DRAWING LIST OF SEB TYPICAL DETAILS

DRAWING No.

DRAWING TITLE

SD/001D

DRAWING LIST OF SEB TYPICAL DETAILS

SD/002A

GENERAL NOTES

SD/003A

CRANKING OF BARS, STANDARD HOOKS AND BENDS

SD/004A

STEEL REINFORCEMENT ANCHORAGE AND LAP LENGTH REQUIREMENT

SD/005B

TYPICAL DETAIL OF SPACER BARS AND STIRRUPS AT BEAMS

SD/006B

TYPICAL DETAIL OF TORSION STIRRUPS AND COLUMN BINDERS

SD/007

TYPICAL WALL JUNCTION DETAILS

SD/008

TYPICAL DETAIL OF BRICK OR R.C. PARTITION WALL AND WALL BASE

SD/009

TYPICAL DETAIL OF R.C. STRUCTURAL WALL

SD/010

TYPICAL DETAIL OF TRIMMING BARS FOR WALL OPENING

SD/011

TYPICAL DETAIL OF TRIMMING BARS FOR. PERMANENT SLAB OPENING

SD/012

TYPICAL DETAIL OF TRIMMING BARS FOR TEMPORARY SLAB OPENING

SD/013

TYPICAL DETAIL FOR TEMPORARY PIPE DUCT OPENING IN SLAB

SD/014

REQUIREMENT OF SPACER BLOCK, 'U' BARS AND STEEL CHAIRS FOR STRUCTURAL ELEMENTS

SD/015

CURTAILMENT OF LONGITUDINAL BARS IN BEAMS

SD/016

TYPICAL DETAIL OF BEAM AND BEAM

SD/017C

TYPICAL DETAIL OF COLUMNS

SD/018

TYPICAL DETAIL OF ROOF BEAM & EXTERIOR COLUMN JUNCTION

SD/019B

TYPICAL DETAIL OF 100 THICK GROUND SLAB ON GRADE

SD/020B

TYPICAL DETAIL OF 150 THICK GROUND SLAB ON GRADE

SD/021B

TYPICAL DETAIL OF 200 THICK GROUND SLAB ON GRADE

SD/022A

TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE

(1 OF 5)

SD/023A

TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE

(2 OF 5)

SD/024A

TYPICAL DETA.IL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE

(3 OF 5)

SD/025A

TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE

(4 OF 5)

SD/026B

TYPICAL DETAIL OF EXTERNAL DRIVEWAY AND CARPARK GROUND SLAB ON GRADE

(5 OF 5)

drawing title

DRAWING LIST OF
SEB 1YPICAL DETAILS

'L' JUNCTION

checked

CSE/1 M.K. WONG


approved

AD(SE) K.T. LEUNG

dote
I------=>

DEC., 2014
dote

DEC., 2014

drawing no.

SD/001

rev.

scale

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.

NOTE : IN LIEU OF THE 1YPES OF BEAM STIRRUPS SHOWN ON THE R.C. DRAWINGS, THE CONTRACTOR
MAY PROPOSE FOR SO'S APPROVAL ALTERNATIVE TYPES OF BEAM STIRRUPS.

u ~

J
(1YPE B)
(1YPE E)

'-

11-----11+--

(1YPE C)

SPACER BARS

lYPE D

lYPE F

si2

S: A\
,_

:::>
CD

10
BUT

70mm

lYPE N
lYPE M
FIG. 1

BEAM STIRRUPS

DEC., 2014
dote

approved

AD(SE) K.T. LEUNG


50

REFER TO TABLE 3 ( SD/006 )

dote

CSE/1 M.K. WONG I

lYPICAL DETAIL OF
SPACER BARS AND
STIRRUPS AT BEAMS

REFER TO TABLE 1 ( SD/003 )

( *b1 )
Ab2

checked

dn;1wing title

(r)

\uJ
u

DEC., 2014

drawing no.

SD/005

rev. , scale

,B

N.T.s.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.

TLL

lit

TLL

11

[]

[J

FIG. 2a TORSION STIRRUPS


NOTE : 1. IN LIEU OF THE TYPES OF COLUMN BINDERS SHOWN ON THE R.C. DRAWINGS, THE CONTRACTOR
MAY PROPOSE FOR SO'S APPROVAL ALTERNATIVE TYPES OF COLUMN BINDERS.
2. TYPE F CROSSTIES ENGAGING THE SAME LONGITUDINAL BAR SHALL HAVE THEIR 90-DEG HOOKS
ALTERNATIVELY FIXED ON OPPOSITE SIDES OF COLUMN.

8~

'\o\1;

TYPE C
BOND LENGTH
FOR REBARS TO

TYPE D

CS2 : 1995 CS2 : 2012


4

~1

BUT 2 50mm
6

BUT 2 60mm

BUT 2 50mm
6
BUT 2 60mm

TABLE 3
BOND LENGTH FOR HOOKS AND BENDS
REQUIREMENT FOR BEAM STIRRUPS
AND COLUMN BINDERS

~150mm

(TYPE D)

OR

FIG. 2b

TYPICAL DETAIL OF COLUMN BINDERS

FOR COLUMN BINDERS : (

r )

REFER TO TABLE 1 ( SD/003 )

checked

drawing title

CSE/1

lYPICAL DETAIL OF
TORSION STIRRUPS AND
COLUMN BINDERS

M.K. WONG / -

approved

AD(SE)
50

K.T. LEUNG

dote
)

[MU

DEC., 2014
dote

DEC., 2014

drawing no.

SD/006

rev.

scale

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.

TLL

I
11

i i

'I

:: :

: )1

OR

If i i
S

: :

TLL

: } { :
: } { :

SPACING OF BARS

WAll END

<:

..

..

0-

:<

.,"

".,

<

OR

-.J
-.J

rV'.,

9 ~

" e

TWO BARS SHOULD BE PLACED WITHIN LOOP


FOR WAlL THICKNESS ~ 200mm.
FOUR BARS SHOULD BE INCLUDED AS SHOWN
FOR WALL THICKNESS OVER 200mm.

Ul

-.J
-.J

....:

Ul

-' ~

'1

..

..

-'.,.- ole

TEE JUNCTION

../'y-

~-

".,

~ c
l..;y.

o e

-=-

1\
10 c

.JV-

-'r--

,
o

....:

~ e

5"'<1

<

OR

c>

-'
-'
~

10
\
0

"-

"

',/

ft

'1

'1

T.L.L.

.-

en

.,

0 t---'Ic-

en

71----' ..-

1
'1

TLL

SPACING OF BARS

l"

JUNCTION

FIG. 3 TYPICAL WALL JUNCTION DETAILS


checked

drawing title

CSE/l C.T. WONG

lYPICAl WALL JUNCTION


DETAilS

approved

-:
...:

AO(SE)
'I'

'I

50

W,W. U
0

10

11111111111

date

~tX<f

JULY. 2008

date

Wd
20

30

1 : 1 SCALE BAR

JULY. 2008
40

50 mm

(PLAN)
scale

drawing no.

SD/007

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 x 297

WALL THICKNESS,
( mm )

VERT. REINF'T

HORI. REINF'T

COMPARTMENT WAll WITH


NO FRP
FIRE RESISTING PERIOD (FRP) REQUIREMENTS
REQUIREMENT
1 HOUR
2 HOUR
4 HOUR

ALL CASES

100 ~ h

< 120

T10-250

Tl0-250

120 ~ h

< 160

T10-300 EF

T10-300 EF

160 ~ h

< 180

T10-300 EF

Tl0-300 EF

Tl0-300 EF

T10-250 EF

180 ~ h

< 200

T10-250 EF

T10-250 EF

T10-250 EF

T10-250 EF

200 ~ h

< 240

T10-200 EF

T10-200 EF

T10-200 EF

T10-200 EF

240 ~ h ~ 250

T10-200 EF

T10-200 EF

T10-200 EF

T10-200 EF

INDICATES THAT WAlL THICKNESS IS NOT PREFERRED AS 1% REINFORCEMENT OF


THE MIN. WAlL THICKNESS IS NEEDED FOR THE FRP REQUIREMENT. WAlL THICKNESS SHOULD BE
INCREASED IN THIS CASE IF POSSIBLE SO THAT NORMAl REINFORCEMENT RATIO COULD BE USED.

TABLE 3 BAR SIZES AND SPACING FOR NON-LOADBEARING PARTITION WALL


It

300

It

It

300

(,

NOTES:
1.

PARTITION WALLS WITH NOMINAL REINFORCEMENT


ARE NOT CONSIDERED AS LOAOBEARING
STRUCTURAl MEMBERS AND HENCE
REINFORCEMENT WILL NOT BE MEASURED
SEPARATELY, BUT DEEMED INCLUDED IN THE
RATES AS FOR OTHER ARCHITECTURAL
FEATURES.

2. SLAB THICKNESS & REINFORCEMENT APPUCABLE


TO BRICK PARTITION WAlL BASES.

600

100 ~ h

< 120

600

POLYTHENE SHEETING
~-

6T10

50 BUNDING LAYER - - - - '

120

WALL

250 WALL

FIG. 4 1YPICAL DETAIL OF BRICK OR R.C. PARTITION WALL & WALL BASE
checked

drawing title

GSEll CJ. WONG

TYPICAL DETAIL OF BRICK


OR R.C. PARTITION WALL
& WALL BASE

date

JULY, 2008
date

approved

AD(sE) W.W. LI
50

10

'"" I",,'

JULY. 2008
20

30

1 : 1 SCAt! BAR

40

50 mm

drawing no.

scale

SD/008

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 x

297~

VERT. REINF'T

WALL THICKNESS,
( mm )

HOR!. REINF'T

h I--N-O-F-R-P---r"F-IR-E-R-ES-ISTI-N-G-P-E-RI-OD-(FR-P-)-R-EQ-U-IRE-M-EN-T-St - - - - - - t
REQUIREMENT

1 HOUR

2 HOUR

4 HOUR

ALL CASES

150 ~ h

<

160

160 ~ h

<

180

T10-200 EF

T10-200 EF

Tl0-200 EF

nO-250 EF

180 ~ h

< 200

T12-250 EF

T12-250 EF

T12-250 EF

Tl0-250 EF

200 ~ h

< 240
T12-170 EF

T12-170 EF

T12-170 EF

nO-300 EF

240 ~ h ~ 250

T12-170 EF

n2-250 EF

INDICATES THAT WALL THICKNESS IS NOT PREFERRED AS 170 REINFORCEMENT OF


THE WALL THICKNESS IS NEEDED FOR THE FRP REQUIREMENT. WALL THICKNESS SHOULD BE
INCREASED IN THIS CASE IF POSSIBLE SO THAT NORMAL REINFORCEMENT RATIO COULD BE USED.

TABLE 4 BAR SIZES AND SPACING FOR R.C. STRUCTURAL WALL


( SEE ALSO DETAIL DRAWINGS WHICH SHALL TAKE PRECEDENCE OVER THIS TABLE.)

300 ..
FL LEV' MIN
"V'

~.

-'
-'

I-

FL LEV
-~

FOR SIZE AND REINFORCEMENT


OF WALL REFER TO TABLE 4 OR
AS SPECIFIED ON THE DETAIL DRAWINGS.

t-

-'
-'

I-

GRD LEV

"V'

l
V~/(',

HARDCORE

J .

l
~/:"-J

REFER RELEVANT
STR UCTURAL DRAWINGS

r-....l~

It

GROUND BEAM OR FOOTING


FER RELEVANT STRUCTURAL DRAWINGS)

/]

~300

(RE

'I

FIG. 5 1YPICAl DETAil OF R.C. STRUCTURAL WALL


checked

drawing title

CSE/1

lYPICAL DETAIL OF
R.C. STRUCTURAL WALL

C.T.WONG

approved

AD(SE) W.W. LI
50

0
10
11111111111

dote

~.

JULY. 2008

dote

Wd
20
I

30

1 : I SCAlE BAR

JULY. 2008
40

50 mm

scale

drawing no.

SD/009

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
M 210 x

297~

, . . - - - - WAll REINFORCEMENT - - - - - ,

r-tY

,h .,

TRIMMING BARS
(TYING WIRE AT ALL INTERSECTIONS)

h < 120

h < 200

120 ~

200 ~

~ 250

SEC. A - A
ELEVATION
r-

TRIMMING BARS
(TYING WIRE AT ALL INTERSECTIONS)

..-- TRIMMING BARS


(TYING WIRE AT AlL INTERSECTIONS)

I
75

WALL REINFORCEMENT

h < 120

120 ~

WALL REINFORCEMENT

L..------L...

~ 250

SEC. B - B
1.

TABLE 5 AND FIG. 6 ARE APPLICABLE FOR NON-LOADBEARING WALLS WHERE OPENING WIDTH (L 1) ~ 2m.
TRIMMING BARS TO OPENING

WALL THICKNESS, h (mm)

<

L1

<

1m

1m

<

L1

2m

1T12 ( SINGLE LAYER )

2T12- 75 (SINGLE LAYER)

< 200

1T12 EF

2T12 - 75 EF

200 ~ h ~ 250

1T16 EF

2T16 - 75 EF

120

120 ~ h

TABLE 5 TRIMMING BARS FOR WALL OPENING AT NON-LOADBEARING WALLS


2.

FOR NON-LOADBEARING WALLS WHERE OPENING WIDTH (L1) > 2m, OR FOR ALL SIZE OF OPENING IN
STRUCTURAL WALLS, THE LOCATION AND SIZE OF THE OPENING SHALL BE APPROVED BY THE PROJECT
STRUCTURAL ENGINEER. DETAILS AND AMOUNT OF TRIMMING BARS SHALL BE SPECIFIED BY THE PROJECT
STRUCTURAL ENGINEER. REFER ALSO TO WALL DETAIL DRAWINGS.

3.

UNDER NORMAL SITUATION, IF OPENING WIDTH (L1)

< BAR

SPACING, NO TRIMMING BAR IS REQUIRED.

FIG. 6 TYPICAL DETAIL OF TRIMMING BARS FOR WALL OPENING


checked

drawing title

CSEll

TYPICAL DETAIL OF
TRIMMING BARS FOR
WALL OPENING

C.T. WONG

approved

AO(sE)
50

'1LW. LI
10
0
11111111111

date

~.

rdd
20

30

1 : 1 SCAI. BAR

JULY. 2008
date

JULY. 2008
40

50 mm

scale

drawing no.

SO/OlO

N.T.s.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 x

297~

-r

2 )( 1T16 T 8 B

- ~~
IY ~
I
I

ill II
II

......
f~"""

\.::J

II

'-2 )( 1T16 T 8 B

AFFECTED BARS

PLAN
300

II
~:: :~:
LL

AND ~ 2h

U-BARS TO LAP THjE


AFFECTED BARS --::

::::::;::::::

U-BARS TO LAP THE


AFFECTED BARS

~ T

t=;:::::t: -"

1T16 T 8 B

1.

1T16 T 8

~FFECTED BARS

r-

B~: ~
I. .TLL

Tl0 EXTRA BARS

.1

--

-? ..c1

AFFECTED BARS

SLAB WITHOUT TOP REINFORCEMENT

SLAB WITH TOP REINFORCEMENT

SEC. A - A
NOTES:
1. FIG. 7 IS APPLICABLE FOR OPENINGS THAT :o. WITH SLAB THICKNESS ~ 200mm
b. HAVE OPENING SIZE NOT MORE THAN 600mm OR 0.25 x SPAN LENGTH OF SLAB
c. DETAIL NOT APPLICABLE TO OPENINGS IN CANTILEVER SLABS
8

2. IF SIZE OF OPENING
REQUIRED.

-=.

< 200mm,

DISPLACE BARS TO SIDES OF OPENING, NO EXTRA TRIMMING BARS

3. FOR SIZE OF OPENING BETWEEN 200mm & 600mm, ADD TRIMMING BARS AS STATED IN THE FIGURE,
OR THE AREA OF TRIMMING BAR ON ONE SIDE EQUAL TO HALF THE AREA OF THE AFFECTED BARS IN
THE CORRESPONDING DIRECTION CUT BY THE OPENING, WHICHEVER IS THE GREATER.

4. FOR LARGER SIZE OF SLAB OPENING, DETAILS OF STEEL ARRANGEMENT SHALL BE SPECIFIED BY THE
PROJECT STRUCTURAL ENGINEER. REFER ALSO TO SLAB DETAIL DRAWINGS.

FIG. 7 lYPICAl DETAil OF TRIMMING BARS FOR PERMANENT SLAB OPENING


checked

drawing title

..."

-=
0

lYPICAl DETAIL OF
TRIMMING BARS FOR
PERMANENT SLAB OPENING

CSE/l C.T. WONG


approved

AO(SE) W.W. LI
'I'

'I

150

10

11111111111

date

~ur

JULY, 2008

date

Wd
20

30

1 : 1 SCAl BAR

JULY, 2008
40

50 mm

drawing no.

scale

SO/011

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 )(

297~

,I ,I
,,
,,
1----.-,""T,-t--L-SlAB REINFORCEMENT

TRIMMING BAR TO BE SPECIFIED BY


THE PROJECT TRUCTURAL ENGINEER
IF NEEDED

--'----------t-i

I I

TRIMMING BARS TO BE SPECIFIED BY


THE PROJECT STRUCTURAL ENGINEER IF NEEDED

FORMWORK TO BE SLOTTED FOR PASSAGE OF BARS


L--'-

SLAB REINFORCEMENT

SEC. A - A
NOTES:
THE FIGURE IS APPLICABLE TO TEMPORARY SLAB OPENING THE SIZE AND LOCATION OF WHICH
SHALL BE APPROVED BY THE PROJECT STRUCTURAL ENGINEER BEFORE CONSTRUCTION.

FIG. 8 TYPICAL DETAIL OF TRIMMING BARS FOR TEMPORARY SLAB OPENING


checked

drawing title

lYPICAL DETAIL OF
TRIMMING BARS FOR
TEMPORARY SLAB OPENING

CSE/I C.T. WONG

~.

JULY. 2008

approved
AD(SE)

50

date

W.W. LI
o
10

I""',,,,!

date
JULY. 2008
20

30
!

1 : 1 SCAlI lIAR

40

50 mm

drawing no.

scale

SD/012

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210

297~

PIPE DUCT OPENINGS TO BE CONCRETED AFTER INSTAlLATION OF PIPS

r-- . .

SLAB REINF'T.

I
1

1',,,-

I
I
I

I
I

It:

10:::

I~

I~

C,!)

C5
0...

DIA & SPACING SAME AS LAB REINF'T.


//~

'L...

I
I
I
I
I
I
I

TRIMMING BARS TO BE SPECIFIED BY


THE PROJECT STRUCTURAL ENGINEER
IF NEEDED.

t:z

-I
/
F=
/
~
I ',
I
'
/
0:::
I
',-'\;- //
Vl~
IIt
I m~'
'
/ / I,TlL~
I I
1 'x/ '1I
~

I
I

/,

//',

--------~I-+--I~I--~I-------

lL.

//

I',

I .

E
E
o
o
Lf)

:z

<"""

I
I

I
I
II

G:i

0:::

-'",

<0...(3
,Vl

'O'd
,~

-I
F=

-------

I
1//
'~
I-~----- - - - -

1//1

~----------~

SLAB REINF'T.

"

WALL - - t -

WIDTH OF OPENING

< 1500mm

CD

:5
en

~r=f : . .

-=-

:z
~

SEC. A - A

NOTES:
THE FIGURE IS APPLICABLE TO TEMPORARY SLAB OPENING THE SIZE AND LOCATION OF WHICH
SHALL BE APPROVED BY THE PROJECT STRUCTURAL ENGINEER BEFORE CONSTRUCTION.

FIG. 9 1YPICAL DETAIL FOR LARGER TEMPORARY PIPE DUCT OPENINGS


checked

drawing title

- lYPICAL DETAIL FOR


TEMPORARY PIPE DUCT
- OPENING IN SLAB
-::

CSE/l C.T. WONG

JULY. 2008

approved

AD(SE)
'I

date

W.W. LI
o
w
'""',,,,'

date
JULY, 2008
~

1 : 1 SCAlE BAR

50 mm

drawing no.

scale

SO/013

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 x

297~

T12 STEEL CHAIR


@1500 clc MAX.

COVER SPACERS
@600 clc MAX.

FORMWORK

~
( :

SECTION OF SLAB

T12

FORMWORK
COVER SPACERS

T12 -U- BAR


@1500 clc MAX.

"u"

BAR

MAX. SPACING: 1500 c/c B.W.

WALL REINFORCEMENT

WALL PLAN

SPACERS WITH
TIE WIRES

)~-

FORMWORK

COVER SPACERS

SECTION OF BEAM
NOTES:
THE DIAMETER AND SPACING OF CHAIRS ARE GIVEN AS MINIMUM REQUIREMENT,
THE CONTRACTOR HAS TO PUT IN ADDITIONAL CHAIRS WHERE NECESSARY TO SUPPORT
THE REINFORCEMENT FROM SAGGING OR DISPLACEMENT.

FIG. 10

REQUIREMENT OF SPACER BLOCK. "Un BARS AND


STEEL CHAIRS FOR STRUCTURAL ELEMENTS

checked

drawing title

REQUIREMENT OF SPACER
BLOCK, 'u' BARS AND
STEEL CHAI RS FOR
STRUCTURAL ELEMENTS

CSE/l C.T. WONG

dote

JULY, 2008

approved

dote

AO(SE) W.W. LI
50

I"" I",,'

10

JULY, 2008

20

30

40

1 : 1 SCAlE BAR

50 mm
!

drawing no.

scale

SD/014

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210

297~

cD

3
3

U!

is

..

'"

CD

~:I:

~~

("')!">
"'m

~C')

U)r'Tl
r'Tlz

r'Tl

a.

a.

0
7':'
CD

CD

0
J

;-t

z:

(]'I

"'0

U)

800

(")

ii>

CIl

::l

<0

!.
::l

c..

CD

- -

~~
.:I:c:
.

<-

E<

c:

G")

:::E
0
:z

;-t

("")

<-

a.

a.

CD

""., S
<

V1

(")

E<

c:

~
~

........

~
Vi'
,...,

III

45(1\1

O.lSl1

BAR OF DIA,

~1

AND

NOTE:

12(1\s

= THE
GREATER OF

SPAN L1

FLOOR BEAM
11

L BEAM BAR OF DIA, ~2

AND L2

45(1\3

O.25L

LANTI-CRACK WEB BARS OF DIA s, FOR BEAM DEPTH> 750

~ L BEAM

AND

I
~

BEAM
DEPTH
LAP

FIG. 11

~3

CURTAILMENT OF LONGITUDINAL BARS IN BEAM

SPAN L2

--.
0.75h

~5
~

BEAM BAR OF DIA,

~4 ~

~
-

0.15L2
AND ~ 454

BEAM BAR OF DIA,

FLOOR BEAM

BEAM BAR OF DIA,

453

O.25L

- L

AND

j;J

1. FOR ARRANGEMENT OF REINFORCEMENT IN EXTERIOR COLUMN AND BEAM JUNCTION


AT ROOF LEVEL REFER TO ORG No. 50/018.

NOTES:

I- Lf

12!11~-

-'-

-r--

~~

TAL I

100

~
125

-'-

,-

TAL +
LES ER (O.5h 0R 8(4)

.h

L_r

SEE NOTE 1

ANTICRA.CK WEB BAR REQUIRED


.IF BEAM DEPTH > 750mm

111-_--::---- .... --j--------...,


J~/
1

iJ-J------ -J----------I_ 1U. .1 ~ ElfAII U.N R8NFORCEMENT


ELEVATION
"'V

1
1
1
1
1
1
1

1
1

I
I
I
I
I
I

I
I
----I
I
I
~ J.
~....

BEAM MAIN REINFORCEMENT

SEE NOTE 1

~
PLAN

....=:

NOTES:

1.

FOR ANTIC RACK BARS AT THE CORNER OF L JUNCTION USE T12 - 250 c/c (MIN.) OR
IF BEAM DEPTH GREATER THAN 750mm. USE ANTICRACK BARS AS SPECIFIED ON BEAM
DETAIL DRAWING.

FIG. 12

lYPICAl DETAil OF BEAM AND BEAM 'L' JUNCTION

checked

drawing title

CSE/1 C.T.WONG

- lYPICAL DETAIL OF BEAM


AND BEAM 'L' JUNCTION

approved

...:

0""1'

AD(SE)

'I

ISO

W. W. LI
10
0
11111111111

date

~.

hid
20

30

1 : 1 SCALE BAR

JULY. 2008

date
JULY. 2008
40

50 mm

scale

drawing no.

SD/016

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 x

297~

BEAM BAR (01) OF DIA = 01,1

I
I

.'

(02)
ROOF BEAM

BEAM BAR OF DIA = Ib2

I LESSER ( 0.5h OR 80b1 )

I
I

(
"1:>

,...

U')

ci
A\

-~

1--H+---I--1I---f--

I ~ 0.75h

II

1 .......

+ TAL

I
1

+
.r:
U')

-'- .8--....

., I

BINDERS WITH
SPACING EO 200mm
(SEE DETAIL DRG)

114---,------t~- COLUMN BAR (02) OF DIA =

hi

0c

f,,--1
COL~MN

I
FIG. 14.1

ROOF BEAM & EXTERIOR COLUMN JUNCTION


- TYPICAL DETAIL (I)

TLL
BEAM BAR (01) OF DIA = Ib1

1 II

~=~1(0=2)====~~~~~~~~~
~

-r-

ROOF BEAM

I - - I t - I - - - I - - - BINDERS WITH

BEAM BAR OF DIA = Ib2

-=-

[I > 0.75h.1

If

!I
I
I

II

SPACING EO 200mm
(SEE DETAIL DRG)

I
I

:
I

COLUMN BAR (02) OF DIA = Ie

.1

COL~MN

FIG. 14.2

checked

drawing title

- lYPICAL DETAIL OF
-:

ROOF BEAM & EXTERIOR COLUMN JUNCTION


- TYPICAL DETAIL (II)

ROOF BEAM &


EXTERIOR COLUMN

CSE/l

JUNCTIO~

approved

AD(S[)
'I

'I

Iso

C.T. WONG

w.w.
0

LI
:lID

11111111111

date

~.

JULY. 2008

date

~
1000

1300

1 1 j 1SCJtII.III!I\R

JULY. 2008
2100

2500nmm

drawing no.

scale

SD/018

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
A4 210 x

297~

aa.

(1)

<
a.

""0

ro-

N
0

coz

:I:

~(")

:;

"'

0
::J
............ !:l
0
N
N

(/)

(1)

a.

--a.
a

-l>-

f'

0
,.,

....

(1)

"
a.

(1)

::::r

co

m ---

c $2
rr1 z

VJ

rr1

~<i)
(")~

rrlz

VJrr~

~~
.:::I:c
.

==

GJ

:z:

?"

:;:::::

{"')
(/)

(/)~"Tl
s;:)>

6~o

c<r

a.

-l>-

::::O::;o~
0--

f'

,.,0

0orrl

GJ

:z:

rfT1
c:::

;...,

:;:><;:

(/)
.!:].

t;

f'T1

" ' )::. ::::o o . ::r


~::::oz)>"'
O:;::o;;:)>'. ;::(:

::;o--1-o
,......""T"1f'Tl-

z:)>X-<

Q(")f'Tl--1

;:

Cl

:r:
,_

u_

<(

C2
cc

<(

Cl

<(

<(

6.0 m

4.5 m

B503
(5.93 kg/sq. m)

C503
(4.34 kg/sq. m)

STEEL MESH
TO BS 4483

20000 MAX.

SINGLE LAYER OF STEEL FABRIC


REINFORCEMENT TO BS 4483
WITH 450mrn LAP MINIMUM
(SEE TABLE 7 FOR MESH TYPE)

EXPANSION JOINT

MAX. SLAB WIDTH BETWEEN


LONGITUDINAL JOINTS,
'B'

::2

~><

g;:

Cl

::21-

i:n
~:r:

::2

~><

Cl

~ g;=

::21-

i:n
~:r:

KERB (IF ANY)

100

CONTRACTION JOINT

20000 MAX.

6.

5.

4.

3.

2.

AREAS

GRANULAR SUB-BASE MATERIAL REFER TO TABLE 8 ON DRG No. SD/026.

CONTRACTOR IS REQUIRED TO SUBMIT LAYOUT OF JOINTS FOR PSE'S APPROVAL PRIOR


TO CONSTRUCTION OF THE EXTERNAL SLABS ON GRADE.

EVERY THIRD JOINT IN THE TRANSVERSE DIRECTION SHOULD BE AN EXPANSION JOINT,


THE REMAINDER BEING CONTRACTION JOINTS.

LONGITUDINAL JOINTS SHOULD BE PROVIDED SO THAT SLABS ARE NOT WIDER THAN
THE MAX. WIDTH IN TABLE 7.

CONCRETE TO BE GRADE 40/20 MIN.

~~

~.

LONGITUDINAL JOINT

EXPANSION JOINT

NOTES:
1. . DRAWINGS No. SD/022 TO SD/026 ARE NOT APPLICABLE TO WORKS
THAT WILL BE HANDED OVER TO HIGHWAYS DEPARTMENT.

60000 MAX.

20000 MAX.

DIRECTION OF TRAFFIC

-4t

CONTRACTION JOINT

"'

0.

"'0.

0<

-o
-o

(./)

",...,

0..

"'

0.

0.
"'"'

"'

::r

N
0J

::::0

............. ?

:.
::::0
(/)<Q

,0

f'

......

G")

?"
::::;:
. 0:z:

$n

.
--l

z:

(J)

ro

~~-~
~::I:

~~~

~8

(/)f'Tl
f'TlZ

.::J:c
.

~~

,0

:z:
G")

rrr1
c:::

;...;

:;><;

>
0
Ui'
-!:!.

'I

rnZ

s;:>

(/)~.,

~~0

c<

0--

G)o~
:::0:::0)>

OOrrl=< 0.
:z>X
;;o---1""0 0
G) ""0 rrl (") :.
~?0~)>-E
o:A>' ;:;:
rr1
' o ro

NOTES

3.

2.

1.

PREFORMED PVC TIGHT FITIING


DOWEL SLEEVE

SEC. A-A DETAIL OF CONTRACTION JOINT


IN EXTERNAL DRIVEWAY AND CAR PARKING AREAS

BOTIOM CRACK-INDUCER ( OF TIMBER, STEEL OR SYNTHETIC MATERIAL )


SECURELY FIXED TO THE BASE. THE COMBINED DEPTH OF DISCONTINUITY
PROVIDED BY THE CRACK-INDUCER AND THE SEALING GROOVE AT THE TOP
OF THE SLAB SHOULD BE AT LEAST 1I 4 OF THE THICKNESS OF THE SLAB

300

BOND BREAKER

APPROVED POLYSULPHIDE I
POLYURETHANE JOINT SEALANT

CD

5Vl

lCl

No:;

I.Cljw
Nt;:;

25 x 15 SEALING GROOVE SAWN OR WET FORMED AT A POSITION VERTICALLY


ABOVE THE CRACK-INDUCER TO WITHIN A TOLERANCE OF 10mm

ROAD FORMATION

ALL THE FILLING MATERIALS FOR ROAD FORMATION SHALL BE COMPACTED IN COMPLIANCE WITH CLAUSE 3.19(vi) OF THE
GENERAL SPECIFICATION; OR, AS APPROVED BY THE SO, CLAUSE 3.20 OF THE GENERAL SPECIFICATION.
IMMEDIATELY PRIOR TO LAYING THE SUB-BASE, CARRY OUT PREPARATION AND SURFACE TREATMENT OF THE ROAD
FORMATION IN ACCORDANCE WITH CLAUSE 3.26 OF THE GENERAL SPECIFICATION.
UNLESS OTHERWISE SPECIFIED, SUB-BASE SHALL BE COMPACTED IN ACCORDANCE WITH CLAUSE 3.20 OF THE GENERAL
SPECIFICATION OR AS APPROVED BY THE SO.

FIG. 16.2

GRANULAR SUB-BASE

25mm DIA 650mm LONG MILD STEEL DOWEL BARS


AT MID-DEPTH AND AT 300mm CENTRES

350

STEEL FABRIC REINFORCEMENT


( SEE DRG No. SDI022 )

ONE LAYER OF 125 J..im POLYTHENE SHEET


WITH 150mm LAP MIN. WHERE REQUIRED.

100

VI

,.....

~
~.

aa.

>

<I>
a_

<

""
0

c;;

a_

~:I:

rTt(")

~~

rTtCDI

(")

~8
.

UlrTt
rTt:z

:::I:c

~~
. .

.j>.

0
,...,
f'

OJ :Z:

);: )>

::>

!.

a_

c;;

a_
0

!I'

z
;-t

)>

'"

(/)

Cil
:"

0
::>
.............. p
0
N

(/)<O

.j>.

0
,...,
f'

G)

:z:

::E

?-:

s::::

<I>
"""
a_

<I>

::r

Ul

iif

-::::::-

",...,

(/)-<.,

o~O

:z:rrl

c:<r

o:::U)>

I~

:z:
C)

c::

fTl

r-

;:><;

<n

cio~

o="')>' e:

~:
.........

(") rrl --I

:z: )>X-<
:::u --I -o
G) -o rrl (")
;:;u )> ;:;u )>
)>:::U:Z:

-1 rrl

Oloootiuul

I
I

1100

3.

2.

1.

NOTES :

I
75

L(1

z
0

. '5:2'.

ROAD FORMATION

~~

12mm DIA. MILD STEEL DOWEL BARS, 1.1m IN LENGTH


AND SPACED AT 600mm CENTRES AT MID-DEPTH

(/)

L(')lw

:5

_I

SEC. B-B DETAIL OF LONGITUDINAL JOINT


IN EXTERNAL DRIVEWAY AND CAR PARKING AREAS

I 75

llYiJ

ALL THE FILLING MATERIALS FOR ROAD FORMATION SHALL BE COMPACTED IN COMPLIANCE WITH CLAUSE 3.19(vi) OF THE
GENERAL SPECIFICATION; OR, AS APPROVED BY THE SO, CLAUSE 3.20 OF THE GENERAL SPECIFICATION.
IMMEDIATELY PRIOR TO LAYING THE SUB-BASE, CARRY OUT PREPARATION AND SURFACE TREATMENT OF THE ROAD
FORMATION IN ACCORDANCE WITH CLAUSE 3.26 OF THE GENERAL SPECIFICATION.
UNLESS OTHERWISE SPECIFIED, SUB-BASE SHALL BE COMPACTED IN ACCORDANCE WITH CLAUSE 3.20 OF THE GENERAL
SPECIFICATION OR AS APPROVED BY THE SO.

FIG. 16.3

GRANULAR SUB-BASE

I_ 50 _

.-- APPROVED SEALING STRIP GLUED TO EDGE OF FIRST SLAB


CAST PRIOR TO POURING THE SECOND SLAB

-~J--- --- _J!

150mm LONG PREFORMED PVC TIGHT FITTING SLEEVE -

r-- ------ --- --- ---

.- STEEL FABRIC REINFORCEMENT


( SEE DRG No. SD/022 )

.---- ONE lAYER OF 125 J.Jm POLYTHENE SHEET


WITH 150mm LAP MIN. WHERE REQUIRED.

lso

OOrrl:(!

'

CD

0.

.j>.

!="'

,0

C)

:z:

==:

?"

s:::

Vl

C)

0.

CD

0.

CD
0.

"

:T
CD

:I:

r'Tl(")

~~I

r'TltD

oP

~C)

(/) fT1
fT1

;:cc
.

;-t
Yl

:z

):>

()1

0
N

;;-

:<

(il

(/J

~~181
........._g

.j>.

!="'

C)

c:
:z:

rr1

~
r-

CD
0.

;:;><;;

0<

-.::>
-.::>

E;;
8..!:].

c:o:Z
0

c<r
z~o
o)>""Tl
(/)=-<
);:l>

GJo~
::::O:;;o)>
0--

:z):>X
~
::::0 --I """0 0
G') """0 rr1 0
!.
:;;o):>::::0):>-.5
):> ::::0 ~I ,....
CJA
;::;:
rr1
' o <n

1\

I..J

..J/"\YYI'\1

VI\

YYLI

rVf\IVI[.U

APPROVED POLYSULPHIDE /
POLYURETHANE JOINT SEALANT

\Jf\VVVL

,., I

PREFORMED PVC TIGHT FITIING


DOWEL SLEEVE

_.. .

125 I

25mm DIA 650mm LONG MILD STEEL DOWEL BARS


AT MID-DEPTH AND AT 300mm CENTRES.
HALF LENGTH PAINTED WITH BOND PREVENTING COMPOUND.

300

SEC. C-C DETAIL OF EXPANSION JOINT


IN EXTERNAL DRIVEWAY AND CAR PARKING AREAS

JOINT FILLER

<

<

---- -- -- -- -- --

mf'=-f-

Vj

LJ

- APPROVED POLYETHYLENE FOAM

~~
25
~

I
I

0:

""- ~

--,50
I TYP

I 51

N
N

Vl

0
L{)

ROAD FORMATION

u
:z

0::

L{)lw
W

:5

ALL THE FILLING MATERIALS FOR ROAD FORMATION SHALL BE COMPACTED IN COMPLIANCE WITH ClAUSE 3.19( vi) OF THE
GENERAL SPECIFICATION; OR, AS APPROVED BY THE SO, ClAUSE 3.20 OF THE .GENERAL SPECIFICATION.
IMMEDIATELY PRIOR TO lAYING THE SUB-BASE, CARRY OUT PREPARATION AND SURFACE TREATMENT OF THE ROAD
FORMATION IN ACCORDANCE WITH ClAUSE 3.26 OF THE GENERAL SPECIFICATION.
UNLESS OTHERWISE SPECIFIED, SUB-BASE SHALL BE COMPACTED IN ACCORDANCE WITH ClAUSE 3.20 OF THE GENERAL
SPECIFICATION OR AS APPROVED BY THE- SO.

FIG. 16.4

GRANUlAR SUB-BASE

3.

2.

1.

NOTES :

350

HOLES DRILLED IN THE FILLER TO GIVE


A DOWEL BAR SLEEVE A "PUSH FIT"

I
I

BOND BREAKER

STEEL FABRIC REINFORCEMENT


( SEE DRG No. SD/022 )

ONE LAYER OF 125 um POLYTHENE SHEET


WITH 150mm LAP MiN. WHERE REQUIRED.

- ---- -- -- -- --

100

RANGE OF GRADING
B. S. SIEVE SIZE

PERCENTAGE BY WEIGHT PASSING


100

75 mm

85 rv 1QQ

37.5 mm
20 mm

60 rv 85

10 mm

40 rv 70

5 mm

25 rv 45

600 J.lm

8 rv.22

75 J.lm

Q rv 10

a.

GRANULAR SUB-BASE MATERIAL SHALL BE COMPRISED OF CRUSHED ROCK, RE-CYCLED


AGGREGATE OR APPROVED RE-CYCLED SUB-BASE MATE~IAL. THE MATERIAL SHALL BE
WELL -GRADED AND LIE WITHIN THE ABOVE GRADING LIMITS. THE PARTICLE SIZE SHALL
BE DETERMINED IN ACCORDANCE WITH THE REQUIREMENTS OF CS3.

b.

THE MATERIAL PASSING THE B.S. SIEVE 425 J.lm WHEN TESTED IN ACCORDANCE WITH
GEOSPEC 3, TEST METHOD 6.1 SHALL BE NON-PLASTIC.

c.

THE MATERIAL SHALL BE LAID AND COMPACTED TO THE. REQUIREMENTS OF


CLAUSE 3.20 OF THE GENERAL SPECIFICATION.

0
0

-=
-

'

TABLE 8 GRANUlAR SUB-BASE MATERIAL

checked

drawing title

TYPICAL DETAIL OF
EXTERNAL DRIVEWAY AND
CARPARK GROUND SLAB
ON GRADE
(5 OF
'I

'I

CSE/1

M.K. WONG

approved

5)

150

AD(SE)

K.T. LEUNG

date
I

...

WJ

DEC., 2014
date

DEC., 2014

drawing no.

SD/026

rev.

scale

N.T.S.

STRU. ENGG. BRANCH


ARCH. SERVICES DEPT.
/