HEAT EXCHANGERS-2

Prabal Talukdar
Associate Professor
Department of Mechanical Engineering
IIT Delhi
E-mail: prabal@mech.iitd.ac.in
p

P.Talukdar/ Mech-IITD
Multipass and Crossflow

The subscripts 1 and 2 represent the inlet and


outlet, respectively..
T and t represent the shell- and tube-side
temperatures respectively
temperatures,

P.Talukdar/ Mech-IITD
T and t represent the shell-
and tube
tube-side
side temperatures
temperatures,
respectively

P.Talukdar/ Mech-IITD
P.Talukdar/ Mech-IITD
Design with LMTD
LMTD method is very suitable for determining the size of a heat
exchanger
h tto realize
li prescribed
ib d outlet
tl t ttemperatures
t when
h ththe mass flflow
rates and the inlet and outlet temperatures of the hot and cold fluids are
specified.

With the LMTD method, the task is to select a heat exchanger that will
meet the prescribed heat transfer requirements. The procedure to be
followed by the selection process is:

Select-type Determine- Inlet, Oulet Calculate Tlm


off Heat
H t t
temp, Heat
H t transfer
t f rate
t and F if neccessary
Exchanger Using energy balance

Obtain U Calculate As

P.Talukdar/ Mech-IITD
Alternative of LMTD
A second kind of problem encountered in heat exchanger analysis is the
determination of the heat transfer rate and the outlet temperatures of the
hot and cold fluids for prescribed fluid mass flow rates and inlet temperatures
when the type and size of the heat exchanger are specified.
specified

The heat transfer surface area A of the heat exchanger in this case is known,
but the outlet temperatures
p are not. Here the task is to determine the heat
transfer performance of a specified heat exchanger or to determine if a heat
exchanger available in storage will do the job.

The LMTD method could still be used for this alternative problem, but the
procedure would require tedious iterations, and thus it is not practical. In an
attempt to eliminate the iterations from the solution of such problems, Kays
andd L
London
d came up with i h a method
h d in
i 1955 called
ll d the
h effectivenessNTU
ff ti NTU
method, which greatly simplified heat exchanger analysis
P.Talukdar/ Mech-IITD
Effectiveness-NTU
Effectiveness NTU method
Effectiveness
.
Q Actual heat transfer rate
= =
Q max Maximum possible heat transfer rate

Actual heat transfer rate


.
Q = Cc (Tc,outt Tc,in
i ) = C h (Th ,in
i Th , outt )

Maximum temperature difference that can occurs


Tmax = Th ,in
i Tc,in
i
Maximum possible heat transfer
.
Q max = C min (Th ,in Tc,in )

P.Talukdar/ Mech-IITD
Maximum heat transfer
The heat transfer in a heat exchanger will reach its maximum value
when
(1) the cold fluid is heated to the inlet temperature of the hot fluid or
(2) The hot fluid is cooled to the inlet temperature of the cold fluid.

These two limiting conditions will not be reached simultaneously


unless the heat capacity rates of the hot and cold fluids are
identical (i
(i.e., ) When Cc Ch, which is usually the case
e Cc = Ch). case,
the fluid with the smaller heat capacity rate will experience a larger
temperature change, and thus it will be the first to experience the
maximum temperature,
p , at which point
p the heat transfer will come to
a halt.
Maximum possible heat transfer
.
Q max = Cmin ( Th ,in Tc ,in )

P.Talukdar/ Mech-IITD
Example

P.Talukdar/ Mech-IITD
Example-
C
Contd.
d

P.Talukdar/ Mech-IITD
Example
-Contd.
C td

The temperature rise of the cold fluid in a


heat exchanger will be equal to the
temperature drop of the hot fluid when the
mass flow rates and the specific heats of
the hot and cold fluids are identical.
P.Talukdar/ Mech-IITD
Effectiveness relation
parallel-flow double-pipe heat exchanger
. C
Q = Cc (Tc, out Tc,in ) = C h (Th ,in Th , out ) T h , out = Th ,in c (Tc,out Tc,in )
Ch

Th ,out Tc,out 1 1 Th ,out Tc,out UA s Cc


ln = UA s + ln = 1 +
Th ,in Tc,in
m h C ph m
& & c C pc Th ,in Tc,in Cc C h

and after adding and subtractingTc, in gives

C
Th ,in Tc,in + Tc,in Tc,out c (Tc,out Tc,in )
Ch UA s Cc
ln = 1 +
Th ,in Tc,in Cc C h

C Tc, out Tc,in UA s Cc


simplifies to ln 1 1 + c = 1 +
C h Th ,in Tc,in Cc C h
P.Talukdar/ Mech-IITD
Effectiveness relation
We now manipulate the definition of effectiveness to obtain
.
Q Cc (Tc, out Tc,in ) Tc, out Tc,in C
= =
= min
. C min (Th ,in Tc,in ) Th ,in Tc,in Cc
Q max

C Tc,out Tc,in UA s Cc
ln 1 1 + c = 1 +
Taking either Cc or Ch to be Cmin (both C h Th ,in Tc,in Cc C h
approaches give the same result), the
relation above can be expressed more
conveniently as results
UA s Cc
1 exp 1 +
UA s C min Cc C h
1 exp 1 + parallel _ flow =
C min C max C min Cc
pparallel _ flow = 1 +
C i Cc C h
1+ min
C max
P.Talukdar/ Mech-IITD
NTU
UAs UAs
NTU = =
Number of transfer units C min .
(m C p ) min

C min
Capacity ratio c=
C max

NotethatNTUisproportionaltoA
Note that NTU is proportional to As .
Therefore,forspecifiedvaluesofUand
Cmin,thevalueofNTUisameasureof
theheattransfersurfaceareaAs .Thus, UA s C min
1 exp 1 +
thelargertheNTU,thelargertheheat
parallel _ flow = C min C max
exchanger. C
1 + min
C max

= function ( UAs / C min , C min / C max ) = function( NTU, c)


P.Talukdar/ Mech-IITD
P.Talukdar/ Mech-IITD
Effectiveness for heat
exchangers (from Kays and London, Ref. 5).

P.Talukdar/ Mech-IITD
Effectiveness for heat
exchangers (from Kays and London, Ref. 5).

P.Talukdar/ Mech-IITD
Effectiveness for heat
exchangers (from Kays and London, Ref. 5).

P.Talukdar/ Mech-IITD
Discussions
1. The value of the effectiveness ranges from 0 to 1.
It increases rapidly with NTU for small values (up
to about NTU 1.5) but rather slowly for larger
values. Therefore, the use of a heat exchanger with
a large NTU (usually larger than 3) and thus a
l
large size
i cannot beb justified
j ifi d economically,
i ll since
i a
large increase in NTU in this case corresponds to a
small increase in effectiveness. Thus, a heat
exchanger
g with a veryy high
g effectiveness mayy be
highly desirable from a heat transfer point of view
but rather undesirable from an economical point of
view.
2 For a given
2. gi en NTU and capacit
capacity ratio c = Cmin
/Cmax, the counter-flow heat exchanger has the
highest effectiveness, followed closely by the
cross-flow heat exchangers with both fluids
unmixed.

P.Talukdar/ Mech-IITD
Discussions
3. The effectiveness of a heat exchanger is
independent of the capacity ratio c for
NTU values of less than about 0.3.
4. The value of the capacity ratio c ranges between
0 and 11. For a given NTU,
NTU the effectiveness
becomes a maximum for c = 0 and a minimum
for c = 1. The case c = Cmin /Cmax 0
corresponds to Cmax , which is realized
d i a phase-change
during h h process iin a condenser
d or
boiler. All effectiveness relations in this case
reduce to = max = 1 - exp(NTU) regardless of
yp of heat exchanger.
the type g Note that the
temperature of the condensing or boiling fluid
remains constant in this case. The effectiveness
is the lowest in the other limiting case of c =
Cmin/Cmax = 1,1 which
hich is realized
reali ed when
hen the heat
capacity rates of the two fluids are equal.
P.Talukdar/ Mech-IITD
Conclusions
Note that the analysis
y of heat exchangers
g with unknown outlet temperatures
p is
a straight forward matter with the effectivenessNTU method but requires
rather tedious iterations with the LMTD method.

When all
Wh ll the
th inlet
i l t andd outlet
tl t ttemperatures
t are specified,
ifi d the
th size
i off the
th heat
h t
exchanger can easily be determined using the LMTD method.

Alternatively, it can also be determined from the effectivenessNTU method


Alternatively
by first evaluating the effectiveness from its definition and then the NTU
from the appropriate NTU relation given in tabular form.

P.Talukdar/ Mech-IITD
Compact heat exchangers

P.Talukdar/ Mech-IITD
P.Talukdar/ Mech-IITD