Professional Documents
Culture Documents
EEE-471
Limitations of HVAC Transmission:
1. Reactive Loss and Drop
For ac transmission, there are lagging reactive VA loss and leading
reactive VA loss due to L & C of the line and the transmission would be
economical if these two losses balance each other at all points along
the line. This happens when the load is terminated with characteristic
impedance of the line. However, it is not possible to operate the line at
characteristic load conditions all the time. Thus this causes reactive
loss in the line. Reactive drop in the line due to L & C is also significant
in case of ac transmission.
2. Stability
The power transmitted over a line of reactance X per phase is,
Vs Vr
P=
sin
X
Maximum steady state power occurs when, =90 .
Considering transient condition, is not generally more than
30
2.
3.
4.
5.
6.
7.
Limitations of HVDC:
1. Cost of terminal equipment is high. The voltage and power to be
transmitted should be high to justify the choice economically.
2. There is possibility of considerable distortion in the waveforms of ac
voltage by use of HVDC link. Special filters would be necessary in the
terminal equipment on either side of HVDC.
3. DC links blocks transmission of reactive kVA load. The receiving end
network must be capable of supplying the whole of reactive
component of power required by the loads and the inverter.
4. DC line is restricted to point to point transmission.
Kinds of DC Links:
Dc lines are classified as
(i)
(ii)
(iii)
Mono-polar
Bi-polar
Homo-polar
In mono-polar line, only one conductor is used and earth is used as return
path.
Bi-polar lines have two conductors. One operating with +(ve) polarity and the
other with (ve) polarity. There are two converters of equal voltage ratings &
connected in series at each end of the dc line. The junction of the converters
may be grounded at one end or at both ends. If it is grounded at both ends,
each line can be operated individually.
Fig: Mono-polar
Fig: Bi-polar
Fig: Homo-polar
RL is the line resistance. Rer &Rci are the resistance of converter & rectifier
respectively. The current in the line is given by,
Rcr + RL+ R
V cos V oi cos
I d=
ci
Grid Control
Tap-change Control
Rectification:
V o=
1
2
n
+
2 n
V m sind
2 n
V m sin ( )
n
n
For 3- , n=3,
V m sin ( )
3
V o=
V o=
3 V m 3
2
For 6- , n=6,
V m sin ( )
6
V o=
6
V o=
3-
3V m
Bridge Rectifier:
Fig: 3-
The output voltage for n-phase is,
V max sin ( )
n
V o=
n
In this case,
V max = 3V m
For n=6,
V o=
3 V m sin ( )
3 3
6
Vm
Inversion:
Bridge Rectifier
E 1 E2
sin
X
Pdc =
E d 1E d 2
Ed 2
V dR
Where,
Ed 1Ed 2
V d = 2V a I a I d
Pd
V d Id
=
Pa V d
I cos
2 d
E1 , E 2
2
cos
Since,
s 1
d a
respectively.
P d 2 d
2V d I d
2V d Id
2 2
2.828
=
=
=
= =
P a 3 a 3 V a I a cos
V
3 cos 3 cos
3 d I d cos
2
Since,
s 1
E 1 E2
sin
X
reactive power generated is greater than consumed, the voltage goes up and
vice-versa. To understand the problem, refer to following figure,
V 2=V 1IZ
Again, V 1 I =P jQ
I=
If
V1
P jQ
V1
V 1=V 1
is reference, then
V 2 =V 1
P jQ
Q
P
X = V 1 X j
X
V1
V1
V1
V1
V2
as it is normal to
V1
. In order to keep
, the drop
Q
X
V1
V2
var.
Methods of Voltage Control:
Voltage is controlled by,
(i)
Series capacitor
(ii)
Shunt capacitor
(iii)
Synchronous capacitor
(iv)
Tap-changing transformer
(v)
Booster transformer
(I) Static Capacitor:
If a static capacitor is connected in series with the line, it reduces the
inductive reactance between the load and the supply point and the voltage
drop is approximated by,
IRcos r + I ( X L X C ) sin r
In practice,
XC
Rcos r
Booster Transformer:
( X L X C ) sin r becomes