STANDARD No.


rlfaeie-1
it S ENGINEERS CONCRETE SLIDING SLEEPER
INDIA LIMITED 7- 65 - 0409 Rev. 6
(A Goa of India Undertalongt
CAST IN SITU TYPE- IV
Page 1 of 1

TOP OF SLEEPER LEVEL 300


MS FLAT 65 X 8 FOR FULL LENGTH
REFER SLEEPER SCHEDULE

, ...-- Nar„...... 1),


>c _1 q•—•
am
m< 12 V LUG 0250 C/C
6.- • • F.G.L.
o <
in > GIVEN IN AREA DRG.)
Ne..cw • •
10 V 0 175C/C
80 0 200 C/0
80 (TYP)
,t

300 (TYP)

• •
U) PCC 1:5:10

WELL COMPACTED SUB GRADE 12D 0175 C/C (8)8


AS PER GEOTECH RECOMMENDATIONS
SECTION A-A 12 11 LUG

{ 300 ir J
0
1 /

150
• •

B0020 IC/C DETAIL OF LUGS


,RIABLE

'V
1,

REFERENCE LINE

a SLEEPER

REPRESENTATION ON AREA DRGS.


•.._ •

PLAN
NOTES:-
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED OTHERWISE.
2. REFER STRUCTURAL GENERAL NOTES OF THE PROJECT FOR REINFORCED CONCRETE
STRUCTURES FOR THE FOLLOWING:-
a) GRADE OF CONCRETE
b) GRADE AND TYPE OF CEMENT
c) REINFORCEMENT STEEL BARS
d) CLEAR COVER IN RCC WORKS.
3. ALL LUGS SHALL BE WELDED WITH 6mm FILLET WELD WITH THE MS FLAT LOCATED AT
TOP OF THE SLEEPER LEVEL.
4. LOCATION LENGTH AND TOP OF SLEEPER LEVEL SHALL BE AS PER RELEVANT PIPING GAD.
5. THIS STANDARD IS APPLICABLE FOR THE BEARING CAPACITY OF SOIL 5.0T/M2 OR MORE.
IN CASE BEARING CAPACITY OF SOIL IS LESS THAN 5.0T/M2, GEO TECH
RECOMMENDATIONS SHALL BE OBTAINED AND JOB DRAWING SHALL BE APPLICABLE.

6 01.02.13 REVISED AND ISSUED AS STANDARD Anil A,„;,1 RC ' 1., ROBY"' SC AP-V DM

5 20.05.09 REVISED AND ISSUED AS STANDARD SKP RK NK ND

Rev. Prepared Checked Stds. Committee GM (ENGG) Stds. Bureau


Date Purpose Convenor Chairman
No. by by
Approved by
Format No. 8-00-0001-F4 Rev.0 Copyright EIL - All rights reserved