Professional Documents
Culture Documents
Department of Electrical and Computer Engineering, Tarbiat Modares University, Tehran, Iran
Keywords: four-leg inverter, parallel inverters operation, Droop method, Virtual output resistive impedance
Sowa kluczowe: poczwrny przeksztatnik, kontrola spadku, niezrwnowaone obcienie.
doi:10.12915/pe.2014.01.25
Introduction voltage peak equal to half the total dc-link voltage. This
According to rapid increase of electronic-based devices gives an approximately 15% advantage in dc voltage
applications, the unbalanced and nonlinear loads form the utilization in favor of the four-leg inverter [3]. However, there
main part of the uninterrupted power sources loads. These are some parasitic capacitances between the dc busbars,
nonlinear and unbalanced loads, lead to voltage disturbance packages, heat sinks, and ground, which may yield to some
directly affecting the proper performance of loads and common-mode current flows through long paths involving
inverters. Four-leg inverters, possessing an additional leg ground. These are known to be a source of electromagnetic
compared to the conventional three-leg ones, are able to compatibility (EMC) problems. This issue can be reduced
pass the zero-sequence current of unbalanced and using a large enough choke coil in the neutral conductor [4].
nonlinear loads [1]. The advantage of four-wire inverters Comparing these two topologies indicates that the four-leg
over three-wire ones falls in its current zero sequence inverters show better performance in low voltage utilizations
provision feature. Three-phase unbalanced loads and the especially if the neutral current is significant. However, the
single-phase ones are the origins of zero sequence current, three-leg inverters with split dc-link capacitors perform
where the zero sequence current flows towards the side is better in high voltage utilizations, particularly under
prevented if a Y- transformer is utilized in the output side multilevel application circumstances [2]
of the three-phase three-wire inverter. Comparing a three- In power systems design, the parallel connection of
phase inverter possessing Y- transformer to a three-phase voltage source inverters has been remarkably considered.
four-wire inverter depicts that the four-wire inverter has Reliability improvement, increase in accessibility, power
distinctive advantages over the three-phase inverter with ratings and fault endurance rate, and simpler maintenance
transformer, from size, weight, moving ability, initial are some advantages of the parallel operation of inverters.
manufacturing costs, compatibility, and system total The issues to be considered in parallel inverters operation
efficiency viewpoints. However, there exist some include equal current sharing between inverters (if the
disadvantages such as input/output complexity, fault inverters ratings are equal) and flexibility in the number of
management, and the number of elements in the system parallel units. Several control techniques have been
compared to the three-phase inverter with transformer [2]. proposed to achieve the mentioned targets, classified into
There are two general topologies for four-leg inverters: two general types. The first control type is based on the
three-leg inverters with split dc-link capacitors, and four-leg droop method, which is a kind of wireless interconnection.
inverters in which the neutral point of load is connected to Since this method requires just the local measurement
the mid-point of the fourth leg. The split-link topology is information, it has higher reliability and flexibility, compared
simpler and uses fewer semiconductors (six compared with to the second type. The second control type consists of
eight) but introduces the problem of ensuring close voltage techniques based on the instantaneous load sharing, which
sharing between the split capacitors and the need to can be classified into four general types: central control,
attenuate voltage ripple off them. A large neutral current master-slave control, circular chain control, and average
(produced by either unbalanced or nonlinear loads) causes current sharing [5].
a large perturbation to the split voltages. Such a In parallel operation of three-phase inverters, different
perturbation needs to be compensated for in the phase- methods are proposed up to now to compensate the
voltage control scheme and risks malfunction of the inverter. resultant unbalancing and nonlinear current, majority of
Voltage balancing controllers, such as dynamic hysteresis which utilize three-phase three-wires, while three-phase
current control, have been proposed to overcome the four-wire inverters with split dc-link capacitors is applied
problem, but the zero-sequence current can still cause large only in one case. Applying synchronous reference frame
dc voltage imbalance. The voltage deviation can be (SRF) theory and PI controller on positive sequence of
attenuated by using larger dc-link capacitors but with an inverter voltage is proposed in [6]. In [7], a method based on
obvious penalty in cost and size. The split-link topology the aggregation of PI controllers and SRF on positive and
requires that the phase voltage peak is less than or equal to negative sequences of inverter output voltage is suggested.
the split dc-link voltage (normally half the total dc-link Negative sequence compensation through shunt converter
voltage), whereas the four-leg inverter can allow a line- [8-9] and through series converter [10] is also investigated.
s1 : 2 2 K c K i cut 0
1 K p 2cut K cGC
s 0 : 02 1 K p 0
(6)
K i 5cut 5 s K i 7cut 7 s (9) Vc G s Vc* Z o s I o
s 2 2cut 5 s 0 s 2 2cut 7 s 0
2 2
where G(s) and Zo (s) are the control transfer function and
the output-impedance transfer function, respectively, and
L
(7) kc are given as follows:
GT
Gv s LL s kcG
where L is the output inductor of the inverter, G is the gain (10) G s
1 rL kcG Cs LCs 2 Gv s LL s kcG
of the converter, and T is the sampling time.
VC* Kicut s I L* rL kcG sL
KP
1 s
(11) Zo s
s 2
2cut s 02 1 s 1 rL kcG Cs LCs 2 Gv s LL s kcG
VC Ki 3cut 3 s
KP In (10), G(s) is the closed-loop transfer function of the
s 2 2cut 3 s 02 voltage loop. The open-loop transfer function of the voltage
loop is given by
Ki 5cut 5 s
KP
s 2 2cut 5 s 02 Gv s LL s kc G
(12) Gop s
Ki 7cut 7 s 1 rL kc G Cs LCs 2
KP
s 2 2cut 7 s 02
The overall block diagram of voltage control loop based
on the proportional-resonant control is shown in Fig. 10.
Fig. 8. Proportional-multiresonant controller for fundamental and
harmonic (third, fifth and seventh) components Parallel Operation of Four-Leg Inverters
In this paper, the control aim is to uniformly share the
Bode Diagram
100 currents of output unbalanced and nonlinear loads of
inverters such that an appropriate voltage is applied across
50
the output loads. In this next section, to illustrate the
Magnitude (dB)
-90
The active and reactive power shared by the converter
-180
are evaluated from the measured signals. The output
-270 capacitor voltage Vc and the output current shared by the
10
0
10
2
10
4
10
6
converter Io are used to determine the instantaneous active
Frequency (rad/sec) and reactive power as follows:
Fig. 9. Bode plot of voltage loop for different values of Ki3 , Ki5 and
Ki7 (in Ohm inverse).
Pi Vc I o
(13)
Qi Vc I o 90
The current controller outputs are added with the
feedfarward output capacitor voltages to relieve the burden
on the current controllers. Next, three inverter reference where Pi and Qi are the instantaneous active and reactive
voltages are given to the power circuit through the powers, respectively. The 90 phase shift in Io is required
modulator and driver. to calculate the reactive power. Then, Pi and Qi are
Concentrating on the controller part, (equation (8) can be processed by low-pass filters (LPFs) in order to eliminate
written from (6) the following: the oscillatory component. The cutoff frequencies of the
(8)
Vi Vc* Vc Gv s LL s I L kcG
LPFs are selected as one decade below the line frequency.
Fig. 10. Block diagram of the voltage control loop based on the proportional-resonant control.
Vca Pa E*
RD I oa
Vcb Pb P3 ph Em*
m Vca*
Vcc Pc
I oa Qa * 120 RD I ob
Q3 ph ref Vcb*
I ob Qb
n 120 RD I oc
I oc Qc
Vcc*
Fig. 11. Block diagram of the voltage control loop based on the proportional-resonant control
*
Em E * nP3 ph E * n Pa Pb Pc Fig. 12 shows the three-phase voltage generated by the
(14) parallel inverters. As it can be observed, the generated
ref * mQ3 ph * m Qa Qb Qc voltage has a three-phase sinusoidal form, despite the
existence of nonlinear and unbalanced loads.
The droop characteristics guarantee to bring the phase 400
0
C. Voltage Reference Generation With Virtual Resistive
Output-Impedance Loop
* -200
With the help of the generated amplitudes ( Em ) and
frequency ( ref ), the voltage references can be obtained
-400
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
as Time (sec)
Vca* Em sin ref t RD I oa
*
Fig. 12. The output voltage of parallel four-leg inverters.
* *
(15)
*
Vcb Em sin ref t 120 RD I ob
Table 1. Power circuit and control parameters values
Parameters Values
Vcc Em* sin ref t 120 RD I oc
Vc
fs
380 v
5kHz
L 3 mH
In (15), RD represents the virtual resistive output R 0.1
impedance.
C 10 F
The Block diagram of the voltage control loop based on
proportional-resonant control is shown in Fig. 10. Fig 11 kc 1.28
illustrates the block diagram of parallel four-leg inverters kp 0.0125 1
control system based on droop and virtual resistive output ki 1.8 1
impedance loops, used to generate the reference voltage. ki3 6 1
ki5 6 1
Simulation Results
The structures of two parallel four-leg inverters in ki7 6 1
presence of nonlinear and harmonic loads are simulated to cut1 31.41 rad / sec
investigate the accuracy of the performance and operation cut 3 92.23 rad / sec
of the proposed system. The power system parameters and
the inverter control parameters are listed in Table I. cut 5 157.08 rad / sec
In order to evaluate the dynamic performance of the cut 7 219.9 rad / sec
proposed system, a nonlinear load is connected to the 108 sec
inverters in the [0 0.1Sec] time interval and an unbalanced
load is then added to the previous load in t = 0.1Sec. 15 sec
0
Transactions on Industrial Electronics, 55(2008) , no. 8, 2845
2859.
-10
[6] M. Illindala and G. Venkataramanan, Control of distributed
-20 generation systems to mitigate load and line imbalances,
-30
Proc. 33rd Annu. IEEE PESC, (2002), 20132018.
[7] P. Hsu and M. Behnke, A three-phase synchronous frame
-40
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 controller for unbalanced load, Proc. 29th Annu. IEEE PESC,
Time (sec) (1998), 13691374.
Fig. 13. The three-phase current of nonlinear and unbalanced loads [8] Y. Li, D. M. Vilathgamuwa, and L. P. Chiang, Microgrid power
at the output of parallel four-leg inverters. quality enhancement using a three-phase four-wire grid-
interfacing compensator, IEEE Trans. Ind. Appl., 41(2005), no.
40
Inv1 Current 6, 17071719.
30 Inv2 Current [9] H. S. Song and K. H. Nam, Dual current control scheme for
Load Current
20 PWM converter under unbalanced input voltage conditions,
IEEE Trans. Ind. Electron., 46, (1999), no. 5, 953959, 1999.
10
[10] W. C. Lee, T. K. Lee, and D. S. Hyun, A three-phase parallel
Current (A)