Worked Example For Cooling Tower PDF
Worked Example For Cooling Tower PDF
Consider a chiller plant system (capacity 500kW) with COP at 4.5 is designed with a cooling
tower, the design entering and leaving condenser water temperature of the cooling tower are
37C and 32C respectively, the design wet bulb temperature of the outdoor air is 28C, what
are:
a) the cooling tower coefficient
b) the required condenser water and air mass rate (in kg/s) in the cooling tower
c) the required height of the fill
Solution
a)
As the air and water temperature are not changing linearly, the entering / leaving water
temperature should be cut down into small steps of, e.g. 1C / 1K, in an iteration process to
determine the heat transfer in each step.
The changing enthalpy of air in each step dha can be derived from the equation:
Enthalpy
Difference
ha
h ha
1
(h ha )
kJ/kg
100.0
(28C WB)
kJ/kg
11.0
kg/KJ
0.09091
K
1
105.0
11.9
0.08403
123.0
110.0
13.0
0.07692
35
129.5
115.0
14.5
0.06897
36
136.2
120.0
16.2
0.06173
37
143.3
125.0
18.3
0.05464
Water
Temperature
Enthalpy
of Film1
Enthalpy
of Air2
hs
C
32
kJ/kg
111.0
33
116.9
34
NTU=
c pwt
(h ha )avg
NTU
0.3656
0.3656
0.3364
0.7020
0.3049
1.0069
0.2732
1.2801
0.2432
1.5233
Note:
1. Enthalpy of saturated air film at different temperature are obtained from thermodynamic tables of moist air.
2. Enthalpy of air starts at 28C WB = 100.0 kJ/kg and then increases by 5.0kJ/kg per 1K increase in water temperature.