2

EQUIPMENT BASE

MAX

#4@12" EW

NON-SHRINK GROUT
3/4" CHAMFER, TYP

d + 1", MIN
INSIDE DIAMETER

2 - #4

2 - #4

SLEEVE, SEE NOTE 2

@ TOP OF PAD

#4@12"
MIN 4 PER PAD
(#5@12" FOR AB 3/4" DIA
OR LARGER)

SUSPENDED SLAB OR SLAB


ON GRADE; FOR REINF AND
THICKNESS NOT SHOWN SEE PLANS

MAX

3/4" CHAMFER, TYP

ADDL #4@6"
FOR PAD HT > 10"

ANCHOR BOLT SLEEVE

CONSTRUCTION JOINT
TYPE A

@ TOP OF PAD

ADDL #4@6"
FOR PAD HT > 10"

SEE NOTE 7

EXST SUSPENDED SLAB


OR SLAB ON GRADE, FOR
THICKNESS SEE PLANS

ANCHOR BOLT,
SIZE AS SHOWN
OR AS REQD
BY MFR

PROJECTION
AS REQD
TOP OF
CONC

ANCHOR BOLT, SEE NOTES


& ANCHOR BOLT DETAILS

3/4" CHAMFER, TYP

2 - #4

@ TOP OF PAD

3/4"
CHAMFER,
TYP

EQUIPMENT

d + 1", MIN

CONCRETE
ANCHORS,
SEE NOTE

ANCHOR BOLT
SLEEVE AS SPECIFIED

FINISH
GRADE

GROUT

FILL BLOCKOUT
W/ NON-SHRINK
GROUT

TOP OF CONC
EQPT PAD

TOP OF
STRUCTURAL
SLAB OR
BEAM

DEPTH
AS REQD

CONC SLAB
OR BEAM

NOTES:
MACHINERY ANCHOR BOLT DETAIL

ADDL #4@6"
FOR PAD HT > 10"

SEE NOTE 7

ANCHOR BOLT RETROFIT

REMOVE FORM AT
TOP BY CUTTING
AFTER CONC IS
CAST AND PRIOR
TO GROUTING

CONC EQPT
PAD HEIGHT
6" MIN, TYP UNLESS
NOTED OTHERWISE
ON PLANS

MAX

ANCHOR BOLT SLEEVE

6d, 4" MIN CORED


HOLE IN EXST CONC

TYPE F

EQUIPMENT BASE

1 1/2"

ROUGHEN
EDGE, CLEAN
ALL AROUND

CONSTRUCTION JOINT,
ROUGHEN & CLEAN
PRIOR TO PLACING PAD

#4@12" EW

FILL WITH
NON-SHRINK
GROUT

1/8" PLATE
WASHER,
3" DIA MIN,
SEE NOTE 2

#5 ADHESIVE DOWEL
@ 12" MAX, 4 MIN,
EMBED PER SPECIFICATIONS

ANCHOR BOLT SLEEVE

4 1/2" MIN ALL AROUND

3" MIN ALL AROUND

PROJECTION
AS REQD

PROJECTION
AS REQD

ANCHOR BOLT, SEE NOTES


& ANCHOR BOLT DETAILS

1 1/2"
1 1/2" FLUID
NON-SHRINK GROUT

SEE NOTE 7

ANCHOR BOLT,
SIZE AS SHOWN
OR AS REQD
BY MFR

EQUIPMENT BASE

3" MIN ALL AROUND

ANCHOR BOLT, SEE NOTES


& ANCHOR BOLT DETAILS

1 1/2"

SEE TYPICAL
EQUIPMENT
ANCHOR
BOLT DETAIL

TOP OF CONC

#4@12" EW

1 1/2" FLUID
NON-SHRINK GROUT

4 1/2" MIN ALL AROUND

3" MIN ALL AROUND

1 1/2" FLUID
NON-SHRINK GROUT

1. FOR CONCRETE EQUIPMENT PAD DETAILS


AND NOTES NOT SHOWN SEE
3356

3" CLR,
ALL AROUND

ELEVATION

ANCHOR BOLT DETAILS

2. MATERIAL TO MATCH BOLT.

NTS

3. d DENOTES ANCHOR BOLT DIAMETER.

ANCHOR BOLT BLOCKOUT

1
1.5

SUSPENDED SLAB OR
SLAB ON GRADE; FOR
REINF AND THICKNESS
NOT SHOWN SEE PLANS

CONSTRUCTION JOINT

PAD HEIGHT AS
REQD, 3 1/2" MIN,
10" MAX

EQUIPMENT PAD
3/4" CHAMFER, TYP

#4 ADHESIVE DOWEL
@ 12" OC @ PERIMETER
SEE SPECIFICATIONS

NOTES:
1. WHEN ANCHORAGE OF EQUIPMENT
TO PAD IS REQUIRED, USE CONCRETE
ANCHORS SPECIFIED.

CONSTRUCTION JOINT,
ROUGHEN & CLEAN PRIOR
TO PLACING PAD

2. CONCRETE PADS FOR ELECTRICAL


EQUIPMENT SHALL BE 3 1/2" HIGH,
UNLESS NOTED OTHERWISE.

EXST OR NEW SUSPENDED


SLAB OR SLAB ON GRADE,
FOR THICKNESS SEE PLANS

TYPE E

CONCRETE EQUIPMENT PADS


NTS

R EG IST
ER
E
JO

S
D
No. M32039

INEER
NG
E

O FESSIO
NA
PR
L
E. SIMO
N

N
H

A
EC
H A N IC

N
IA

T
S

M
T

O
O F CA LIF

IC
H

REG
IST
E
R
M

CENTERLINE OF WALL

2. THE SIZE, NUMBER, TYPE, LOCATION, AND THREAD PROJECTION OF THE ANCHOR
BOLTS SHALL BE DETERMINED BY THE EQUIPMENT MANUFACTURER AND AS
APPROVED BY THE ENGINEER. ANCHOR BOLTS SHALL BE HELD IN POSITION WITH
A TEMPLATE OR OTHER ACCEPTABLE MEANS, MATCHING THE BASE PLATE, WHILE
PAD IS BEING PLACED.

4. ANCHOR BOLT SLEEVES SHALL HAVE A MINIMUM INTERNAL DIAMETER 1" GREATER
THAN BOLT DIAMETER AND A MAXIMUM INTERNAL DIAMETER 3" GREATER THAN
ANCHOR BOLT DIAMETER. SLEEVES SHALL BE FILLED WITH NON-SHRINK GROUT
AFTER BOLTS ARE ALIGNED. SEE 3357
.

3"

ADJUSTABLE
PIPE SADDLE
SUPPORT

STD PIPE FLANGE.


ATTACH TO CONC
WITH ANCHORS
A
1 1/2" GROUT

A
2-1/2"
2-1/2"

4"

3"

6"

3"

8"

3"

10"

3"

12"

3"

14"

4"

16"

4"

20"

6"

5. EQUIPMENT BASES SHALL BE INSTALLED LEVEL UNLESS INDICATED OTHERWISE.


6. WEDGES, SHIMS, OR LEVELING NUTS SHALL BE USED TO SUPPORT THE BASE WHILE
THE NON-SHRINK GROUT IS PLACED. WEDGES OR SHIMS THAT ARE LEFT IN PLACE
SHALL NOT BE EXPOSED TO VIEW.

24"

6"

30"

6"

36"

6"

INSIDE
VAULT

AB DIA (IN.)

1/2

5/8

3/4

7/8

1 1/4

1 3/8

1 1/2

1 3/4

MIN PAD HT (IN.)

8 1/2

10

11

12 1/2

15

16 1/2

18

21

24

SCHEDULE 80
PVC PIPE

AM RYAN

CHK
SM FREY
M WRAY

NO.

DATE

PVC SEEP RING 1/4"


MINIMUM THICKNESS
C

ENDS AS
SHOWN
ON PLANS

D+2"

MAIN CORE DRILL


THROUGH WALL
TO D+1" OR LESS

CORE DRILL TO D+4",


SEE NOTE 1

AS REQUIRED FOR
PIPE INSTALLATION,
9" MINIMUM
HOT AIR WELD
AROUND
BOTH SIDES

REVISION

BY

APVD

1"

IF NOT ONE INCH ON


THIS SHEET, ADJUST
SCALES ACCORDINGLY.

NOTE:
1. CHIP HAMMER SURFACE TO MINIMUM
1/8" PROFILE. FILL RECESS WITH
NON-SHRINK GROUT.

PIPE SUPPORT

PVC WALL PIPE

NTS

NTS

15500

15610

VERIFY SCALE
BAR IS ONE INCH ON
ORIGINAL DRAWING.

DR

APVD

OUTSIDE
VAULT

7. HEIGHT OF PADS SHALL BE MINIMUM REQUIRED FOR ANCHOR BOLT CLEARANCE TO


KEEP ANCHOR BOLT ABOVE SUPPORTING SLAB (SEE TABLE BELOW). WHERE
EQUIPMENT OR PIPING ELEVATION REQUIRE A PAD HEIGHT LESS THAN THE
MINIMUM SHOWN, USE TYPE "B" EQUIPMENT PAD WITH BLOCKOUT.

MJ McHENRY
IA

2-1/2"

3. ANCHOR BOLT SLEEVES SHALL BE USED TO PROVIDE MINIMUM ANCHOR BOLT


MOVEMENT OF 1/2" IN ALL HORIZONTAL DIRECTIONS. THE MINIMUM SLEEVE LENGTH
SHALL BE 8 TIMES THE BOLT DIAMETER.

DSGN

N
R

PIPE
SIZE

1. PAD SIZE SHALL BE MINIMUM INDICATED OR AS SHOWN ON THE PLANS OR AS


INDICATED BY THE MANUFACTURER AND APPROVED BY THE ENGINEER.

EER
IN

Y
NR
E

O F CA LIFO

DIMENSION TABLE
NOTES:

G
N

2 1/2" THRU 36" PIPE

3356

Exp.9-30-07
CIVIL

TYPE H

E J. McH
EL

No. C051025

T
A
T

WHEN ANCHORAGE OF EQUIPMENT


TO PAD IS REQUIRED, USE CONCRETE
ANCHORS SPECIFIED.

9. WHERE APPROVED BY THE ENGINEER, EQUIPMENT MAY BE SUPPORTED BY


LEVELING NUTS INSTALLED ON CONCRETE ANCHORS PRIOR TO EQUIPMENT
PAD CONCRETE PLACEMENT.

ON
OFESSI
AL
PR
ED

#5@12" EW
CENTERED

8. AT CONTRACTORS OPTION, CONCRETE ANCHORS MAY BE USED IN LIEU


OF CAST-IN-PLACE ANCHOR BOLTS FOR EQUIPMENT ANCHOR BOLTS LESS
THAN 3/4" DIAMETER WHEN APPROVED BY THE EQUIPMENT MANUFACTURER
AND APPROVED BY THE ENGINEER. ANCHORS SHALL BE INSTALLED WITH
4" MINIMUM EDGE DISTANCE IN EACH DIRECTION.

Exp. 06-30-06

3357

NOTE:

#3@12" EW, 1" CLR


FOR PAD HT < 4",
#4@12" EW, 1 1/2" CLR
FOR PAD HT > 4"
EQUIPMENT

2 - #5 CONT

MIN

TYPE B

2" MIN ALL AROUND


OR AS REQUIRED BY
ANCHORAGE
CALCULATIONS

6"

THICKENED
EDGE OF SLAB
ALL AROUND

REUSE OF DOCUMENTS:

#4@12"
MIN 4 PER PAD
(#5@12" FOR AB 3/4" DIA
OR LARGER)

3357

SHEET

STRUCTURAL/MECHANICAL

HYDROGEOLOGIC, INC
OU-I MID-PLUME GROUNDWATER TREATMENT
FORT ORD
MONTEREY, CALIFORNIA

MISCELLANEOUS DETAILS

FILENAME:

30ns001d_343084.dgn PLOT DATE:

7/6/2006

16

DWG

30-SM-03

DATE

JULY 2006

PROJ

343084.01

PLOT TIME:

c CH2M HILL

4 1/2" MIN ALL AROUND

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
CH2M HILL AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF CH2MHILL.

11:48:43 AM