You are on page 1of 2

1

THREE PHASE TRANSFORMER EXAMPLE:


2+j 8.64
3000

3 phase
Y-
Transformer

Ve

Vo

A
3 phase
-Y
Transformer

3 + j 2.25
B

Load

All 6 xfmrs are identical.


Ratings: 4.5 MVA, 15kV :3 kV.
O.C. Test: Voc = 3000 V, Ioc = 30 A, Poc = 45 kW.
S.C. Test: Vsc = 750 V, Isc = 300 A, Psc = 90 kW.
Parameters referred to HV side: G1 = 0.2 mS, B1 = 0.346 mS, Req = 1 ,
Xeq = 2.29 .
Parameters referred to LV side: G1 = 5 mS, B1 = 8.66 mS, Req = 0.04 ,
Xeq = 0.092 .
a) Transform load to Y: ZLY = ZL/3 = 1.2536.9
b) Refer to HV side: ZLY,HV = 25+j18.75
c) Equiv. Cct. on HV Side ( connected):
Zeq = 25.65+j20.93

1+j2.29

d) Convert to Y and add to Zt.


Zeq,y + Zt = 10.55 + j15.62 = Ztot

(0.2-j0.356)E-3
25+j18.75

e) Convert to and refer to LV side of Xfmr


#1.
Ztot, = 31.65 + j 46.86
Ztot,,LV = 1.27 + j1.88
a) Equiv. Cct on LV side (Y connected)
IaLV = 3000/(1.31+j1.97) = 702.2-j1056
Iexc = 15-j26 A
Is = 1298-56.5
IV. Transformers-1

.04+j0.092

3000

(5-j8.66)E-3
1.27+j1.88

P = 6456 kW
b) Solving back to the right,
Vo,LV = 2874.9-0.45
Vo = 14374-0.45
Ve,ln = 4868-47.2
Ve = 8431.7-17.2
VL = 2729.810.7

IV. Transformers-2