You are on page 1of 3

DAS-CI-17-EU

Central Air Handling units


Series PAC-DX
DX Boost

Cavotec INET has a proud history of being at the forefront of new technology applications to increase
efficiency for practical fixed pre-conditioned air and 400Hz ground power systems.

General information
INETs Series PAC-DX air handlers are specially designed to accommodate the severe air pressure
and flow requirements for groundbased cooling, heating and ventilation of commercial passenger
aircraft. These light-weight units contain air filter, blower, heat exchanger coil, output plenum, digital
controls, and use a combination of building chilled water for first stage cooling with DX Compressors
for second stage cooling, and a range of accessories to provide fully automatic cabin conditioning.
Units are available in ratings to service a full range of aircraft from narrow body through the new A380
configuration.

Bridge mounted unit

In the cooling mode, the air handlers use INETs patented SuperCool technology to optimize
overall energy input and to reduce size and weight. Optional heating can be achieved by
either built-in electrical resistance units, centralized hot water or a combination of these.
Operating mode, airflow, and supply temperature are automatically and continuously
adjusted to accommodate varying climate and aircraft conditions.

STANDARD FEATURES

Local controls, remote provisions

Direct-digital automatic controller


Local controls, remote provisions
Remote cabin sensing
On/Off and running time indicators
High-efficiency centrifugal blower
Direct drive

RS-232 and RS-485 ports


Auto or manual operation
Low-voltage controls
Variable air flow and temp
2-stage disposable air filters
Condensate water pump

OPTIONS
Electric strip heaters / controls
Bridge pre-cooling/heating
Variable-Speed Blower
Remote Monitoring & Control

INET`s patented SuperCool technology

Air Delivery Hoses & Devices


Across-Bridge Accessories
Hose Storage
Adaptors

Related Products/services







Complete central system


System feasibility studies
Turnkey design/build projects
Commissioning and Training
Point of Use PC Air Units
400 Hz equipment and systems
Complete integrated gate systems
Precision power products

SPECIFICATIONS - SERIES PAC-DX


IMPORTANT NOTES:
1. The model series shown below lists basic units for standard 1. design ambient conditions using the most common chilled water supply, DX
compressors and outlet air delivery configurations. Other blower performance models having unique model number suffixes may be selected by the
factory to optimize operating conditions for a given set of aircraft mix, climate, altitude, and installation configurations. It is suggested that this data
sheet be used as an initial guide pending analysis of full system requirements by INET factory applications engineering staff.
2. Operating data shown is for common conditions as follows: Summer Design Temperature: 48C (118F) dry bulb/33C (91F) wet bulb.
Supply Building Chilled Water: at 6C (48F) supply temperature.
PAC-DX60

PAC-DX140

PAC-DX180(*)

Narrow-Body through B727

Narrow-Body through MD-80, B757

Aircraft
Suggested A/C Suitability to maintain 24C(78F) cabin:

Wide-Body through MD11, A310, B767


Jumbo through B747-400, A340, A380

PHYSICAL CHARACTERISTICS
Input Voltage Frequency 50Hz Models

380V, 3 phase

380V, 3 phase

380V, 3 phase

Input Current FLA at Max Air @ 380V

160

195

224

Maximum Circuit Ampacity

200

250

350

394 x 229 x 152

394 x 229 x 152

432 x 229 x 152

155 x 90 x 60

155 x 90 x 60

170 x 90 x 60

2700 (5953)

3125 (6890)

3750 (8267)

60

139

180

155kW

380kW

380kW

Dimensions (L x W x H) in cm
Dimensions (L x W x H) in inches
Operating Weight {kg (lbs)}
Compressor Type, Hermetically Sealed Scroll
PERFORMANCE
Cooling (Tons)
1st Stage Chilled Water Capacity
2nd Stage Compressor Capacity
Chilled Water Supply Flow L/sec (Gal/min)
Chilled Water Supply Temp C (F)
Chilled Water Return Temp C (F)

45kW

110kW

170kW

11.4 (180)

14.45 (228.5)

17.5 (277)

6 (48)

6 (48)

6 (48)

20 (68)

20 (68)

20 (68)

154 (340)

200 (440)

249 (550)

5.4Kpa 22W

6.05Kpa 28.5W

8.7Kpa 35W

Minimum Supply Air Temp C

-4 +/- 1

-8 +/- 1

-10 +/- 1

Minimum Supply Air Temp F

25 +/- 2

17.6 +/- 2

14 +/- 2

Supply Airflow kg/min (lb/min)


Supply Air Presure

(*) PAC-DX180 Capacity, provided chilled water capacity available for first stage cooling and second stage compressor capacity is
sized for ultimate cooling capacity of -10C

For further information please visit www.cavotec.com


Disclaimer:specificationsaresubjecttochangewithoutnotice

www.cavotec.com

Technical drawings

OUTLINE DRAWING --- TOP VIEW

COMPRESSOR

STAGE 1
CONDENSER
HX

90.00

CW COIL

BLOWER
COMPRESSOR

EVAPORATOR

OUTLET AIR PLENUM

STAGE 2
CONDENSER
HX

VFD

POWER & CONTROL PANEL

170.00
AIR IN

AIR IN

POWER &
CONTROL
PANEL

AIR IN

60.00

OUTLINE DRAWING --- SIDE VIEW

PAC-DX180

For further information please visit www.cavotec.com


Disclaimer:specificationsaresubjecttochangewithoutnotice

www.cavotec.com