
.
.I
-c
7 . y
L l n O i - . - & - -
uo---
..........
--.--..
- 1 ,
-,..-..-+-8
- - - ------
-_-A
TRtP T I H E
---i-.-
--,-.----
3-t
. .' - r
I
..........,..................
...
I.:
;-.,
: - , .
--,
....
_ . _ _ - - .. . . . . . . . .
-.-2 Zd:6i
SECO&JDf
f IIS6,jf
1.-
.,A.
b:
A 6 . 9 Continued
f R I P TIME IN SECONDS
4hl, ----
.- .
...
xw
.m
.
-. .-
.l
I . .
- - --.
...-
,i-.-
+
~ --,.- + - k. t f "----i-C
- l.--. - ----- r
.
i+*
..
L.-.
-----..
--I
-..
. - ",
"
4.-
..
-..
. . . . .
-. . . . . . . . . . .
. - - - i d .
6.--
.
I:
I . -.
. ! :... .--r.-. :
. .
. .
L I-
::
.
.
3m
...
. .
........
.-----.
-T7
., - 4 -.w
7:-=-
r r g r z x i
T R I P TIWE IN S E C O N D S .
"
2
522i!?f
1rZa
A 6 . 9 Continued
IN SECONDS
TRlP TtME
LX:,
- l .
----------. .
...
. r
-----i . ? .
..-.--.---...A-
L...
--..
.-..
L..
-.,
-.
-.---.
. , #
, ,.
i--1--7-
ta
-.
.-
- -. - -..--
..
I
.
.
-.-,
,
--*
<,.*.
rur
-0
.-------.-,--.-..
: .,- --.--.---: -..-. :--!A_
--;..-____
,-,-r*+-,l---.--*
__;
--, .
-----..
- ..
-..-1 . L - I
-.--..
- . . --.. ...-..-- --. . - .
._A
'
"
- - - a -
L
U
. ..-----
_ _ #
TRlP T I W E IN S E C O N D S
'
.-.
-1
8Z.i:
f 5 3
1M
\..-
A 6 . 9 Continued
T R I P TIME IN SECONDS
A 6 . 9 Continued.
L47.2 Type
KRP-C H I - C A P F u s e s ( 6 0 0 ~[I91
)
APPENDIX 8
AND FUNCTIONS
AND FUNCTIONS
device
within
function
the
device
number
which
symbol
on
is placed adjacent to or
all
wiring
diagrams
and
arrangement
be
readily
which
the
was
adopted
American
The
Standards
following
Association
is
list
and
of
appear
FUNCTION
ASA
in
AND DEFINITION
.1
Master Element
Overspeed Device
Synchronous speed Device
Underspeed Device
Speed or Frequency Matching Device
Reversed for future application
Shunting or Discharge Switch
Accelarating or Decelerating Device
Starting to Run Transition Contactor
Electrically Operated Valve
Distance Relay
Equalizer Circuit Breaker
Temperature Control Device
Reversed for future application
Synchronizing or synchronism Check Device
Apparatus Thermal Device
Undervoltage Relay
Reserved for future application
Isolating Contactor
Annunciator Relay
Separate Excitation Device
Direction power Relay
Position Switch
Motor Operated Sequence Switch
Brush operating or Slip ring Short cir. Device
Polarity Device
185
Time delay Stopping or Opening Relay
Liquid or Gas Pressure, Level, or Flow Relay
Ground Protection Relay
Governor
Notching or Jogging Device
A-C Directional Overcurrent Relay
Blocking Relay
Permissive Control Device
Electrically Operated Rheostat
Reserved for future application
D-C Circuit Breaker
Load Resistor Contactor
Alarm Relay
Position Changing Mechanism
D-C Overcurrent Relay
Pulse Transmitter
Phase Angle Measuring
A-C Reclosing Relay
Reserved for future application
Frequency Relay
D-C Reclosing Relay
Automatic Selective Control or Transfer Relay
Operating Mechanism
Carrier or pilot wire Receiver Relay
Locking out Relay