Professional Documents
Culture Documents
Coordination of Transformers
BY F. J. VOGEL*
Associate, A.I.E.E.
11
to the transformer from the line, by the specification of
line insulation and protective gaps.' In the meanwhile,
progress has been made in the laboratory study of the
surge characteristics of the insulators, gaps, and insulation structures commonly used in transformers.2 This
paper presents data from these insulation studies and
shows the relationships between the present coordination standards and the strength of transformer insulation. The results of tests of insulation under oil are
reported, the strength of the various voltage ratings of FIG. 2-VIEW OF CORE TYPE TRANSFORMER INSULATION MODEL
The low-voltage coil and iron are represented as one piece
transformers estimated and these in turn compared to
the flashover values of line insulation and gaps.
tests, for the purpose of obtaining data on the strength
SURGE STRENGTH OF INSULATIONS UNDER OIL
of major insulation.
It should clearly be understood that the results obThe heart of the insulation of a transformer, as determined by the present A.I.E.E. rules, is in the insu- tained apply only to the major insulation and do not
represent the insulation strengths of complete transformers unless the insulation between turns and coils
has been so made that even under the conditions of
surge tests the major insulation is the weakest part of
the entire structure.
The shell type models were first given 60-cycle tests
_
to breakdown voltage. The results of these tests are as
given in Table I. The procedure of testing was to hold
tbl L mkI-T
2 r 1X1
a___:______,__X__________
Model
lation between the high-voltage and low-voltage windings, commonly known to the designer as majorinsulation. It is desired to keep these insulation clearances
as small as possible to obtain low reactance, low losses,
15 ..
280
.290
.310
16.300
270.280
18
.
260.270
20.
Average
.........280
...
290
33-38
412
Transactions A.I.E.E.
used were approximately 1Y2 ysec front and 40 usec in Fig. 7. The extension of the barrier beyond the
from the crest to half value. The results of these tests electrode was such as to produce puncture. The results
are plotted in Fig. 3. The comparison between these of this test are given below:
results and the 60-cycle tests (approx. impulse ratio) is
shown in Fig. 4.
Rms
Model
3.
300 ..
310
4................. 27....................... 280
7.
300 ..
310
S.
320 ..
330
9.
280
.290
10..........310.............320
.
11 .---..-...300 .................
310
12................. 320 ....................... 330
Average ....
300
2.8
221 kv ....
485 kv ....
450 kv ..
Impiulse
2.2
2.04
_ _
R2.6-v_
Ve
2.4
2.2
XI~-
-l.
...-.
310
3.0 _0
2.0-
Crest
156 kv ....
Surge strength
Voltage
Time lag
60 sec test
5
6
7
8 9
TIME IN MICROSECONDS
l0
11
12
13
900
800
1300
-J
200.-
>2700
l-00
IC l
0600
TIME
INMICROSECOCREST-AVERAGE
900-
-J
ma>eojce7ha
200
0POIIEWV00
6
5
6
7
9
TIME IN MICROSECONDS
hs
IC
500.
1213 11
<
o rpeettv001
400
-CREST-AVERAGE
iNs
INSULATION
WAVE
1 USING
MODEL
l240 POSITIVE
3CC
200
It may be objected that these are not representative
of all types of major insulation. These tests represent
lat
conditions where the dielectric field is formed between whethe
.s
i.T
-jo
June 1933
3.4
3.2
-
3.0
2.8
2<<-<
<2
D
2.
a_.4 4
_ _
_
t
L
2.2 EE WESH
2.0 0
-.
3
2
TIME IN MICROSECONDS
413
<4
WI
rELECTRODE
~~~~~~
~~~~~~~GROUND//
414
-_
- -__
- -
12CC - -
_- - - -
700 - -- 600
- -
500 400
-X
-
- -CREST-AVERAGE
An estimated curve of the relationships existing between the standard point gap and insulation for negative waves is shown on curve 11, for the 230-kv class.
This is of interest in indicating still further the desirability of keeping the bushing characteristics at the
lowest level.
THE COORDINATION PROBLEM
Originally it was the opinion of engineers generally
that since transformers gave satisfactory service, coordination of the transformer insulation with the line
insulation was obtained. Surge voltage data were not
..
lc00
90C - - - -
Transactions A.I.E.E.
300
18401;I
100.10~
2
FIG.
9-SURGE
FOR
VOLTAGE
STRENGTH
OF
160CIC
II
INTERLEAVED
12
13
BARRIER
1300
230-KV
II
C CD 4-j0-IN.INSULATORS
CLASS
MAJOR
1200
0
o 1100__AIIIIIIII
< 10CC
INSULATION_
70-IN. GAP
STNDR
--
T4-IN -AP
Group I is for 230-kv class, Group II is for 138-kv class and Group III is
time lags but here the margin of strength for the insulafor
69-kv class. A for all classes is the present standard coordinating gap
tion is much greater.
time-lag curve for the voltage class. B is the curve for the proposed gap for
Tests have been made with negative waves and they testing purposes and is a proposed bushing level. C is the curve for the line
formerly proposed for coordinating purposes. D is the minimum
indicate little increase in voltage for short time lags insulation
possible curve for the major insulation level based on the standard ATI.E.E.
compared to positive waves. There iS however some -tests from the high-voltage winding to the low-voltage winding and ground
increase in the voltage for long time lags due to change
in polarity. Complete data of the effect of humidity on may greatly modify and reduce them. It is of interest,
negative waves is not yet available. Nevertheless it is therefore, (see Fig. 10) to note that with major insulaimportant that the effect of negative waves be consid- tion designed just to meet the requirements of the
ered. One reason for this is the fact that the highest standard A.I.E.E. tests, coordination with the line
lightning surges on lines have generally been found insulators would have been obtained in the higher voltage classes except at very short time lags. The margin
to be negative.4
June 1933
415
gation of this sort in the several voltage classes to determine if major insulation designed to meet the requirements of the standard A.I.E.E. tests would be coordinated with the standard gaps at the 2-microsecond
point. The results of such an investigation are presented
in Table III.
In this table an effort has been made to arrive at
logical values for the surge voltage requirements of the
major insulation for the different voltage classes. It
shows that in voltage classes
kv and above, the
700OC 9 _I || | ] ] || 0 requirement that coordination34.5
be obtained at the 2160j
7
microsecond point will determine the necessary surge
MAJOR
$.
_
_voltage
strength of the major insulation, and that these
\D
MAJOR INSULATI ON
230-KV INSULATION _
surge voltage strengths so obtained, when translated
(1400
\\
corresponding 60-cycle tests, give values almost
oI30C
- NEGATIVEinto
0
exactly in agreement with the present standard A.I.E.E.
NEGATIVE'WAVE-70O'ZIN.GAP
Y-200- -tests. In the lower voltage classes, however, this re10 -- NEGATIVEWAVE64
quirement would dictate surge voltage strengths less
A _ POSITIVE WAVE-64-lN. GAP
than would be required to meet the surge tests proposed
_000 - TIME _NROSECONDS
by the Transformer Subcommittee, so that in these
4
6
0 2 14 6 18 20
9000
lower voltage classes the proposed
tests would
TIME IN MICROSECONDS
dictate the necessary surge voltage strengths of the
FIG. 11-COMPARISON OF POSITIVE AND NEGATIVE WAVE major insulation. These strengths translated into corsurge
A is the time-lag curve for a positive wave, the standard 64-in. gap and
corrected to standard atmospheric conditions. B is the time-lag curve for
lower
THE
a negative wave and the standard 64-in. gap, not corrected to standard
atmospheric conditions. C is the curve for a negative wave for a 70 M2-in.
gap proposed as a test standard and bushing level. D is the transformer
insulation level
curves
vary so radically. In the coordination work so far accomplished, characteristics such as obtained with the
point gap or insulator strings only have been considered.
The possibility of coordinating with a gap having impulse characteristics of similar shape to transformer
insulation is an alternative. Such a gap might be a
sphere gap. With the use of such a gap, a uniform factor
of safety would be possible between transformer major
insulation and the gap, instead of the variation now experienced between short and long timre lags. An example
of the results to be expected from such an arrangement
is indicated as follows:
TABLE III
Coordinating
Voltage class
gap
Full wave
(1 )/-40)
standard gap
2 microsecond
strength
standard gap
............
............
161,000
230,000
.44)M.~.
.64
......725
. 1,000
.....
1,020 .
.......
1,440
.....
=
=
60-cycle (C)
test req'd by
surge strength
Present
60-cycle
test
21.6 (D)......... 10
29.2 (D).
18.4
37 ....
6
.....
vau
47
.
215....... 23
............ 70
.
93
86. . ............ 91.5.............
67 ....
91.
115
151.48.5 .
..............1,000
..............1,440
....
....
....
322 .........323
....
462 .........461
....
(B) Major insulation requirements up to the 23-ky class are determined to meet surge tests 10 per cent above the flashover of a gap which is 10 per
cent higher than the standard gap. In the higher voltage classes the major insulation strength is determined by the requirement that coordination must
be obinined at a time lag of 2 microseconds.
(C) Surge strengths divided by i2 and by 2.2.
(B) MNanufacturers have long recognized the necessity for higher insulation strengths of these transformers, and it has generally been built in.
416
Any gap used should be protected by lightning arresters, to obtain continuity of service. The discharge
voltage of an autovalve arrester for 230-kv service is in
the neighborhood of 850 kv. The coordinating gap used
might then be set to furnish some desired margin, and in
turn a further-margin taken for the transformer insulation above the gap. The total of these margins might
15C- _
-
1300
ooo00
-.s-
-8oo
-4 - -_ _l
>
0700
6700-
14-oo
> >_o9Sgq4v9
tX
g
A
ACKNOWLEDGMENT
(J
< 2oN zoL jThe author desires to acknowledge the assistance of
/ es, /,)5<_
his associates in the laboratories and engineering depart-
5CC - - - 400
--
sooALZL1.S
9
31
+-
- - -
0C C24C60
20 40
SC ICC 120 140 160 180 2CC
VOLTAGE_CLASS IN KILOVOLTS
Hments of the
l;
600
300
200C
should be increased.
5. Greatest security is obtained if the surge flashover
1200.-l l lXqa
l l $4Lof the bushing is only slightly greater than that of the
coordinating gap. A margin of 10 per cent is suggested
Ll Ll >; tvqtl,8 72
as the most desirable bushing level.
1400
900
Transactions A.I.E.E.
tw
.this paper.
ICC
220 240
Bibliography
1. Recommendations on Balancing Transformer and Line Insula|.tions, V. M. Montsinger and W. M. Dann, A.I.E.E. TRANS.,
Lightnig.nvstgat
a0K
St
Penna.
ot
Lightning
pointed out that in this case coordination with present Insulation, V. M. Montsinger and W. M. Dann, A.I.E.E.
TRANS., Vol. 51, December 1932, p. 923.
designs of bushings would be impossible.
SUMMARY
The following conclusions have been reached:
1. The time lag characteristics of major insulation are
Discussion
For discussion of this paper see page 440.